Pepperl Fuchs VAA-2EA-G1-ZE/P-S
AS-Interface pneumatic module
- MPN
- VAA-2EA-G1-ZE/P-S
- Category
- Modules
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs VAA-2EA-G1-ZE/P-S?
AS-Interface certificate
Degree of protection IP65
Flat or round cable connection (via standardized EMS base, not included with delivery)
Cable piercing method for flat cable
Inputs for 2- and 3-wire sensors
Function display for bus, inputs and outputs
Direct connection of pneumatic cylinders
Pneumatic module, 2 inputs and 2 pneumatic outputs
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 048157 |
| Node type | Standard node |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Indicators/operating means
| LED AS-i | AS-Interface voltage; LED green |
| LED IN | switching state (input); 2 LED yellow |
| LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface Ue |
| Rated operating current | ≤ 45 mA (without sensors) Ie |
Input
| Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC |
| Supply | from AS-Interface |
| Current loading capacity | ≤ 100 mA, short-circuit protected |
| Switching point | OFF: ≤ 1.5 mA ON: ≥ 5 mA, ≥ 10 V |
Output
| Number/Type | 2 pneumatic outputs with separated 3/2-way valves |
Pneumatic output
| Venting guide | Sinter filter |
| Compressed air | 2 ... 8 bar, filtered (5 µm), oiled or unoiled compressed air |
| Air throughput | 400 l/min |
| Valve cross-section | 5 mm |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity
| Degree of protection | EN 60529:2000 |
| AS-Interface | EN 62026-2:2013 |
Programming instructions
| Profile | S-3.F |
| IO code | 3 |
| ID code | F |
| ID1 code | F |
| ID2 code | F |
| Data bits (function via AS-Interface) | InputOutput |
| D0 | IN1 - |
| D1 | IN2 - |
| D2 | - OUT3 |
| D3 | - OUT4 |
| Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Ambient conditions
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
| Storage temperature | -20 ... 55 °C (-4 ... 131 °F) |
Mechanical specifications
| Degree of protection | IP65 according to EN 60529 |
| Connection | cable piercing methos or terminals flat cable or standard round cable inputs: M12 x 1 quick disconnect outputs: plug-in hose connector (8 mm) |
| Mass | approx. 200 g |
| Dimensions: Height | 60 mm |
| Dimensions: Width | 45 mm |
| Dimensions: Length | 102 mm |
| Mounting | DIN rail or screw mounting |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (1)
VAA-2EA-G1-ZE/P-S: frequently asked questions
When can VAA-2EA-G1-ZE/P-S be shipped?
VAA-2EA-G1-ZE/P-S is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up VAA-2EA-G1-ZE/P-S in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for VAA-2EA-G1-ZE/P-S and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for VAA-2EA-G1-ZE/P-S, subject to availability and destination.