Siemens 6EP4134-0GB00-0AY0

SITOP UPS1100 battery module with maintenance- free sealed lead-acid batteries for SITOP DC UPS modules 24 V…

MPN
6EP4134-0GB00-0AY0
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Siemens parts? We buy surplus →

What is the Siemens 6EP4134-0GB00-0AY0?

SITOP UPS1100 battery module with maintenance- free sealed lead-acid batteries for SITOP DC UPS modules 24 V DC 7 Ah

Specifications

General information

Technical Product Detail Pagehttps://i.siemens.com/1P6EP4134-0GB00-0AY0
product brand nameSITOP
product type designationUPS1100
product designationBattery module 7 Ah
type of batterymaintenance-free lead-acid batteries
product versionExtension module/battery module

electrical data

end-of-charge voltage at DC — at -10 °C recommended28 V
end-of-charge voltage at DC — at 0 °C recommended28 V
end-of-charge voltage at DC — at 10 °C recommended27.8 V
end-of-charge voltage at DC — at 20 °C recommended27.3 V
end-of-charge voltage at DC — at 30 °C recommended26.8 V
end-of-charge voltage at DC — at 40 °C recommended26.6 V
end-of-charge voltage at DC — at 50 °C recommended26.3 V

output

battery capacity7 A·h
output current rated value40 A
output current in buffering mode maximum40 A
peak current120 A; for 30 ms
charging current maximum1.75 A
output voltage at DC rated value24 V

interfaces

communication functionYes

protection and monitoring

design of short-circuit protectionBattery fuse 2x 25 A/32 V (solid-state circuitry blade-type fuse + support)
design of the overload protectionValve control
display version for normal operationLED green: Battery OK; LED flashing green: Error or warning; OFF: No communication

safety

operating resource protection classClass III
protection class IPIP20

standards, specifications, approvals

certificate of suitability — CE markingYes
certificate of suitability — UL approvalYes; cURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
certificate of suitability — EAC approvalYes

standards, specifications, approvals hazardous environments

certificate of suitability — ATEXNo

standards, specifications, approvals marine classification

shipbuilding approvalYes
Marine classification association — American Bureau of Shipping Europe Ltd. (ABS)Yes
Marine classification association — Det Norske Veritas (DNV)Yes

standards, specifications, approvals Environmental Product Declaration

Environmental Product DeclarationYes
global warming potential [CO2 eq] — total24.166 kg
global warming potential [CO2 eq] — during manufacturing13.567 kg
global warming potential [CO2 eq] — during operation8.167 kg
global warming potential [CO2 eq] — after end of life0.715 kg

ambient conditions

ambient conditionFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
ambient temperature — during operation-15 ... +50 °C
ambient temperature — during transport-20 ... +50 °C
ambient temperature — during storage-20 ... +40 °C
relative temporary capacity loss at 20 °C in a month typical3 %

service life

service life of energy storage — typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
service life of energy storage — at 20 °C typical4 a
service life of energy storage — at 30 °C typical2 a
service life of energy storage — at 40 °C typical1 a
service life of energy storage — at 50 °C typical0.5 a
noteAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.

connection method

type of electrical connectionscrew terminal
type of electrical connection — for UPS module1 screw terminal each for 0.5 ... 16 mm² for + BAT and - BAT
type of electrical connection — for control circuit and status message1 screw terminal each for 0.14 ... 4 mm²

mechanical data

width × height × depth of the enclosure186 × 186 × 110 mm
installation width × mounting height186 mm × 201 mm
required spacing — top15 mm
required spacing — bottom0 mm
required spacing — left0 mm
required spacing — right0 mm
fastening methodcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
fastening method — DIN-rail mountingNo
fastening method — S7 rail mountingNo
fastening method — wall mountingYes
net weight6.1 kg
number of cells12

accessories

product component includedAccessories pack with solid-state circuitry fuse 25 A

further information internet links

internet link — to website: Industry Mallhttps://mall.industry.siemens.com
internet link — to web page: selection aid TIA Selection Toolhttps://www.siemens.com/tstcloud
internet link — to web page: power supplieshttps://siemens.com/sitop
internet link — to website: CAx-Download-Managerhttps://www.siemens.com/cax
internet link — to website: Industry Online Supporthttps://support.industry.siemens.com

additional information

other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

security information

security informationSiemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7)

Downloads & documentation

Official documents from Siemens, downloaded directly from the manufacturer.

Data sheets & manuals

6EP4134-0GB00-0AY0: frequently asked questions

When can 6EP4134-0GB00-0AY0 be shipped?

6EP4134-0GB00-0AY0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 6EP4134-0GB00-0AY0 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 6EP4134-0GB00-0AY0 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 6EP4134-0GB00-0AY0, subject to availability and destination.

More Siemens parts

Siemens 6EP4132-0GB00-0AY0 – SITOP UPS1100/Battery module/24V/2.5AH SITOP UPS1100 battery module with maintenance- free sealed pure…
Siemens
6EP4132-0GB00-0AY0

SITOP UPS1100/Battery module/24V/2.5AH SITOP UPS1100…

Siemens 6EP4133-0GA00-0AY0 – SITOP BAT1600/Battery module/24V/3.2AH SITOP BAT1600 24 V DC 3.2 Ah Pb battery module with maintenance- fee…
Siemens
6EP4133-0GA00-0AY0

SITOP BAT1600/Battery module/24V/3.2AH SITOP BAT1600 24 V…

Siemens 6EP4133-0GB00-0AY0 – SITOP UPS1100/Battery module/24V/3.2AH Spare part: SITOP UPS1100 battery module with maintenance- free sealed…
Siemens
6EP4133-0GB00-0AY0

SITOP UPS1100/Battery module/24V/3.2AH Spare part: SITOP…

Siemens 6EP4133-0JB00-0AY0 – SITOP UPS1100/BAT. MODULE/24V/5AH/LIFEPO Spare part: SITOP UPS1100 battery module with maintenance- free…
Siemens
6EP4133-0JB00-0AY0

SITOP UPS1100/BAT. MODULE/24V/5AH/LIFEPO Spare part: SITOP…

Siemens 6EP4134-0GE10-0AY0 – SITOP BAT1600 24 V DC 7 Ah Pb battery module with maintenance- free sealed lead-acid battery for SITOP UPS1600
Siemens
6EP4134-0GE10-0AY0

SITOP BAT1600 24 V DC 7 Ah Pb battery module with…

Siemens 6EP4134-0HA00-0AY0 – SITOP CAS1600 0.3 Ah 24 V DC 0.3 Ah SuCAP capacitor module with maintenance- free sealed supercapacitors for…
Siemens
6EP4134-0HA00-0AY0

SITOP CAS1600 0.3 Ah 24 V DC 0.3 Ah SuCAP capacitor module…

Siemens 6EP4134-0JA00-0AY0 – SITOP BAT1600 24 V DC 7.5 Ah LiFePO4 lithium battery for SITOP UPS1600 - - not for air freight - -
Siemens
6EP4134-0JA00-0AY0

SITOP BAT1600 24 V DC 7.5 Ah LiFePO4 lithium battery for…

Siemens 6EP4134-0GB00-0AY0Price and lead time confirmed within 1 business day
Request a Quote