2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; gray
2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; blue
Through terminal block, 2007 Series, Push-in CAGE CLAMP®
This through terminal block (item number 2007-8804) is designed for simple and secure connections. Strip lengths must be between 13 and 15 mm when connecting conductors to this through terminal block. Featuring conductor terminals along with Push-in CAGE CLAMP®, this product outperforms the competition. Our Push-in CAGE CLAMP® is a universal, maintenance-free connection solution for all conductor types, offering a key advantage: both solid and fine-stranded conductors with ferrules can be directly inserted without the need for tools or any preparation, such as crimping the ferrule. Depending on the conductor type, this through terminal block is designed for conductor cross sections ranging from 0.5 mm² to 10 mm².
| Ratings per | IEC/EN 60664-1 |
| Nominal voltage (III/3) | 500 V |
| Rated impulse withstand voltage (III / 3) | 6 kV |
| Rated current | 30 A |
| Legend (ratings) | (III / 3) ≙ Overvoltage category III / Pollution degree 3 |
| Ratings per | IEC/EN 60664-1 / IEC/EN 60664-1 / IEC/EN 60664-1 |
| Overvoltage category | III / III / II |
| Pollution degree | 3 / 2 / 2 |
| Nominal voltage | 500 V |
| Rated impulse withstand voltage | 6 kV |
| Rated current | 30 A |
| Approvals per | UL 1059 |
| Rated voltage UL (Use Group B) | 300 V |
| Rated current UL (Use Group B) | 30 A |
| Rated voltage UL (Use Group C) | 300 V |
| Rated current UL (Use Group C) | 30 A |
| Rated voltage UL (Use Group D) | 300 V |
| Rated current UL (Use Group D) | 10 A |
| Approvals per | UL 1059 / UL 1059 / UL 1059 |
| Use group | B / C / D |
| Rated voltage | 300 V / 300 V / 300 V |
| Rated current | 30 A / 30 A / 10 A |
| Approvals per | CSA 22.2 No 158 |
| Rated voltage CSA (Use Group B) | 300 V |
| Rated current CSA (Use Group B) | 30 A |
| Rated voltage CSA (Use Group C) | 300 V |
| Rated current CSA (Use Group C) | 30 A |
| Rated voltage CSA (Use Group D) | 300 V |
| Rated current CSA (Use Group D) | 10 A |
| Approvals per | CSA 22.2 No 158 / CSA 22.2 No 158 / CSA 22.2 No 158 |
| Use group | B / C / D |
| Rated voltage | 300 V / 300 V / 300 V |
| Rated current | 30 A / 30 A / 10 A |
| Power loss, per pole (potential) | 0.702 W |
| Rated current I<sub>N</sub> for power loss specification | 30 A |
| Resistance value for specified, current-dependent power loss | 0.001 Ω |
| Wiring direction | Front-entry wiring |
| Clamping units | 2 |
| Total number of potentials | 1 |
| Number of levels | 1 |
| Number of jumper slots | 2 |
| Connection technology | Push-in CAGE CLAMP® |
| Actuation type | Operating tool |
| Connectable conductor materials | Copper |
| Nominal cross-section | 6 mm² / 10 AWG |
| Solid conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Solid conductor; push-in termination | 1 … 10 mm² / 14 … 8 AWG |
| Fine-stranded conductor | 0.5 … 10 mm² / 20 … 8 AWG |
| Fine-stranded conductor; with insulated ferrule | 0.5 … 6 mm² / 20 … 10 AWG |
| Fine-stranded conductor; with uninsulated ferrule | 1.5 … 6 mm² / 16 … 10 AWG |
| Fine-stranded conductor; with ferrule; push-in termination | 2.5 … 6 mm² / 16 … 10 AWG |
| Strip length | 13 … 15 mm / 0.51 … 0.59 inches |
| Wiring direction | Front-entry wiring |
| Width | 8 mm / 0.315 inches |
| Height | 99.6 mm / 3.921 inches |
| Depth from upper-edge of DIN-rail | 46.8 mm / 1.843 inches |
| Mounting type | DIN-35 rail |
| Marking level | Center/side marking |
| Note (material data) | Information on material specifications can be found here |
| Color | blue |
| Material group | I |
| Insulation material (main housing) | Polyamide (PA66) |
| Flammability class per UL94 | V0 |
| Fire load | 0.387 MJ |
| Weight | 21.9 g |
| Test socket color | orange |
| Processing temperature | -35 … +85 °C |
| Continuous operating temperature | -60 … +105 °C |
| Test specification: <br/>Railway applications –<br/>Rolling stock –<br/>Electronic equipment | DIN EN 50155 (VDE 0115-200):2022-06 |
| Test procedure: <br/>Railway applications – <br/>Rolling stock equipment – <br/>Vibration and shock tests | DIN EN 61373 (VDE 0115-0106):2011-04 |
| Spectrum/Mounting location | Service life test, Category 1, Class A/B |
| Functional test with noise-like oscillations | Test passed according to Section 8 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.101g (highest test level used for all axes) |
| Test duration per axis | 10 min. |
| Test directions | X, Y and Z axes |
| Monitoring of contact faults and interruptions | Passed |
| Voltage drop measurement before and after each axis | Passed |
| Simulated service life test through increased levels of noise-like oscillations | Test passed according to Section 9 of the standard |
| Frequency | f1 = 5 Hz to f2 = 150 Hz |
| Acceleration | 0.572g (highest test level used for all axes) |
| Test duration per axis | 5 h |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Shock test | Test passed according to Section 10 of the standard |
| Shock pulse form | Half sine |
| Acceleration | 5g (highest test level used for all axes) |
| Shock duration | 30 ms |
| Number of shocks (per axis) | 3 pos. und 3 neg. |
| Test directions | X, Y and Z axes |
| Extended testing: Monitoring of contact faults and interruptions | Passed |
| Extended testing: Voltage drop measurement before and after each axis | Passed |
| Vibration and shock stress for rolling stock equipment | Passed |
| PU (SPU) | 20 pcs |
| Packaging type | box |
| Country of origin | CN |
| GTIN | 4055143300285 |
| Customs tariff number | 85369010000 |
| UNSPSC | 39121410 |
| eCl@ss 10.0 | 27-14-11-20 |
| eCl@ss 9.0 | 27-14-11-20 |
| ETIM 9.0 | EC000897 |
| ETIM 10.0 | EC000897 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 7439-92-1 |
| REACH Candidate List Substance | Lead |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 6(c) |
| SCIP notification number (Austria) | f054a96e-b7df-4515-a5fc-d3750186064c |
| SCIP notification number (Belgium) | 355615ac-9ae0-4344-b217-ba2182860087 |
| SCIP notification number (Bulgaria) | b791c995-6634-4ba2-aaa3-96caa33d2bb7 |
| SCIP notification number (Czech Republic) | 45223efb-59c8-4127-920e-8e30fb70ebb6 |
| SCIP notification number (Denmark) | 342eb0d9-bd6d-4b4c-92b6-4cd59f754ffe |
| SCIP notification number (Finland) | f9813f4a-5b26-4d2b-86ce-f1a07c8fd110 |
| SCIP notification number (France) | f4cbdd21-38a6-4f68-aba2-9db91fdcf487 |
| SCIP notification number (Germany) | de9ca837-15ae-40ee-b1cd-e657c0cd7965 |
| SCIP notification number (Hungary) | 5cc1332a-128b-4a2b-8007-c7cac0206d5e |
| SCIP notification number (Italy) | 505c92d4-a356-48a3-88a4-6a865830bc2f |
| SCIP notification number (Netherlands) | cd8be6be-047e-4d9d-a405-fb4a8e2e6fdc |
| SCIP notification number (Poland) | 17a3edc6-d03d-4524-857d-0a116a831e08 |
| SCIP notification number (Romania) | fce9afda-ff5e-4a73-9d5e-e1ab895cd0ef |
| SCIP notification number (Sweden) | c21c5bcb-d713-451b-b2ae-49bf0c2fee06 |
2007-8804 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for 2007-8804 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 2007-8804, subject to availability and destination.

2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; gray

2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; gray

2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; gray

2-conductor through terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; gray

2-conductor ground terminal block; 6 mm²; with touch-proof test socket; for 4 mm Ø test plugs; side and center marking; for DIN-rail 35 x 15 and 35 x 7.5; Push-in CAGE CLAMP®; 6,00 mm²; green

2-conductor disconnect/test terminal block; e.g., voltage transformer circuits; with touch-proof test sockets; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5; 6 mm²; Push-in CAGE CL

2-conductor disconnect/test terminal block; e.g., voltage transformer circuits; with touch-proof test sockets; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5; 6 mm²; Push-in CAGE CL

2-conductor disconnect/test terminal block; e.g., voltage transformer circuits; with touch-proof test sockets; for 4 mm Ø test plugs; for DIN-rail 35 x 15 and 35 x 7.5; 6 mm²; Push-in CAGE CL