Quick facts
| Availability | Confirmed on request |
| Category | Altivar 71 |
| Lifecycle | Discontinued |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Country of origin | CN |
| UPC / EAN | 3389119214957 |
| Datasheet | Manufacturer datasheet ↗ |
Shipping & availability
Can I still buy the ATV71HC13Y now that it is discontinued?
Yes. Schneider Electric has discontinued the ATV71HC13Y, but sourcing discontinued parts is what PartnerPLC specialises in — new old stock, used and refurbished units. Request a quote and we'll confirm availability, condition and lead time.
When can ATV71HC13Y be shipped?
ATV71HC13Y is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up ATV71HC13Y in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for ATV71HC13Y and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for ATV71HC13Y, subject to availability and destination.
Schneider Electric ATV71HC13Y — variable speed drive ATV71 - 132kW - 690V - EMC filter-graphic terminal (Altivar 71). Discontinued by Schneider Electric. PartnerPLC sources discontinued and surplus Schneider Electric automation parts — request a quote for price, condition and lead time.
Specifications
Main
| Range of product | Altivar 71 |
| Product or component type | Variable speed drive |
| Product specific application | Complex, high-power machines |
| Component name | ATV71 |
| Motor power kW | 110 kW, 3 phases at 500 V; 132 kW, 3 phases at 690 V |
| Motor power hp | 150 hp, 3 phases at 575 V |
| Maximum motor cable length | 15 m shielded cable; 30 m unshielded cable |
| power supply voltage | 500...690 V - 15...10 % |
| Network number of phases | 3 phases |
| Line current | 133 A for 600 V 3 phases / 150 hp; 137 A for 690 V 3 phases 132 kW; 153 A for 500 V 3 phases 110 kW |
| EMC filter | Integrated |
| Assembly style | With heat sink |
| Variant | Reinforced version |
| Prospective line Isc | 28 kA for 3 phases |
| Nominal output current | 144 A at 2.5 kHz 575 V 3 phases / 150 hp; 150 A at 2.5 kHz 690 V 3 phases 132 kW; 165 A at 2.5 kHz 500 V 3 phases 110 kW |
| Maximum transient current | 247.5 A for 60 s 3 phases 110 kW; 272.25 A for 2 s 3 phases / 150 hp; 272.25 A for 2 s 3 phases 132 kW |
| Output frequency | 0.1…500 Hz |
| Nominal switching frequency | 2.5 kHz |
| Switching frequency | 2.5...4.9 kHz adjustable; 2.5...4.9 kHz with derating factor |
| Asynchronous motor control profile | Voltage/frequency ratio (2 or 5 points); ENA (Energy adaptation) system for unbalanced loads; Flux vector control (FVC) with sensor (current vector); Sensorless flux vector control (SFVC) (voltage or current vector) |
| Type of polarization | No impedance for Modbus |
Complementary
| Product destination | Asynchronous motors; Synchronous motors |
| power supply voltage limits | 425…759 V |
| power supply frequency | 50...60 Hz - 5...5 % |
| power supply frequency limits | 47.5...63 Hz |
| Speed range | 1…100 for asynchronous motor in open-loop mode, without speed feedback; 1…1000 for asynchronous motor in closed-loop mode with encoder feedback; 1…50 for synchronous motor in open-loop mode, without speed feedback |
| Speed accuracy | +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn; +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn |
| Torque accuracy | +/- 15 % in open-loop mode, without speed feedback; +/- 5 % in closed-loop mode with encoder feedback |
| Transient overtorque | 170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes; 220 % of nominal motor torque +/- 10 % for 2 s |
| Braking torque | <= 150 % with braking or hoist resistor; 30 % without braking resistor |
| Synchronous motor control profile | Vector control without speed feedback |
| Regulation loop | Adjustable PI regulator |
| Motor slip compensation | Automatic whatever the load; Suppressable; Adjustable; Not available in voltage/frequency ratio (2 or 5 points) |
| diagnostic | 1 LED (red) for drive voltage |
| Output voltage | <= power supply voltage |
| Insulation | Electrical between power and control |
| type of cable for mounting in an enclosure | With a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC; With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |
| Electrical connection | Terminal, clamping capacity: 2.5 mm², 14 AWG (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); Terminal, clamping capacity: 2 x 120 mm² (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3); Terminal, clamping capacity: 120 mm² (PA, PB); Terminal, clamping capacity: 2 x 120 mm² (PC/-, PO, PA/+) |
| Tightening torque | 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); 24 N.m, 212 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3); 24 N.m, 212 lb.in (PA, PB); 24 N.m, 212 lb.in (PC/-, PO, PA/+) |
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection; Internal supply: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
| Analogue input number | 2 |
| Analogue input type | AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign; AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits; AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits |
| input sampling time | 2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s); 2 ms +/- 0.5 ms (Al2) - analog input(s); 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s); 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s) |
| Response time | <= 100 ms in STO (Safe Torque Off); AO1 2 ms, tolerance +/- 0.5 ms for analog output(s); R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s); R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
| absolute accuracy precision | +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C; +/- 0.6 % (AI2) for a temperature variation 60 °C; +/- 1 % (AO1) for a temperature variation 60 °C |
| Linearity error | +/- 0.15 % of maximum value (AI1-/Al1+, AI2); +/- 0.2 % (AO1) |
| Analogue output number | 1 |
| Analogue output type | AO1 software-configurable logic output 10 V 20 mA; AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits; AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits |
| Discrete output number | 2 |
| Discrete output type | Configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles; Configurable relay logic: (R2A, R2B) NO - 100000 cycles |
| Minimum switching current | 3 mA at 24 V DC for configurable relay logic |
| Maximum switching current | R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4; R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4; R1, R2: 5 A at 250 V AC resistive load, cos phi = 1; R1, R2: 5 A at 30 V DC resistive load, cos phi = 1 |
| Discrete input number | 7 |
| Discrete input type | LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm; LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm; LI6: switch-configurable PTC probe 0…6, impedance: 1500 Ohm; PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d |
| Discrete input logic | Negative logic (sink) (LI1...LI5), > 16 V (state 0), < 10 V (state 1); Positive logic (source) (LI1...LI5), < 5 V (state 0), > 11 V (state 1); Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1); Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1) |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s; S, U or customized; Automatic adaptation of ramp if braking capacity exceeded, by using resistor |
| Braking to standstill | By DC injection |
| Protection type | Against exceeding limit speed: drive; Against input phase loss: drive; Break on the control circuit: drive; Input phase breaks: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Overvoltages on the DC bus: drive; Short-circuit between motor phases: drive; Thermal protection: drive; Motor phase break: motor; Power removal: motor; Thermal protection: motor |
| Insulation resistance | > 1 mOhm 500 V DC for 1 minute to earth |
| Frequency resolution | Analog input: 0.024/50 Hz; Display unit: 0.1 Hz |
| Communication port protocol | CANopen; Modbus |
| Connector type | 1 RJ45 (on front face) for Modbus; 1 RJ45 (on terminal) for Modbus; Male SUB-D 9 on RJ45 for CANopen |
| Physical interface | 2-wire RS 485 for Modbus |
| Transmission frame | RTU for Modbus |
| Transmission rate | 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal; 9600 bps, 19200 bps for Modbus on front face; 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen |
| Data format | 8 bits, 1 stop, even parity for Modbus on front face; 8 bits, odd even or no configurable parity for Modbus on terminal |
| Number of addresses | 1…127 for CANopen; 1…247 for Modbus |
| Method of access | Slave CANopen |
| Marking | CE |
| Operating position | Vertical +/- 10 degree |
| Height | 1190 mm |
| Depth | 377 mm |
| Width | 340 mm |
| Net weight | 116 kg |
| Option card | Communication card for CC-Link; Controller inside programmable card; Communication card for DeviceNet; Communication card for EtherNet/IP; Communication card for Fipio; I/O extension card; Communication card for Interbus-S; Interface card for encoder; Communication card for Modbus Plus; Communication card for Modbus TCP; Communication card for Modbus/Uni-Telway; Overhead crane card; Communication card for Profibus DP; Communication card for Profibus DP V1 |
Environment
| Noise level | 77 dB conforming to 86/188/EEC |
| Dielectric strength | 3110 V DC between earth and power terminals; 5345 V DC between control and power terminals |
| Electromagnetic compatibility | 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Standards | IEC 61800-3; IEC 61800-5-1; EN 55011 class A group 2; UL Type 1; IEC 60721-3-3 class 3C2; IEC 61800-3 environments 2 category C3; IEC 61800-3 environments 1 category C3 |
| Product certifications | GOST; C-Tick; NOM 117; CSA; UL |
| Pollution degree | 2 conforming to IEC 61800-5-1; 3 conforming to UL 840 |
| IP degree of protection | IP41 on upper part conforming to IEC 60529; IP41 on upper part conforming to IEC 61800-5-1; IP54 on lower part conforming to IEC 60529; IP54 on lower part conforming to IEC 61800-5-1; IP00 conforming to IEC 60529; IP00 conforming to IEC 61800-5-1; IP30 on side parts conforming to IEC 60529; IP30 on side parts conforming to IEC 61800-5-1; IP30 on the front panel conforming to IEC 60529; IP30 on the front panel conforming to IEC 61800-5-1 |
| Vibration resistance | 0.6 gn (f= 10…200 Hz) conforming to IEC 60068-2-6; 1.5 mm peak to peak (f= 3…10 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 7 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -10…50 °C (without derating) |
| Ambient air temperature for storage | -25…70 °C |
| Operating altitude | <= 1000 m without derating; 1000...2260 m with current derating 1 % per 100 m |
Downloads & documentation
Official documents from Schneider Electric, downloaded directly from the manufacturer.
Data sheets & manuals
| Product data sheet ATV71HC13Y |
More Schneider Electric parts
Available on requestvariable speed drive ATV71 - 132kW-200HP - 480V - EMC filter-graphic terminal
Available on requestvariable speed drive ATV71 - 132kW-200HP - 480V - EMC filter-graphic terminal
Available on requestvariable speed drive ATV71 - 132kW-200HP - 480V - EMC filter-graphic terminal
Available on requestSPEEDDRIVE200HP460VATV71+CONDUIT BOX
Available on requestvariable speed drive ATV71 - 160kW-250HP - 480V - EMC filter-graphic terminal
Available on requestvariable speed drive ATV71 - 160kW-250HP - 480V - EMC filter-graphic terminal
Available on requestSPEEDDRIVE250HP460VATV71+CONDUIT BOX
Available on requestvariable speed drive ATV71 - 160kW - 690V - EMC filter-graphic terminal