Wago 750-889
Controller KNX IP
- MPN
- 750-889
- Category
- Controller
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
- 100% positive eBay feedback
What is the Wago 750-889?
This controller can accommodate up to two KNX logic devices at the same time.
1. In conjunction with the WAGO I/O System, the KNX IP Controller is used as a user-programmable application controller within KNX IP networks. The controller supports all digital, analog and specialty modules found within the 750/753 Series. The IEC 61131-3 programmable controller is capable of 10/100 Mbit/s data rates. KNX objects of any type (EIS/DPT) can be created using the programming tool. Libraries including pre-made function blocks are readily available on the WAGO Website for programming. The controller supports a maximum of 253 communication objects, as well as 254 group addresses and associations.
2. Combined with the KNX/EIB/TP1 Module, the 750‐889 KNX IP Controller operates as a router on an IP backbone (ETHERNET). No IEC application is required for router functionality.
Both devices are commissioned and configured via ETS software using the WAGO product database. The software includes a plug‐in that automatically installs and opens for configuration.
The KNX IP Controller features an integrated 2‐port 10/100 Mbit/s switch, allowing a line structure to be easily created without additional network components. The maximum number of controllers that can be wired in series is 20.
An internal server is available for Web-based applications.
The controller provides 1024 KB program memory, 1024 KB data memory and 32 KB retain memory. It is capable of multitasking, has a battery-backed, real-time clock and is based on a 32-bit CPU.
The controller offers many different application protocols for control tasks (MODBUS, KNXnet/IP) or for system management and diagnostics (HTTP, BootP, DHCP, DNS, AutoIP, SNTP, FTP, SNMP and SMTP).
The number of KNX/EIB/TP1 Modules (750‐646) supported by the KNX IP Controller does not depend on the application.
Specifications
Notes
| Note | The WAGO ETS3/4 plug-in is a component of the WAGO-ETS3 product databank and can be downloaded for free at www.wago.com. |
Technical data
| Communications | KNX IP, Modbus (TCP, UDP), ETHERNET |
| ETHERNET protocols | HTTP, BootP, DHCP, DNS, AutoIP, SNTP, FTP, SNMP V3, SMTP |
| Visualization | Web-Visu |
| CPU | 32 bits |
| Programming languages per IEC 61131-3 | Instruction List (IL), Ladder Diagram (LD), Function Block Diagram (FBD), Continuous Function Chart (CFC), Structured Text (ST), Sequential Function Chart (SFC) |
| Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
| Configuration options | WAGO-I/O-CHECK, Web-Based Management |
| Device specification | KNX/TP1 bus specification: 1.0 |
| Network length (max.) | ≤ 2000 m; max. 20 controllers in series |
| Transmission rate | 10/100 Mbit/s |
| Bus segment length (max.) | 100 m |
| Transmission medium (communication/fieldbus) | S-UTP; 100 Ω; Cat. 5 |
| Program memory | 1024 KB |
| Data memory | 1024 KB |
| Non-volatile software memory | 32 kbyte |
| Memory for fieldbus input variables (max.) | 512 Byte |
| Memory for fieldbus output variables (max.) | 512 Byte |
| Type of memory card | SD and SDHC up to 32 GB (all guaranteed properties only valid with WAGO's memory card) |
| Memory card slot | Push-push mechanism; Cover lid (sealable) |
| Number of modules per node (max.) | 250 |
| Number of modules without a bus extension (max.) | 64 |
| Input and output process image (fieldbus) max. | 1020 words/1020 words |
| Device-specific | Number of group addresses: 254; Number of communication objects: 253 |
| Powerfail RTC buffer | 6 days (min.) |
| Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS/PRG IP, NS/PRG RT) red/green: IP device programming mode, router; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply |
| Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
| Input current (typ.) at nominal load (24 V) | 500 mA |
| Power supply efficiency (typ.) at nominal load (24 V) | 90 % |
| Current consumption (5 V system supply) | 450 mA |
| Total current (system supply) | 1,700 mA |
| Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
| Current carrying capacity (power jumper contacts) | 10 A |
| Number of outgoing power jumper contacts | 3 |
| Isolation | 500 V system/field |
| KNX certified | IP Controller: 61/8316/08; IP Router: 61/8317/08 |
Connection data
| Connection technology: communication/fieldbus | KNX IP: 2 x RJ-45; Modbus (TCP, UDP): 2 x RJ-45 |
| Connection technology: system supply | 2 x CAGE CLAMP® |
| Connection technology: field supply | 6 x CAGE CLAMP® |
| Connectable conductor materials | Copper |
| Connection type | System/field supply |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Connection technology: device configuration | 1 x Male connector; 4-pole |
Physical data
| Width | 61.5 mm / 2.421 inches |
| Height | 100 mm / 3.937 inches |
| Depth | 71.9 mm / 2.831 inches |
| Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Mechanical data
| Mounting type | DIN-35 rail |
Material data
| Color | gray |
| Housing material | Polycarbonate; polyamide 6.6 |
| Fire load | 2.2 MJ |
| Weight | 192 g |
| Conformity marking | CE |
Environmental requirements
| Mounting type | DIN-35 rail |
| Ambient temperature (operation) | 0 … +55 °C |
| Ambient temperature (storage) | -25 … +85 °C |
| Protection type | IP20 |
| Pollution degree | 2 per IEC 61131-2 |
| Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
| Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
| Relative humidity (without condensation) | 95 % |
| Vibration resistance | 4g per IEC 60068-2-6 |
| Shock resistance | 15g per IEC 60068-2-27 |
| EMC immunity to interference | per EN 61000-6-2 |
| EMC emission of interference | per EN 61000-6-3 |
| Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
| Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 % | 10 ppm |
| Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 % | 25 ppm |
Commercial data
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4055143093330 |
| Customs tariff number | 85371091990 |
Product Classification
| UNSPSC | 32151705 |
| eCl@ss 10.0 | 27-24-26-07 |
| eCl@ss 9.0 | 27-24-26-07 |
| ETIM 9.0 | EC000236 |
| ETIM 10.0 | EC000236 |
| ECCN | NO US CLASSIFICATION |
Environmental Product Compliance
| CAS-No. | 12060-00-3, 1303-86-2, 1317-36-8, 25550-51-0, 693-98-1, 7439-92-1, 79-94-7, 80-43-3 |
| REACH Candidate List Substance | 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol, 2-methylimidazole, 4-Methyl-1,2-cyclohexanedicarboxylic anhydride, Diboron trioxide, Lead, Lead monoxide, Lead titanium oxide (PbTiO3), Peroxide, bis(1-methyl-1-phenylethyl) |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c), 7(a), 7(c)-I, 7(c)-II |
| SCIP notification number (Bulgaria) | 9793eec1-c150-4d81-9410-31c58838db9b |
| SCIP notification number (Czech Republic) | 7a8111e3-7cea-40f7-9c8e-fced1566c9e4 |
750-889: frequently asked questions
When can 750-889 be shipped?
750-889 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 750-889 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 750-889 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 750-889, subject to availability and destination.
More Wago parts




Controller ETHERNET; 3rd Generation; SD Card Slot; Media Redundancy; Ext. Temperature


Controller Modbus TCP; 4th generation; 2 x ETHERNET, SD Card Slot; Ext. Temperature

Controller Modbus TCP; 4th generation; 2 x ETHERNET, SD Card Slot; Ext. Temperature

Controller Modbus TCP; 4th generation; 2 x ETHERNET, SD Card Slot; Telecontrol technology; Ext. Temperature; ECO