Fuse plug; with pull-tab; for miniature metric fuses 5 x 20 mm and 5 x 25 mm; with blown fuse indication by neon lamp; 230 V; 6 mm wide; gray
Quadruple-deck rail-mounted terminal block; Rail-mounted terminal block for electric motor wiring; 2.5 mm²; L1 - L2 - L3 - PE; for DIN-rail 35 x 15 and 35 x 7.5; CAGE CLAMP®; 2,50 mm²; gray
Quadruple-deck terminal block, 281 Series, gray
This quadruple-deck terminal block (item number 281-530) simplifies electrical installations. Ensure that the strip lengths are between 8 and 9 mm when connecting conductors to this quadruple-deck terminal block. The quadruple-deck terminal block also serves as a through terminal block as well as a ground terminal block. This product features conductor terminals and utilizes CAGE CLAMP®. Our highly-rated and maintenance-free CAGE CLAMP® connection makes it easy to connect all types of conductors without having to prepare the conductor. For example, you don't need to crimp ferrules. This quadruple-deck terminal block is suitable for conductor cross sections ranging from 0.08 mm² to 4 mm².
| Ratings per | IEC/EN 60947-7-1 |
| Nominal voltage (III/3) | 400 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Rated current | 20 A |
| Current at conductor cross-section (max.) mm² | 25 A |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
| Ratings per | IEC/EN 60947-7-1 / IEC/EN 60947-7-1 / IEC/EN 60947-7-1 |
| Overvoltage category | III / III / II |
| Pollution degree | 3 / 2 / 2 |
| Nominal voltage | 400 V |
| Rated impulse withstand voltage | 6 kV |
| Rated current | 20 A |
| Current at conductor cross-section (max.) mm² | 25 A |
| Power loss, per pole (potential) | 1.596 W |
| Rated current I<sub>N</sub> for power loss specification | 20 A |
| Resistance value for specified, current-dependent power loss | 0.001 Ω |
| Wiring direction | Front-entry wiring |
| Clamping units | 7 |
| Total number of potentials | 4 |
| Number of levels | 4 |
| Connection technology | CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper, Aluminum |
| Connectable conductor materials (note) | Terminating Aluminum ConductorsWAGO Spring-Clamp Terminal Blocks are suitable for solid aluminum conductors up to 4 mm²/12 AWG if WAGO “Alu-Plus” Contact Paste 249-130 is used for termination.“Alu-Plus” Contact Paste Advantages:Automatically destroys the oxide film during clamping.Prevents fresh oxidation at the clamping point.Prevents electrolytic corrosion between aluminum and copper conductors (in the same terminal block).Provides long-term protection against corrosion.Using terminal blocks with CAGE CLAMP® Spring Pressure Connection Technology, aluminum conductors must first be cleaned with a blade and then immediately inserted into the clamping units filled with “Alu-Plus” contact paste.It is also possible to apply WAGO “Alu-Plus” additionally on the whole surface of the aluminum conductor before termination.Please note that the nominal currents must be adapted to the reduced conductivity of the aluminum conductors:2.5 mm² = 16 A4 mm² = 22 A |
| Nominal cross-section | 2.5 mm² |
| Solid conductor | 0.08 … 4 mm² / 28 … 12 AWG |
| Fine-stranded conductor | 0.08 … 4 mm² / 28 … 12 AWG |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Wiring direction | Front-entry wiring |
| Width | 6 mm / 0.236 inches |
| Height | 100 mm / 3.937 inches |
| Depth from upper-edge of DIN-rail | 62.5 mm / 2.461 inches |
| Potential marking | L1 - L2 - L3 - PE |
| Design | angled |
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
| Note (material data) | Information on material specifications can be found here |
| Color | gray |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 0.356 MJ |
| Weight | 23.2 g |
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
| Product Group | 1 (Rail Mounted Terminal Blocks) |
| PU (SPU) | 50 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4045454017071 |
| Customs tariff number | 85369010000 |
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-20 |
| eCl@ss 9.0 | 27-14-11-20 |
| ETIM 9.0 | EC000897 |
| ETIM 10.0 | EC000897 |
| ECCN | NO US CLASSIFICATION |
| RoHS Compliance Status | Compliant,No Exemption |
281-530 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 281-530 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 281-530, subject to availability and destination.

Fuse plug; with pull-tab; for miniature metric fuses 5 x 20 mm and 5 x 25 mm; with blown fuse indication by neon lamp; 230 V; 6 mm wide; gray

Fuse plug; with pull-tab; for miniature metric fuses 5 x 20 mm and 5 x 25 mm; with blown fuse indication by neon lamp; 120 V; 6 mm wide; gray

Fuse plug; with pull-tab; for miniature metric fuses 5 x 20 mm and 5 x 25 mm; with LED indicator; 24 V AC/DC; 6 mm wide; gray

Fuse plug; with pull-tab; for miniature metric fuses 5 x 20 mm and 5 x 25 mm; with LED indicator; 6 mm wide; gray

Quadruple-deck rail-mounted terminal block; Rail-mounted terminal block for electric motor wiring; L1 - L2; for DIN-rail 35 x 15 and 35 x 7.5; 4 mm²; 4,00 mm²; gray

Quadruple-deck rail-mounted terminal block; Rail-mounted terminal block for electric motor wiring; L1 - L2 - L3; for DIN-rail 35 x 15 and 35 x 7.5; 4 mm²; 4,00 mm²; gray

2-conductor through terminal block; 4 mm²; lateral marker slots; for DIN-rail 35 x 15 and 35 x 7.5; CAGE CLAMP®; 4,00 mm²; gray

Component terminal block; 2-conductor; with diode 1N5408; anode, left side; for DIN-rail 35 x 15 and 35 x 7.5; 4 mm²; CAGE CLAMP®; gray