Miniature circuit breaker (MCB), Acti9 C120N, 4P, 125A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

MPN
A9N18355
EAN
3606480379291
Category
Acti9 C120
Price and lead time confirmed within 1 business day
Request a Quote

A real person replies, typically within 1 business day — see our privacy policy.

What happens next
  1. We check stock, condition and lead time
  2. You get a written quote by email
  3. Approve it and we ship — in-stock parts within 1 business day
  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • Ships via
  • 100% positive eBay feedback

Have spare Schneider Electric parts? We buy surplus →

What is the Schneider Electric A9N18355?

This Acti9 C120N product is a low-voltage miniature circuit breaker (MCB). It is a 4P circuit breaker with 4 protected poles, 125A rated current and a B tripping curve. The rated short circuit breaking capacity goes up to 10000A at 400VAC, conforming to IEC/EN 60898-1 standard. This product complies with residential standard IEC/EN 60898-1 and industrial standard IEC/EN 60947-2. It combines functions of circuit protection against short circuit and overload current, control and isolation. The presence of a green strip guarantees contact open physically and allows work to be carried out safely on the downstream circuit. It is designed to offer a high industrial performance level. It boasts exceptional durability, with electrical endurance reaching up to 5000 cycles and mechanical endurance extending to 20000 cycles. The rated operational voltage is from 380VAC to 415VAC. The rated insulation voltage is 500VAC, and the rated impulse withstand voltage is 6kV. Additionally, its limitation class 3 enhances the downstream circuit protection cost, while the pollution degree 3 ensures reliable performance in challenging environments. It can be mounted on a 35mm symmetrical DIN rail. The width in 9mm pitches is 12. The dimensions are (W) 108mm x (H) 81mm x (D) 73mm. The product colour is white. The weight is 0.82kg. It offers reliable protection with an IP20 rating on its terminals. The operating temperature is from -25°C to 70°C. The storage temperature is from -40°C to 85°C.

Specifications

Specifications

RangeActi9
Product nameActi9 C120
Product or component typeMiniature circuit-breaker
Device short nameC120N
Device applicationDistribution
Poles description4P
Number of protected poles4
[In] rated current125 A at 30 °C
Network typeAC
Trip unit technologyThermal-magnetic
Curve codeB
Breaking capacity10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1, 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2, 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2
Suitability for isolationYes conforming to IEC 60947-2
StandardsEN/IEC 60947-2, EN/IEC 60898-1
Product certificationsEAC
Network frequency50/60 Hz
[Ue] rated operational voltage380...415 V AC 50/60 Hz, <= 500 V DC, 220...240 V AC 50/60 Hz, 440 V AC 50/60 Hz, 230...400 V AC 50/60 Hz
Magnetic tripping limit3...5 x In
[Ics] rated service breaking capacity7500 A 75 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz, 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz, 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz, 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz, 10 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC
Limitation class3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Comb busbar and distribution block compatibilityYES
9 mm pitches12
Height81 mm
Depth73 mm
Width108 mm
Net weight0.82 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability5000 cycles conforming to IEC 60947-2
Locking options descriptionHandle sealable with cable diameter 0.7mm in OFF or ON position
Connections - terminalsTunnel type terminals1…50 mm² rigid, Tunnel type terminals1.5…35 mm² flexible
Wire stripping length15 mm
Tightening torque3.5 N.m
Earth-leakage protectionSeparate block
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Overvoltage categoryIV
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Operating altitude2000 m
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C

Packaging

Package 11 PCE, 10.800 cm × 8.800 cm × 7.500 cm (L × W × H), 777.000 g
Package 23 BB1, 33.100 cm × 9.500 cm × 8.500 cm (L × W × H), 2.391 kg
Package 318 S03, 40.000 cm × 30.000 cm × 30.000 cm (L × W × H), 14.928 kg

Downloads & documentation

Official documents from Schneider Electric, downloaded directly from the manufacturer.

Data sheets & manuals

A9N18355: frequently asked questions

When can A9N18355 be shipped?

A9N18355 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up A9N18355 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for A9N18355 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for A9N18355, subject to availability and destination.

More Schneider Electric parts

Schneider Electric A9N18351 – Miniature circuit breaker (MCB), Acti9 C120N, 3P, 125A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18351

Miniature circuit breaker (MCB), Acti9 C120N, 3P, 125A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18352 – Miniature circuit breaker (MCB), Acti9 C120N, 4P, 63A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18352

Miniature circuit breaker (MCB), Acti9 C120N, 4P, 63A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18353 – Miniature circuit breaker (MCB), Acti9 C120N, 4P, 80A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18353

Miniature circuit breaker (MCB), Acti9 C120N, 4P, 80A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18354 – Miniature circuit breaker (MCB), Acti9 C120N, 4P, 100A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18354

Miniature circuit breaker (MCB), Acti9 C120N, 4P, 100A, B curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18356 – Miniature circuit breaker (MCB), Acti9 C120N, 1P, 63A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18356

Miniature circuit breaker (MCB), Acti9 C120N, 1P, 63A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18357 – Miniature circuit breaker (MCB), Acti9 C120N, 1P, 80A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18357

Miniature circuit breaker (MCB), Acti9 C120N, 1P, 80A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18358 – Miniature circuit breaker (MCB), Acti9 C120N, 1P, 100A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18358

Miniature circuit breaker (MCB), Acti9 C120N, 1P, 100A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18359 – Miniature circuit breaker (MCB), Acti9 C120N, 1P, 125A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)
Schneider Electric
A9N18359

Miniature circuit breaker (MCB), Acti9 C120N, 1P, 125A, C curve, 10000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider Electric A9N18355Price and lead time confirmed within 1 business day
Request a Quote