Hotel Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, White Case/Fascia.
Hotel LV Fan Coil Room Controller & Zone Controller: BACnet MS/TP, ZigBee Embedded, RH sensor, IP ready, PIR motion sensor, Silver Case/Fascia.
SE8300 Series room controllers are used for Low Voltage Fan Coil Unit control, with touch color screen. The room controllers rated supply voltage range is 24 to 28V AC at 50 or 60Hz +/-15%. The rated current is 4A. The device consumption is up to 12VA. The room controller is colored sliver and is equiped with a communication port that uses BACnet MS/TP protocol and a PIR sensor. Its Room and Outdoor Air Temperature Display Range is between -40 and 50 °C. The measurement accuracy is +/- 0.5%. The product follows the following standards: IEC 61326-1: 2005, FCC part 15 subpart C, RSS 210 issue 8, FCC part 15 subpart B. The ambient air temperature for operation is between 0 and 50 °C. The relative humidity for operating or storage is between 0 and 75% non condensing. The room controller is equiped with 7 Universal inputs, 5 Digital outputs and 4 Universal outputs (could be DO or AO). The room Controllers supports a built-in LUA script engine which allows the user to alter the sequence of operation to customize it for different applications The room Controller has Zigbee Pro onboard to support wireless connectivity with BMS system or Zigbee sensors.
| AWG gauge | AWG 24...AWG 18 |
| Humidity measurement drift | Less than 1 % yearly |
| Width | 86 mm |
| Market segment | Lodging/hotel, Small buildings, Buildings, Healthcare, Office, Non-critical buildings, Residential, School, Hotel |
| Device application | Low voltage fan coil |
| Net weight | 340 g |
| Product or component type | Room controller |
| Product name | SE8000 Series |
| Device short name | SE8300 |
| Height | 120 mm |
| Directives | 2014/30/EU - electromagnetic compatibility, 2014/35/EU - low voltage directive, 2014/53/EU - radio equipment directive |
| [In] rated current | 4 A |
| Temperature resolution | 0.1 °C |
| Housing colour | Silver |
| Ambient air temperature for storage | -30…50 °C |
| Depth | 25 mm |
| Ambient air temperature for operation | 0…50 °C |
| Measurement accuracy | Temperature: +/- 0.5 °C,, Humidity: +/- 5 %, 20...80 % RH (non-condensing), Humidity: +/- 10 %, 10...20 % (non-condensing), Humidity: +/- 10 %, 80...90 % (non-condensing) |
| Information displayed | Temperature: - 40...122 °F |
| Network frequency | 50 Hz, 60 Hz |
| Communication port protocol | BACnet MS/TP, Modbus RTU, Zigbee Pro |
| Relative humidity | 0…95 % |
| Temperature setting range | 12…37.5 °C cooling, 4.5…32 °C heating |
| Calibration certificate | 1 pt |
| Sensor type | 10 kOhm T2 NTC thermistor temperature, Space RH sensor humidity, Bulk polymer humidity |
| Output current | 1 A relay output, 3 A relay output (inrush), 0.3 A universal output, 1.5 A universal output (inrush) |
| [Us] rated supply voltage | 24 V AC 50/60 Hz +/- 15 % |
| Input type | 2 x dry contact, 5 x analog |
| Output voltage | 24 V AC for relay output, 0...10 V DC for analog output |
| Output type | 5 xrelay output, 4 xuniversal |
| Standards | EN/IEC 60730-1, EN/IEC 60730-2-9, EN/IEC 60730-2-13, CSA E60730-2-9, UL 60730-2-9, UL 60730-2-13, ICES-003, FCC part 15 Subpart B, ETSI EN 300 328:v2.1.1, ETSI EN 301 489-1:v1.9.2, FCC part 15 Subpart C, ETSI EN 301 489-17:v2.2.1, 2012, RSS 247 |
| Humidity setting range | 30…95 % |
| Input voltage | 0...10 V DC |
| Range | EcoStruxure Building Expert |
| Economizer | No |
| Humidity control | Yes |
| PIR cover | Yes |
| Scheduling | No |
| surface treatment | Untreated |
| Surface finish | Matt |
| Function available | Fan control, HVAC control, Available with CO2/RH/T, Brightness sensor, Changes can be made directly over display, Code lock function, Easily configurable, Firmware update by USB |
| Package 1 | 1 PCE, 15.4 cm × 10.7 cm × 4.8 cm (L × W × H), 425 g |
Official documents from Schneider Electric, downloaded directly from the manufacturer.
SE8350U5B00PH is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for SE8350U5B00PH and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for SE8350U5B00PH, subject to availability and destination.

Hotel Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, White Case/Fascia.

Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, PIR motion sensor, Silver Case/Fascia

Hotel Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, PIR motion sensor, Silver Case/Fascia.

Low-Voltage FCU Room Controller & Zone Controller: BACnet MS/TP, ZigBee Embedded, RH sensor, PIR motion sensor, Silver Case/Fascia

Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, PIR motion sensor, White Case/Fascia

Hotel Low-Voltage Fan Coil Room Controller & Zone Controller: BACnet MS/TP, RH sensor & control, PIR motion sensor, White Case/Fascia.

Low-Voltage FCU Room Controller & Zone Controller: BACnet MS/TP, ZigBee Embedded, RH sensor & control, PIR sensor, White Case/Fascia

Hotel LV Fan Coil Room Controller & Zone Controller: BACnet MS/TP, ZigBee Embedded, IP ready, RH sensor & control, PIR sensor, White Case/Fascia.