SIRIUS 3RV2 motor starter protectors Parts
























Compare SIRIUS 3RV2 motor starter protectors
Key specifications of the parts listed on this page, taken from the manufacturer's data sheets.
| MPN | continuous current rated value | Net Weight | adjustable current response value current of the current-dependent overload release | operational current rated value | response value current of instantaneous short-circuit trip unit |
|---|---|---|---|---|---|
| 3RV2021-0DA10-0DA0 | 0.32 A | 259.6 g | 0.22 ... 0.32 A | 0.32 A | 4.2 A |
| 3RV2021-0DA10 | 0.32 A | 0.263 kg | 0.22 ... 0.32 A | 0.32 A | 4.2 A |
| 3RV2021-0CA10-0DA0 | 0.25 A | 0.261 kg | 0.18 ... 0.25 A | 0.25 A | 3.3 A |
| 3RV2021-4EA10-0BA0 | 32 A | 355.6 g | 27 ... 32 A | 32 A | 400 A |
| 3RV2021-4EA10-Z X95 | 32 A | 351.6 g | 27 ... 32 A | 32 A | 400 A |
| 3RV2021-4EA10-Z W97 | 32 A | 351.6 g | 27 ... 32 A | 32 A | 400 A |
| 3RV2021-4EA10-Z W96 | 32 A | 351.6 g | 27 ... 32 A | 32 A | 400 A |
| 3RV2021-4EA10 | 32 A | 351.6 g | 27 ... 32 A | 32 A | 400 A |
| 3RV2021-4DA25 | 25 A | 412.6 g | 18 ... 25 A | 25 A | 325 A |
| 3RV2032-4RA15 | 80 A | 1.186 kg | 70 ... 80 A | 80 A | 1 040 A |
| 3RV2032-4RA10-Z X95 | 80 A | 1.179 kg | 70 ... 80 A | 80 A | 1 040 A |
| 3RV2032-4KA10 | 73 A | 1.164 kg | 62 ... 73 A | 73 A | 949 A |
| 3RV2032-4JA15 | 65 A | 1.18 kg | 54 ... 65 A | 65 A | 845 A |
| 3RV2032-4JA10-Z X95 | 65 A | 1.173 kg | 54 ... 65 A | 65 A | 845 A |
| 3RV2031-4JB10 | 65 A | 1.214 kg | 54 ... 65 A | 65 A | 845 A |
| 3RV2031-4JA15 | 65 A | 1.185 kg | 54 ... 65 A | 65 A | 845 A |
| 3RV2031-4JA10-0BA0 | 65 A | 1.16 kg | 54 ... 65 A | 65 A | 845 A |
| 3RV2031-4DB15 | 25 A | 1.082 kg | 18 ... 25 A | 25 A | 325 A |
| 3RV2031-4DB10 | 25 A | 1.074 kg | 18 ... 25 A | 25 A | 325 A |
| 3RV2031-4DA15 | 25 A | 1.066 kg | 18 ... 25 A | 25 A | 325 A |
| 3RV2411-1DA10 | 3.2 A | 326.6 g | 2.2 ... 3.2 A | 3.2 A | 65 A |
| 3RV2411-1CA20-0DA0 | 2.5 A | 0.34 kg | 1.8 ... 2.5 A | 2.5 A | 52 A |
| 3RV2411-1CA20 | 2.5 A | 344.6 g | 1.8 ... 2.5 A | 2.5 A | 52 A |
| 3RV2411-1CA15 | 2.5 A | 336.18 g | 1.8 ... 2.5 A | 2.5 A | 52 A |
Common to all listed parts
| Product equipment of circuit breaker for motor protection complete unit with protection device | Yes |
| product function disconnector functionality | Yes |
| product extension auxiliary switch | Yes |
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| reference code according to IEC 81346-2 | Q |
| installation altitude at height above sea level maximum | 2 000 m |