What is the Wago 750-458?

This analog input module directly connects to thermocouples.

The module automatically linearizes the entire temperature range.

Cold junction compensation mitigates the clamping unit offset voltage over the 0–55°C operating range.

A line break is indicated by a red LED.

Unused channels can be deactivated.

The module can be configured via WAGO‐I/O‐CHECK or GSD files.

It features multiple setting options and high accuracy.

Specifications

Technical data

Number of analog inputs8
Total number of channels (module)8
Signal typeThermocouple, Low voltages
Signal type (configurable)yes
Sensor connection8 x (2-wire)
Data width8 x 16-bit data; 8 x 8-bit control/status (optional)
Resolution (over entire range)0.1 °C
Conversion time (typ.)100 ms
Measurement error (25 °C)Without cold junction compensation: ≤ ±1 K (type E, N, K, T, J, C); ≤ ±2 K (type S, R); ≤ ±3 K (type B); Cold-junction compensation measurement error: ≤ ±4 K
Temperature error (max.) of the upper-range value0.05 %/K
Sensor typesThermocouple K; Configurable: J, B, E, N, R, S, T, U, C; Voltage sensor: ±30 mV, ±60 mV, ±120 mV, ±240 mV
Temperature rangeSensor-specific
Cold junction compensationinternal and external
Configuration optionsWAGO-I/O-CHECK, CODESYS Library, e!COCKPIT
Supply voltage (system)5 VDC; via data contacts
Current consumption (5 V system supply)100 mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation500 V system/field
IndicatorsLED (1-8) green: Status TC 1 … TC 8; LED (9-16) red: Error TC 1 … TC 8
Number of incoming power jumper contacts2
Number of outgoing power jumper contacts2

Connection data

Connection technology: I/O16 x Push-in CAGE CLAMP®
Connectable conductor materialsCopper
Connection typeInputs/Outputs
Solid conductor0.08 … 1.5 mm² / 28 … 16 AWG
Fine-stranded conductor0.25 … 1.5 mm² / 22 … 16 AWG
Strip length8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69 mm / 2.717 inches
Depth from upper-edge of DIN-rail61.8 mm / 2.433 inches

Mechanical data

Mounting typeDIN-35 rail
Pluggable connectorfixed

Material data

Housing materialPolycarbonate; polyamide 6.6
Fire load0.62 MJ
Weight63 g
Conformity markingCE

Environmental requirements

Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-40 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 … 2000 m / 0 … 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Vibration resistance4g per IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-1; EN 61000-6-2
EMC emission of interferenceper EN 61000-6-3
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %10 ppm
Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %25 ppm

Commercial data

PU (SPU)1 pcs
Packaging typebox
Country of originDE
GTIN4055143350372
Customs tariff number85389099990

Product Classification

UNSPSC32151706
eCl@ss 10.027-24-26-01
eCl@ss 9.027-24-26-01
ETIM 9.0EC001596
ETIM 10.0EC001596
ECCNNO US CLASSIFICATION

Environmental Product Compliance

CAS-No.12060-00-3, 1303-86-2, 1317-36-8, 7439-92-1
REACH Candidate List SubstanceDiboron trioxide, Lead, Lead monoxide, Lead titanium oxide (PbTiO3)
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption6(c), 7(a), 7(c)-I, 7(c)-II
SCIP notification number (Austria)97d7ff78-46f1-4056-8dd2-60c498336e65
SCIP notification number (Belgium)9a4d3221-1995-4de2-8787-cb2633bf2bf3
SCIP notification number (Bulgaria)ddec7740-3867-48a1-a756-dc9d74bb5ce3
SCIP notification number (Czech Republic)afcdd371-5593-4677-8aa3-3abda0fadd63
SCIP notification number (Denmark)63b9f664-a59b-4017-b8a8-cde93e28a0e8
SCIP notification number (Finland)d583aa06-8ccf-40bc-9cd9-fa38372b46db
SCIP notification number (France)627f8c2d-b9c9-4e8a-b5e8-d69a498074a1
SCIP notification number (Germany)bb38c92f-f788-4c3f-a8ee-4c32288228e7
SCIP notification number (Hungary)767dcaa2-031d-49c3-87f4-b96e893e7852
SCIP notification number (Italy)85c5fca1-400f-44da-b489-03d5f7158f58
SCIP notification number (Netherlands)9e6d10a7-fa20-44e8-b489-f50074e29a1e
SCIP notification number (Poland)9c9fbd57-4ef5-46d2-a9b7-28192953ebbd
SCIP notification number (Romania)14d3eeb9-d77a-47d1-9cae-031031d4a532
SCIP notification number (Sweden)d33954a3-788c-4cf7-9af8-8d61fcdce0f7

750-458: frequently asked questions

When can 750-458 be shipped?

750-458 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 750-458 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 750-458 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 750-458, subject to availability and destination.

More Wago parts

Wago 750-456/000-200 – 2-channel analog input; ±10 VDC; Differential input; S5 PLC data format
Wago
750-456/000-200

2-channel analog input; ±10 VDC; Differential input; S5 PLC data format

Wago 750-457 – 4-channel analog input; ±10 VDC; Single-ended
Wago
750-457

4-channel analog input; ±10 VDC; Single-ended

Wago 750-457/025-000 – 4-channel analog input; ±10 VDC; Single-ended; Ext. Temperature
Wago
750-457/025-000

4-channel analog input; ±10 VDC; Single-ended; Ext. Temperature

Wago 750-457/040-000 – 4-channel analog input; ±10 VDC; Single-ended; Extreme
Wago
750-457/040-000

4-channel analog input; ±10 VDC; Single-ended; Extreme

Wago 750-459 – 4-channel analog input; 0 ... 10 VDC; Single-ended
Wago
750-459

4-channel analog input; 0 ... 10 VDC; Single-ended

Wago 750-460 – 4-channel analog input; For Pt100/RTD resistance sensors
Wago
750-460

4-channel analog input; For Pt100/RTD resistance sensors

Wago 750-460/000-003 – 4-channel analog input; For Pt1000/RTD resistance sensors
Wago
750-460/000-003

4-channel analog input; For Pt1000/RTD resistance sensors

Wago 750-460/000-005 – 4-channel analog input; For Ni1000/RTD resistance sensors
Wago
750-460/000-005

4-channel analog input; For Ni1000/RTD resistance sensors

Wago 750-458Price and lead time confirmed within 1 business day
Request a Quote