2-conductor disconnect/test terminal block; e.g., current transformer circuits; with receptacle for adjacent jumper with switch lever; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5
Compact terminal block; for current and voltage transformers; 6,00 mm²; multicoloured
Current transformer terminal block, 2007 Series, operating tool
Our current transformer terminal block (item number 2007-8874) ensures effortless electrical installations. Conductors should only be connected to this current transformer terminal block if their strip length is between 13 and 15 mm . This product features conductor terminals and utilizes Push-in CAGE CLAMP®. Push-in CAGE CLAMP® technology provides a universal connection solution for any type of conductor. It allows both solid and fine-stranded conductors with ferrules to be inserted directly into the clamping point without the need for tools. This current transformer terminal block is suitable for conductor cross sections ranging from 0.5 mm² to 10 mm².
| Nominal voltage (III/3) | 500 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
| Wiring direction | Front-entry wiring |
| Number of levels | 1 |
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper |
| Nominal cross-section | 6 mm² / 10 AWG |
| Solid conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Solid conductor; push-in termination | 1 … 10 mm² / 14 … 8 AWG |
| Fine-stranded conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.5 … 6 mm² / 20 … 10 AWG |
| Fine-stranded conductor; with uninsulated ferrule | 1.5 … 6 mm² / 16 … 10 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6 mm² / 16 … 10 AWG |
| Strip length | 13 … 15 mm / 0.51 … 0.59 inches |
| Wiring direction | Front-entry wiring |
| Width | 127 mm / 5 inches |
| Height | 99.6 mm / 3.921 inches |
| Depth from upper-edge of DIN-rail | 65.3 mm / 2.571 inches |
| Module width | 8 mm / 0.315 inches |
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
| Note (material data) | Information on material specifications can be found here |
| Color | multi-colored |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 6.477 MJ |
| Weight | 402.4 g |
| Test socket color | orange |
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
| Test specification: <br/>Railway applications –<br/>Rolling stock –<br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure: <br/>Railway applications – <br/>Rolling stock equipment – <br/>Vibration and shock tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
| Spectrum/Mounting location | Service life test, Category 1, Class A/B |
| Functional test with noise-like oscillations | Test passed according to Section 8 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.101g (highest test level used for all axes) |
| Test duration per axis | 10 min. |
| Test directions | X, Y and Z axes |
| Monitoring of contact faults and interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed |
| Simulated service life test through increased levels of noise-like oscillations | Test passed according to Section 9 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.572g (highest test level used for all axes) |
| Test duration per axis | 5 h |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard |
| Shock pulse form | Half sine |
| Acceleration | 5g (highest test level used for all axes) |
| Shock duration | 30 ms |
| Number of shocks (per axis) | 3 pos. und 3 neg. |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Vibration and shock stress for rolling stock equipment | Passed |
| Product Group | 22 (TOPJOB S) |
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| GTIN | 4055143070294 |
| Customs tariff number | 85369010000 |
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-47 |
| eCl@ss 9.0 | 27-14-11-47 |
| ETIM 9.0 | EC000276 |
| ETIM 10.0 | EC000276 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 7439-92-1 |
| REACH Candidate List Substance | Lead |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c) |
| SCIP notification number (Austria) | be090492-316a-4da2-8615-f61e4d86728a |
| SCIP notification number (Belgium) | 445f69c5-a5ef-4db5-ba0d-67db0ff386aa |
| SCIP notification number (Bulgaria) | 2cf95ddd-9e24-4057-8a95-0872de205fd5 |
| SCIP notification number (Czech Republic) | dd82830c-1bc6-4249-be16-2a84f8eae2f3 |
| SCIP notification number (Denmark) | fb14f858-96a6-4850-b673-5cfed08e7f46 |
| SCIP notification number (Finland) | 784d71b6-1ff6-496f-84a9-ec5e6405fb71 |
| SCIP notification number (France) | 46ebaf43-c978-422a-9b07-7ac1d06b43c1 |
| SCIP notification number (Germany) | d14407af-157c-4e3b-9d7e-8c4ac153311a |
| SCIP notification number (Hungary) | e6882aae-9fa8-4576-aaac-44abb965d1a5 |
| SCIP notification number (Italy) | dd3c6457-22e6-437d-8d9f-0f7c0a4a3360 |
| SCIP notification number (Netherlands) | 2b7a5329-22ed-44c3-bd9b-a39ac1ea3dd3 |
| SCIP notification number (Poland) | 98a2045c-d4ac-4d19-8465-e3593ecf3353 |
| SCIP notification number (Romania) | 52920352-634b-45e1-95e6-c249bdfae9ae |
| SCIP notification number (Sweden) | 80f65056-a8cb-4be4-945f-953fba3801a1 |
2007-8874 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 2007-8874 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2007-8874, subject to availability and destination.

2-conductor disconnect/test terminal block; e.g., current transformer circuits; with receptacle for adjacent jumper with switch lever; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5

2-conductor disconnect/test terminal block; e.g., current transformer circuits; with receptacle for adjacent jumper with switch lever; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5

2-conductor disconnect/test terminal block; e.g., current transformer circuits; with receptacle for adjacent jumper with switch lever; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5



Compact terminal block; for 3-phase current transformer circuit; 6,00 mm²; multicoloured