2-conductor through terminal block; 10 mm²; suitable for Ex e II applications; center marking; for DIN-rail 35 x 15 and 35 x 7.5; CAGE CLAMP®; 10,00 mm²; light gray
2-conductor through terminal block; 185 mm²; lateral marker slots; with fixing flanges; POWER CAGE CLAMP; 185,00 mm²; blue
High-current terminal block, 285 Series, t-wrench und 8 mm
Our through terminal block (item number 285-1164) makes connections quick and easy. Strip lengths must be between 45 and 47 mm when connecting conductors to this through terminal block. This product features conductor terminals and utilizes POWER CAGE CLAMP. Our POWER CAGE CLAMP connection technology is the perfect choice when it comes to securely connecting large conductor cross-sections. This universal connector is reliable and maintenance-free. Unlike other connections methods, you do not need to crimp the ferrule or use a torque wrench. This makes it nice and easy to use. This through terminal block is suitable for conductor cross sections ranging from 50 mm² to 185 mm².
| Ratings per | IEC/EN 60947-7-1 |
| Nominal voltage (III/3) | 1000 V |
| Rated impulse withstand voltage (III / 3) | 12 kV |
| Rated current | 353 A |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
| Ratings per | IEC/EN 60947-7-1 / IEC/EN 60947-7-1 / IEC/EN 60947-7-1 |
| Overvoltage category | III / III / II |
| Pollution degree | 3 / 2 / 2 |
| Nominal voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated current | 353 A |
| Rated voltage (III / 3) | 1500 V |
| Rated impulse withstand voltage (III/3) | 12 kV |
| Approvals per | UL 1059 |
| Rated voltage UL (Use Group B) | 600 V |
| Rated current UL (Use Group B) | 310 A |
| Rated voltage UL (Use Group C) | 600 V |
| Rated current UL (Use Group C) | 310 A |
| Approvals per | UL 1059 / UL 1059 / UL 1059 |
| Use group | B / C / D |
| Rated voltage | 600 V / 600 V |
| Rated current | 310 A / 310 A |
| Approvals per | CSA 22.2 No 158 |
| Rated voltage CSA (Use Group B) | 1000 V |
| Rated current CSA (Use Group B) | 310 A |
| Rated voltage CSA (Use Group C) | 1000 V |
| Rated current CSA (Use Group D) | 310 A |
| Approvals per | CSA 22.2 No 158 / CSA 22.2 No 158 / CSA 22.2 No 158 |
| Use group | B / C / D |
| Rated voltage | 1000 V / 1000 V |
| Rated current | 310 A |
| Power loss, per pole (potential) | 11.215 W |
| Rated current I<sub>N</sub> for power loss specification | 353 A |
| Resistance value for specified, current-dependent power loss | 9 Ω |
| Voltage type 1 | AC/DC |
| Voltage type 2 | DC |
| Wiring direction | Side-entry wiring |
| Clamping units | 2 |
| Total number of potentials | 1 |
| Number of levels | 1 |
| Number of jumper slots | 2 |
| Connection technology | POWER CAGE CLAMP |
| Actuation type | T-wrench; 8 mm |
| Connectable conductor materials | Copper |
| Nominal cross-section | 185 mm² / 350 kcmil |
| Solid conductor | 50 … 185 mm² / 1/0 AWG … 350 kcmil |
| Stranded conductor | 50 … 185 mm² / 1/0 AWG … 350 kcmil |
| Fine-stranded conductor | 50 … 185 mm² / 1/0 AWG … 350 kcmil |
| Fine-stranded conductor; with insulated ferrule | 50 … 150 mm² / 1/0 AWG … 300 kcmil |
| Fine-stranded conductor; with uninsulated ferrule | 50 … 185 mm² / 1/0 AWG … 350 kcmil |
| Strip length | 45 … 47 mm / 1.77 … 1.85 inches |
| Wiring direction | Side-entry wiring |
| Width | 32 mm / 1.26 inches |
| Height from the surface | 123 mm / 4.843 inches |
| Depth | 170 mm / 6.693 inches |
| Mounting type | Mounting flange |
| Mounting type | Panel mounting |
| Marking level | Side marking |
| Note (material data) | Information on material specifications can be found here |
| Color | blue |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 4.592 MJ |
| Weight | 546.4 g |
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
| PU (SPU) | 4 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4055143424158 |
| Customs tariff number | 85369010000 |
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-20 |
| eCl@ss 9.0 | 27-14-11-20 |
| ETIM 9.0 | EC000897 |
| ETIM 10.0 | EC000897 |
| ECCN | NO US CLASSIFICATION |
| RoHS Compliance Status | Compliant,No Exemption |
No matching specifications
285-1164 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 285-1164 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 285-1164, subject to availability and destination.

2-conductor through terminal block; 10 mm²; suitable for Ex e II applications; center marking; for DIN-rail 35 x 15 and 35 x 7.5; CAGE CLAMP®; 10,00 mm²; light gray

3-conductor through terminal block; 10 mm²; suitable for Ex e II applications; center marking; for DIN-rail 35 x 15 and 35 x 7.5; CAGE CLAMP®; 10,00 mm²; light gray


2-conductor through terminal block; 185 mm²; lateral marker slots; with fixing flanges; POWER CAGE CLAMP; 185,00 mm²; gray

Three phase set; with 185 mm² high-current terminal block; with fixing flanges; copper; 185 mm²; POWER CAGE CLAMP; 185,00 mm²; multicoloured

2-conductor through terminal block; 185 mm²; lateral marker slots; with fixing flanges; POWER CAGE CLAMP; 185,00 mm²; dark gray-yellow

Three phase set; with 185/120 mm² high-current tbs; only for DIN 35 x 15 rail; copper; 185 mm²; POWER CAGE CLAMP; 185,00 mm²; gray/blue/green-yellow