Control Signal Terminal Strip; Westfalen Weser Netz Version; according to § 9 EEG; 2,50 mm²; gray
Control Signal Terminal Strip; E.ON Version; according to § 14a EnWG; 2,50 mm²; gray
Control Signal Terminal Strips per § 14a EnWG
Due to the Energy Industry Act (EnWG), system operators whose connection power is greater than 4.2 kW (usually wallboxes or heat pumps for private households) are obligated to install throttle devices that can be controlled by the grid operator in an emergency to ensure grid stability in the event of excessive power consumption. For this purpose, WAGO offers the Control Signal Terminal Strips according to § 14a EnWG as an interface between consumers and grid operators, which were developed in cooperation with grid operators according to the valid TABs. They offer the advantages of a uniform structure, standards and meet the requirements for clear separation of load and control current.
These sets are delivered ready for installation and without a DIN-rail for the end user. They are developed for the German energy market.
| Ratings per | IEC/EN 60947-7-1 |
| Nominal voltage (III/3) | 400 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Rated current | 16 A |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
| Ratings per | IEC/EN 60947-7-1 / IEC/EN 60947-7-1 / IEC/EN 60947-7-1 |
| Overvoltage category | III / III / II |
| Pollution degree | 3 / 2 / 2 |
| Nominal voltage | 400 V |
| Rated impulse withstand voltage | 6 kV |
| Rated current | 16 A |
| Approvals per | UL 1059 |
| Rated voltage UL (Use Group B) | 300 V |
| Rated current UL (Use Group B) | 15 A |
| Rated voltage UL (Use Group C) | 300 V |
| Rated current UL (Use Group C) | 15 A |
| Approvals per | UL 1059 / UL 1059 / UL 1059 |
| Use group | B / C / D |
| Rated voltage | 300 V / 300 V |
| Rated current | 15 A / 15 A |
| Approvals per | CSA 22.2 No 158 |
| Rated voltage CSA (Use Group B) | 300 V |
| Rated current CSA (Use Group B) | 15 A |
| Rated voltage CSA (Use Group C) | 300 V |
| Rated current CSA (Use Group C) | 15 A |
| Approvals per | CSA 22.2 No 158 / CSA 22.2 No 158 / CSA 22.2 No 158 |
| Use group | B / C / D |
| Rated voltage | 300 V / 300 V |
| Rated current | 15 A / 15 A |
| Ratings per | ATEX: PTB 20 ATEX 1007 U / IECEx: PTB 20.0013U (Ex ec IIC Gc) |
| Rated voltage EN (Ex e II) | 440 V |
| Rated current (Ex e II) | 17 A |
| Power loss, per pole (potential) | 0.341 W |
| Rated current I<sub>N</sub> for power loss specification | 16 A |
| Resistance value for specified, current-dependent power loss | 0.001 Ω |
| Wiring direction | Front-entry wiring |
| Clamping units | 12 |
| Total number of potentials | 6 |
| Number of levels | 1 |
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Push-button |
| Connectable conductor materials | Copper |
| Nominal cross-section | 2.5 mm² |
| Solid conductor | 0.25 … 4 mm² / 22 … 12 AWG |
| Solid conductor; push-in termination | 0.75 … 4 mm² / 18 … 12 AWG |
| Fine-stranded conductor | 0.25 … 4 mm² / 22 … 12 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.25 … 2.5 mm² / 22 … 14 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 1 … 2.5 mm² / 18 … 14 AWG |
| Note (conductor cross-section) | Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination. |
| Strip length | 10 … 12 mm / 0.39 … 0.47 inches |
| Wiring direction | Front-entry wiring |
| Width | 44.2 mm / 1.74 inches |
| Height | 66.1 mm / 2.602 inches |
| Depth from upper-edge of DIN-rail | 32.9 mm / 1.295 inches |
| Depth | 39.5 mm / 1.555 inches |
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
| Note (material data) | Information on material specifications can be found here |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 1.326 MJ |
| Actuator color | orange |
| Weight | 55.6 g |
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
| PU (SPU) | 1 pcs |
| Packaging type | Box |
| Country of origin | DE |
| GTIN | 4066966781250 |
| Customs tariff number | 85369010000 |
| ETIM 9.0 | EC000902 |
| ETIM 10.0 | EC000902 |
| ECCN | NO US CLASSIFICATION |
| RoHS Compliance Status | Compliant,No Exemption |
821-509 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 821-509 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 821-509, subject to availability and destination.

Control Signal Terminal Strip; Westfalen Weser Netz Version; according to § 9 EEG; 2,50 mm²; gray




Control Signal Terminal Strip; DIN VDE 4100:2025-05 Version; according to § 14a EnWG; (TAB Westnetz,TAB EWR Remscheid, etc.)

Control Signal Terminal Strip; AVU Gevelsberg Version; according to § 14a EnWG; 2,50 mm²; gray

Control Signal Terminal Strip; Vers. Ava. / Ener. / CUN / BS-Netz / LSW; according to § 14a EnWG; 2,50 mm²; gray