8-Port IO-Link Master Class A; Profinet; DC 24 V / 2.0 A; 8xM12 connection; WideLine
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | I/O Systems |
| Lifecycle | active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
Shipping & availability
When can 765-4101/100-000 be shipped?
765-4101/100-000 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 765-4101/100-000 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 765-4101/100-000 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 765-4101/100-000, subject to availability and destination.
<p>Application:</p><p>Decentralized processing of digital and IO-Link signals</p><p> </p><p>The device controls IO-Link-capable digital field devices (e.g., actuators and hubs) and records digital signals from IO-Link-capable field devices (e.g., sensors and hubs) that are sent or received by a higher-level controller. The device is designed as a Class A master and offers 8 IO-Link ports or 16 digital inputs/outputs.</p><p> </p><p>IO-Link:</p><p>The device has several IO-Link communication interfaces for interoperation with IO-Link devices.</p><p>The IO-Link interface enables direct access to the process and diagnostic data and allows the parameters of the connected devices to be set during operation.</p><p>The IODD can also be <a href="https://ioddfinder.io-link.com">https://ioddfinder.io-link.com</a> downloaded via the IODDfinder.</p>
Specifications
Technical data - Fieldbus
| Communications | PROFINET, PROFINET IO device; 2-port switch, LLDP, MRP, SNMP |
| Connection technology: communication/fieldbus | 2 x D-coded M12; 4-pole |
| Interface standard | 10BASE-T/100BASE-TX; potential-free |
| Autonegotiation; autocrossover | yes |
| PROFINET IO features | PROFINET IO device; 2-port switch, LLDP, MRP, SNMP |
Technical data - Device functions
| Parameter | Input filter, Output current, Temperature |
| Diagnostics | Undervoltage; Overcurrent; Overload; Overtemperature |
| Device functions | Bluetooth®, OPC UA server |
| Visualization | Android/iOS app, Web server |
Technical data - IO-Link master
| IO-Link master classification | Class A; V1.1 specification |
| Port-Modus | IO-Link: autoconfig, manual, tool-based, DI, DO |
| Cycle time | 400 μs (min.) |
| Operating mode | IO-Link master, DI or DO (adjustable for pin 4 per port); DI or DO (adjustable for pin 2 per port) |
Technical data - IO-Link ports
| Number of digital inputs | 16 |
| Number of digital outputs | 16 |
| Connection technology: I/O | 8 x A-coded M12; 5-pole |
| Signal type (voltage) | 24 VDC |
| Input characteristic | High-side switching |
| Input filter | 0.2 … 20 ms |
| Input characteristic | Type 3, per IEC 61131-2 |
| Output current (per channel) | 2 A (typ.) for DO |
| Supply current per port | 1L: 1 A for IO-Link; 4 A (max.) for DIO |
Technical data - Supply (module)
| Connection technology: supply | 2 x L-coded M12; 5-pole |
| Supply voltage | 24 VDC (18 … 31.2 V); 1L |
| Current consumption (max.) | 16000 mA |
| Current consumption (note) | per supply line; overload- and short-circuit-protected |
| Reverse voltage protection | Yes |
Physical data
| Width | 60 mm / 2.362 inches |
| Height | 30 mm / 1.181 inches |
| Depth | 210 mm / 8.268 inches |
Material data
| Weight | 610 g |
| Conformity marking | CE |
Environmental requirements
| Ambient temperature (operation) | -25 … +70 °C |
| Ambient temperature (storage) | -40 … +80 °C |
| Protection type | IP67 |
| Protection class | III per EN 61140, IEC 61140, VDE 0140-1 |
| Pollution degree | 3 (EN 60664-1) |
| Operating altitude | 0 … 2000 m / 0 … 6562 ft |
| Relative humidity (without condensation) | 95 % |
| Vibration resistance | 5g per IEC 60068-2-6 |
| Shock resistance | Short-term: 50g/11 ms/half-sine per IEC 60068-2-27; Long-term: 30g/6 ms/half-sine per IEC 60068-2-29 |
| EMC immunity to interference | per EN 61000-6-2 |
| EMC emission of interference | per EN 61000-6-4 |
Commercial data
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4055143949996 |
| Customs tariff number | 85371098990 |
Product Classification
| UNSPSC | 32151705 |
| ETIM 9.0 | EC001601 |
| ETIM 10.0 | EC001601 |
| ECCN | NO US CLASSIFICATION |
Environmental Product Compliance
| CAS-No. | 7439-92-1 |
| REACH Candidate List Substance | Lead |
| RoHS Compliance Status | Compliant,No Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I |
| SCIP notification number (Austria) | 3d1b5f75-0483-45fd-94ce-081697512ae4 |
| SCIP notification number (Belgium) | 2345134c-9018-4565-95d4-8989d408f3d5 |
| SCIP notification number (Bulgaria) | 3ebe2820-3366-4690-b9b3-41b90079f1b9 |
| SCIP notification number (Czech Republic) | 94b741cb-a59a-4c93-ab8e-fe235a561502 |
| SCIP notification number (Denmark) | 0adc9ac4-e60d-46c0-bfa9-6e30b0c06044 |
| SCIP notification number (Finland) | d26c4196-9345-490c-bc64-07e80b4d51b5 |
| SCIP notification number (France) | f1567d28-637b-4580-b962-7fc67b19afd7 |
| SCIP notification number (Germany) | ec77edca-13ab-40d1-b1c0-987ff3355111 |
| SCIP notification number (Hungary) | 2869872b-f535-42f4-847c-eceb43f0a0c2 |
| SCIP notification number (Italy) | f95be9a8-4689-407b-89d1-1a535a82b8bc |
| SCIP notification number (Netherlands) | 46e786b0-3e2d-435a-b6e6-33f69ba20460 |
| SCIP notification number (Poland) | 2bd9299e-30d5-4051-bc95-7c46764e5617 |
| SCIP notification number (Romania) | b8658276-5634-4d52-a5a9-4159c451ac9a |
| SCIP notification number (Sweden) | b3ad0cc5-fb1c-4cef-8923-368ed8406760 |