Siemens 3RK1308-0AE00-0CP0

Direct-on-line starter High Feature; Incl. fan (3RW4928-8VB00); Electronic switching

MPN
3RK1308-0AE00-0CP0
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Siemens parts? We buy surplus →

What is the Siemens 3RK1308-0AE00-0CP0?

Direct-on-line starter High Feature; Incl. fan (3RW4928-8VB00); Electronic switching; Electronic overload protection up to 5.5 kW / 400 V; Adjustment range 4.0 .. 12 A; PROFIenergy; Option: 3DI/LC module

Specifications

General

product brand nameSIMATIC
product categoryMotor starter
product designationDirect-on-line starter
product type designationET 200SP

General technical data

equipment version according to IEC 60947-4-23
product functionDirect-on-line starter
product function — on-site operationYes
product function — intrinsic device protectionYes
product function — remote firmware updateYes
product function — for power supply reverse polarity protectionYes
power loss [W] for rated value of the current — at AC in hot operating state per pole2.6 W
insulation voltage rated value500 V
degree of pollution2
overvoltage categoryIII
surge voltage resistance rated value6 kV
maximum permissible voltage for protective separation — between main and auxiliary circuit500 V
consumed current maximum180 mA
shock resistance6 g / 11 ms
vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
operating frequency maximum1 1/s
mechanical service life (operating cycles) of the main contacts typical30 000 000
type of coordination1
utilization category — according to IEC 60947-4-2AC-53a: 12 A: (8-0,5: 72-32)
utilization category — according to IEC 60947-4-3AC-51: 12 A: (1,2-10: 50-360); AC-55a: 5 A: (3-240: 40-6)
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)04/15/2016
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.42 kg
product function — direct startYes
product function — reverse startingNo
product component motor brake outputNo
product function short circuit protectionYes
design of short-circuit protectionfuse
maximum short-circuit current breaking capacity (Icu) — at 400 V rated value55 kA
maximum short-circuit current breaking capacity (Icu) — at 500 V rated value55 kA
maximum short-circuit current breaking capacity (Icu) — at 500 V according to UL 60947 rated value100 kA
maximum short-circuit current breaking capacity (Icu) in the IT network — at 400 V rated value55 kA
maximum short-circuit current breaking capacity (Icu) in the IT network — at 500 V rated value55 kA

Electromagnetic compatibility

EMC emitted interference according to IEC 60947-1class A
EMC immunity according to IEC 60947-1Class A
conducted interference — due to burst according to IEC 61000-4-42 kV
conducted interference — due to conductor-earth surge according to IEC 61000-4-52 kV
conducted interference — due to conductor-conductor surge according to IEC 61000-4-51 kV
conducted interference — due to high-frequency radiation according to IEC 61000-4-6Class A
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-28 kV air discharge
conducted HF interference emissions according to CISPR11Class A for industrial environment
field-bound HF interference emission according to CISPR11Class A for industrial environment

Safety related data

MTBF46 a
touch protection against electrical shockfinger-safe
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe

Main circuit

number of poles for main current circuit3
design of the switching contactHybrid
adjustable current response value current of the current-dependent overload release4 ... 12 A
minimum load [%]50 %; from smallest adjustable rated current
type of the motor protectionsolid-state
operating voltage rated value48 ... 500 V
relative symmetrical tolerance of the operating voltage10 %
operating frequency 1 rated value50 Hz
operating frequency 2 rated value60 Hz
relative symmetrical tolerance of the operating frequency5 %
relative positive tolerance of the operating frequency5 %
relative negative tolerance of the operating frequency5 %
operational current at AC at 400 V rated value12 A
ampacity when starting maximum120 A
operating power for 3-phase motors at 400 V at 50 Hz2.2 ... 5.5 kW

Inputs/ Outputs

number of digital inputs4
number of digital inputs — note4 via 3DI/LC module
address space memory of address range — of the inputs4 byte
address space memory of address range — of the outputs2 byte

Supply voltage

type of voltage of the supply voltageDC
supply voltage 1 at DC rated value — minimum permissible20.4 V
supply voltage 1 at DC rated value — maximum permissible28.8 V
supply voltage at DC rated value24 V
consumed current for rated value of supply voltage — in standby mode of operation85 mA
consumed current for rated value of supply voltage — during operation90 mA
consumed current for rated value of supply voltage — at switching on of motor180 mA
power loss [W] for rated value of supply voltage — in switching state OFF with bypass circuit2.2 W
power loss [W] for rated value of supply voltage — in switching state ON with bypass circuit4.32 W
inrush current peak at 24 V25 A; Observe the manual for group configuration
duration of inrush current peak at 24 V0.14 ms

Response times

ON-delay time20 ms
OFF-delay time35 ... 50 ms

Power Electronics

operational current — at 40 °C rated value12 A
operational current — at 50 °C rated value10 A
operational current — at 55 °C rated value9 A
operational current — at 60 °C rated value9 A

Installation/ mounting/ dimensions

mounting positionVertical, horizontal (observe derating)
fastening methodpluggable in BaseUnit
height142 mm
width30 mm
depth150 mm
required spacing with side-by-side mounting — upwards50 mm
required spacing with side-by-side mounting — downwards50 mm

Ambient conditions

installation altitude at height above sea level maximum4 000 m
ambient temperature — during operation-25 ... +60 °C; For derating see manual
ambient temperature — during storage-40 ... +70 °C
ambient temperature — during transport-40 ... +70 °C
environmental category during operation according to IEC 607213K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices)
relative humidity during operation10 ... 95 %
air pressure according to SN 31205900 ... 1 060 hPa

Communication/ Protocol

protocol is supported — PROFIBUS DP protocolYes
protocol is supported — PROFINET protocolYes
product function bus communicationYes
protocol is supported AS-Interface protocolNo
product function — supports PROFIenergy measured valuesYes
product function — supports PROFIenergy shutdownYes
type of electrical connection of the communication interfacePlug contact to Base Unit

Connections/ Terminals

type of electrical connection — 1 for digital input signalsPluggable module - accessory
type of electrical connection — for main energy infeedPlug contact to Base Unit
type of electrical connection — for load-side outgoing feederPlug contact to Base Unit
type of electrical connection — for supply voltage line-sidePlug contact to Base Unit
wire length for motor unshielded maximum200 m

UL/CSA ratings

full-load current (FLA) for 3-phase AC motor at 480 V rated value12 A
current with locked rotor (LRA) for 3-phase AC motor at 480 V rated value72 A
yielded mechanical performance [hp] — for single-phase AC motor — at 110/120 V rated value0.5 hp
yielded mechanical performance [hp] — for single-phase AC motor — at 230 V rated value2 hp
yielded mechanical performance [hp] — for 3-phase AC motor — at 200/208 V rated value2 hp
yielded mechanical performance [hp] — for 3-phase AC motor — at 220/230 V rated value3 hp
yielded mechanical performance [hp] — for 3-phase AC motor — at 460/480 V rated value7.5 hp
operating voltage at AC at 60 Hz according to CSA and UL rated value480 V

Downloads & documentation

Official documents from Siemens, downloaded directly from the manufacturer.

Data sheets & manuals

3RK1308-0AE00-0CP0: frequently asked questions

When can 3RK1308-0AE00-0CP0 be shipped?

3RK1308-0AE00-0CP0 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up 3RK1308-0AE00-0CP0 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for 3RK1308-0AE00-0CP0 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 3RK1308-0AE00-0CP0, subject to availability and destination.

More Siemens parts

Siemens 3RK1308-0AA00-0CP0 – Direct-on-line starter High Feature; Electronic switching
Siemens
3RK1308-0AA00-0CP0

Direct-on-line starter High Feature; Electronic switching

Siemens 3RK1308-0AB00-0CP0 – Direct-on-line starter High Feature; Electronic switching
Siemens
3RK1308-0AB00-0CP0

Direct-on-line starter High Feature; Electronic switching

Siemens 3RK1308-0AC00-0CP0 – Direct-on-line starter High Feature; Electronic switching
Siemens
3RK1308-0AC00-0CP0

Direct-on-line starter High Feature; Electronic switching

Siemens 3RK1308-0AD00-0CP0 – Direct-on-line starter High Feature; Electronic switching; Electronic overload protection up to 4 kW / 400 V
Siemens
3RK1308-0AD00-0CP0

Direct-on-line starter High Feature; Electronic switching

Siemens 3RK1308-0BA00-0CP0 – Reversing starter High Feature; Electronic switching; Electronic overload protection up to 0.09 kW / 400 V
Siemens
3RK1308-0BA00-0CP0

Reversing starter High Feature; Electronic switching

Siemens 3RK1308-0AE00-0CP0Price and lead time confirmed within 1 business day