What is the Wago 753-469?

This analog input module directly connects to two thermocouples. Internal electrical isolation allows operation of grounded sensors.

The module automatically linearizes the entire temperature range.

Cold junction compensation mitigates the clamping unit offset voltage over the 0–55°C operating range.

A line break is indicated by a red LED. A green LED indicates readiness for operation and error-free communication with the coupler.

The shield directly connects to the DIN-rail.

Specifications

Notes

NotePluggable connectors and coding fingers (753 Series) are not included.

Technical data

Number of analog inputs2
Total number of channels (module)2
Signal typeThermocouple
Sensor connection2 x (2-wire)
Data width2 x 16-bit data; 2 x 8-bit control/status (optional)
Internal resistance1000 kΩ
Resolution (over entire range)0.1 °C
Conversion time (typ.)320 ms
Measurement error (25 °C)< ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K)
Temperature coefficient< ±0.2 K/K
Sensor typesThermocouple K
Temperature range−100 … +1370 °C
Cold junction compensationat each pair of terminal blocks
Supply voltage (system)5 VDC; via data contacts
Current consumption (5 V system supply)65 mA
Isolation500 V system/field
IndicatorsLED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2

Connection data

Connection technology: I/O8 x CAGE CLAMP®
Connectable conductor materialsCopper
Connection typeInputs/Outputs
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip length9 … 10 mm / 0.35 … 0.39 inches

Physical data

Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail62.6 mm / 2.465 inches

Mechanical data

Mounting typeDIN-35 rail
Pluggable connectorPluggable

Material data

Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Fire load0.653 MJ
Weight56 g
Conformity markingCE

Environmental requirements

Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-40 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 … 2000 m / 0 … 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Vibration resistance4g per IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2, marine applications
EMC emission of interferenceper EN 61000-6-4, marine applications
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %10 ppm
Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %25 ppm

Commercial data

Product Group15 (I/O System)
PU (SPU)1 pcs
Packaging typebox
Country of originDE
GTIN4045454394493
Customs tariff number85389099990

Product Classification

UNSPSC32101505
eCl@ss 10.027-24-26-01
eCl@ss 9.027-24-26-01
ETIM 9.0EC001596
ETIM 10.0EC001596
ECCNNO US CLASSIFICATION

Environmental Product Compliance

CAS-No.1303-86-2, 1317-36-8, 25550-51-0, 7439-92-1
REACH Candidate List Substance4-Methyl-1,2-cyclohexanedicarboxylic anhydride, Diboron trioxide, Lead, Lead monoxide
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption6(c), 7(a), 7(c)-I, 7(c)-II
SCIP notification number (Austria)47f0972f-5ddb-43fd-88af-3c06eef123f2
SCIP notification number (Belgium)3b8470ad-3c70-4f8b-adb3-22379a5504e4
SCIP notification number (Bulgaria)76e4824e-cb23-4f2f-adf0-3d0c7b83a4f7
SCIP notification number (Czech Republic)b69f7d30-86fe-445c-ae77-d65dcf8416f7
SCIP notification number (Denmark)1bd9dfa0-42fe-4f08-b716-3f0b4f3b3201
SCIP notification number (Finland)4f8760e6-a141-460d-9525-6878106a3195
SCIP notification number (France)258d3c82-b64f-4e16-b73e-7e1db18422b5
SCIP notification number (Germany)273e1d5c-d668-4155-b4d0-a9d320c43155
SCIP notification number (Hungary)ab384b18-8330-4dac-8e12-24a67fe4b62a
SCIP notification number (Italy)afc9d2e8-bff3-494b-ba5f-deb355657079
SCIP notification number (Netherlands)8fd69244-4f89-4351-9b5c-bf643cad89c8
SCIP notification number (Poland)0be8a598-003f-41a2-a20f-5b4c284bb5dc
SCIP notification number (Romania)48a25004-5aba-4a6f-8adb-4022119c3135
SCIP notification number (Sweden)8c33ca30-1720-4dbc-bde7-d2742ffaf370

753-469: frequently asked questions

When can 753-469 be shipped?

753-469 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 753-469 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 753-469 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 753-469, subject to availability and destination.

More Wago parts

Wago 753-461/003-000 – 2-channel analog input; For Pt100/RTD resistance sensors; Adjustable
Wago
753-461/003-000

2-channel analog input; For Pt100/RTD resistance sensors; Adjustable

Wago 753-465 – 2-channel analog input; 0 … 20 mA; Single-ended
Wago
753-465

2-channel analog input; 0 … 20 mA; Single-ended

Wago 753-466 – 2-channel analog input; 4 … 20 mA; Single-ended
Wago
753-466

2-channel analog input; 4 … 20 mA; Single-ended

Wago 753-467 – 2-channel analog input; 0 ... 10 VDC; Single-ended
Wago
753-467

2-channel analog input; 0 ... 10 VDC; Single-ended

Wago 753-469/003-000 – 2-channel analog input; Thermocouple K; Diagnostics, adjustable
Wago
753-469/003-000

2-channel analog input; Thermocouple K; Diagnostics, adjustable

Wago 753-472 – 2-channel analog input; 0 … 20 mA; Single-ended; 16 bits
Wago
753-472

2-channel analog input; 0 … 20 mA; Single-ended; 16 bits

Wago 753-474 – 2-channel analog input; 4 … 20 mA; Single-ended; 16 bits
Wago
753-474

2-channel analog input; 4 … 20 mA; Single-ended; 16 bits

Wago 753-475 – 2-channel analog input; 0 … 1 A AC/DC; Differential input
Wago
753-475

2-channel analog input; 0 … 1 A AC/DC; Differential input

Wago 753-469Price and lead time confirmed within 1 business day
Request a Quote