| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| protection class IP on the front | IP20 |
| mechanical service life (operating cycles) typical | 10 000 000 |
| electrical endurance (operating cycles) at AC-15 at 230 V typical | 200 000 |
| Substance Prohibitance (day/month/year) | 10/01/2009 |
| Net Weight | 44.69 g |
| number of NC contacts for auxiliary contacts – instantaneous contact | 0 |
| number of NC contacts for auxiliary contacts – lagging switching | 0 |
| number of NO contacts for auxiliary contacts – instantaneous contact | 2 |
| number of NO contacts for auxiliary contacts – leading contact | 0 |
| number of CO contacts of auxiliary contacts instantaneous contact | 0 |
| operational current at AC-15 at 690 V rated value | 1 A |
| operational current of auxiliary contacts at AC-12 – at 24 V | 10 A |
| operational current of auxiliary contacts at AC-12 – at 230 V | 10 A |
| operational current of auxiliary contacts at AC-14 – at 125 V | 6 A |
| operational current of auxiliary contacts at AC-14 – at 250 V | 6 A |
| operational current of auxiliary contacts at AC-12 maximum | 10 A |
| operational current of auxiliary contacts at AC-15 – at 24 V | 6 A |
| operational current of auxiliary contacts at AC-15 – at 230 V | 6 A |
| operational current of auxiliary contacts at AC-15 – at 400 V | 3 A |
| operational current of auxiliary contacts at DC-12 – at 24 V | 10 A |
| operational current of auxiliary contacts at DC-12 – at 110 V | 3 A |
| operational current of auxiliary contacts at DC-12 – at 220 V | 1 A |
| operational current with 2 current paths in series at DC-12 – at 24 V rated value | 10 A |
| operational current with 2 current paths in series at DC-12 – at 60 V rated value | 10 A |
| operational current with 2 current paths in series at DC-12 – at 110 V rated value | 4 A |
| operational current with 2 current paths in series at DC-12 – at 220 V rated value | 2 A |
| operational current with 2 current paths in series at DC-12 – at 440 V rated value | 1.3 A |
| operational current with 2 current paths in series at DC-12 – at 600 V rated value | 0.65 A |
| operational current with 3 current paths in series at DC-12 – at 24 V rated value | 10 A |
| operational current with 3 current paths in series at DC-12 – at 60 V rated value | 10 A |
| operational current with 3 current paths in series at DC-12 – at 110 V rated value | 10 A |
| operational current with 3 current paths in series at DC-12 – at 220 V rated value | 3.6 A |
| operational current with 3 current paths in series at DC-12 – at 440 V rated value | 2.5 A |
| operational current with 3 current paths in series at DC-12 – at 600 V rated value | 1.8 A |
| operational current with 2 current paths in series at DC-13 – at 24 V rated value | 10 A |
| operational current with 2 current paths in series at DC-13 – at 60 V rated value | 3.5 A |
| operational current with 2 current paths in series at DC-13 – at 110 V rated value | 1.3 A |
| operational current with 2 current paths in series at DC-13 – at 220 V rated value | 0.9 A |
| operational current with 2 current paths in series at DC-13 – at 440 V rated value | 0.2 A |
| operational current with 2 current paths in series at DC-13 – at 600 V rated value | 0.1 A |
| operational current with 3 current paths in series at DC-13 – at 24 V rated value | 10 A |
| operational current with 3 current paths in series at DC-13 – at 60 V rated value | 4.7 A |
| operational current with 3 current paths in series at DC-13 – at 110 V rated value | 3 A |
| operational current with 3 current paths in series at DC-13 – at 220 V rated value | 1.2 A |
| operational current with 3 current paths in series at DC-13 – at 440 V rated value | 0.5 A |
| operational current with 3 current paths in series at DC-13 – at 600 V rated value | 0.26 A |
| operational current of auxiliary contacts at DC-13 – at 24 V | 6 A |
| operational current of auxiliary contacts at DC-13 – at 48 V | 2 A |
| operational current of auxiliary contacts at DC-13 – at 60 V | 2 A |
| operational current of auxiliary contacts at DC-13 – at 110 V | 1 A |
| operational current of auxiliary contacts at DC-13 – at 125 V | 0.9 A |
| operational current of auxiliary contacts at DC-13 – at 220 V | 0.3 A |
| operational current of auxiliary contacts at DC-13 – at 250 V | 0.3 A |
| design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 10 A; 0.4 kA |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |