Pepperl Fuchs NJ50-FP-N-P1
Inductive sensor
- MPN
- NJ50-FP-N-P1
- Category
- Inductive Sensors
Request a Quote
- 1We check stock, condition and lead time
- 2You get a written quote by email
- 3Approve it and we ship — in-stock parts within 1 business day
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- 100% positive eBay feedback
- Ships via
What is the Pepperl Fuchs NJ50-FP-N-P1?
50 mm non-flush
NAMUR output
Switching function: Normally closed (NC), Output type: NAMUR, Installation: non-flush, Output type: 2-wire, Construction type: Rectangular, Series: Rectangular type, Type of voltage: DC, Equipment protection level Ga: IECEx PTB 11.0021X, Equipment protection level Gb: IECEx PTB 11.0021X, Equipment protection level Da: IECEx PTB 11.0021X, Equipment protection level Mb: IECEx PTB 11.0021X, Equipment protection level Ga: PTB 00 ATEX 2032 X, Equipment protection level Gb: PTB 00 ATEX 2032 X
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 70133037 |
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 50 mm sn |
| Installation | non-flush |
| Assured operating distance | 0 ... 40.5 mm sa |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.3 |
| Reduction factor r304 | 0.85 |
| Output type | 2-wire |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Nominal ratings
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) Uo |
| Switching frequency | 0 ... 100 Hz f |
| Current consumption: Measuring plate not detected | ≥ 3 mA |
| Current consumption: Measuring plate detected | ≤ 1 mA |
Safety-relevant product characteristics
| MTTFd | 11400 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives
| Standard conformity: NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standard conformity: Standards | EN IEC 60947-5-2 |
Approvals and certificates
| IECEx approval: Equipment protection level Ga | IECEx PTB 11.0021X |
| IECEx approval: Equipment protection level Gb | IECEx PTB 11.0021X |
| IECEx approval: Equipment protection level Da | IECEx PTB 11.0021X |
| IECEx approval: Equipment protection level Mb | IECEx PTB 11.0021X |
| ATEX approval: Equipment protection level Ga | PTB 00 ATEX 2032 X |
| ATEX approval: Equipment protection level Gb | PTB 00 ATEX 2032 X |
| ATEX approval: Equipment protection level Da | PTB 00 ATEX 2032 X |
| UL approval | cULus Listed Load Type: General Purpose Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0451 |
| CCC approval: Hazardous Location | 2020322315002304 |
| CML approval | on request |
| ANZEx | 19.3001X |
Ambient conditions
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications
| Connection type | screw terminals |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Core cross section | up to 2.5 mm2 , stripped insulation length: 7 mm |
| Minimum core cross-section | without wire end ferrules 0.5 mm2 , with connector sleeves 0.34 mm2 |
| Maximum core cross-section | without wire end ferrules 2.5 mm2 , with connector sleeves 1.5 mm2 |
| Connection (system side) | screw terminals , M20 x 1.5 cable gland , usable thread length 10 mm , screw-in depth max. 10 mm |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| Dimensions: Height | 40 mm |
| Dimensions: Width | 80 mm |
| Dimensions: Length | 80 mm |
| Note | Tightening torque: 1.8 Nm (housing) |
General information
| Use in the hazardous area | see instruction manuals |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
Certificates (9)
- Japan CML Ex ia (CML 21JPN2712X)
- Canada USA UL Ordinary Location (UL-US-2140027-2 / UL-CA-2133552-2)
- EU PTB ATEX ia 2G, 1G, 1D s. certificate (PTB 00 ATEX 2032 X)
- China SITIIAS CCC Ex Certificate (2020322315002304 (Mannheim))
- Taiwan OSHA Ex ia (ML141200701630)
- EU Declaration of Conformity (Pepperl+Fuchs)
- Canada USA UL Hazardous Location (E501628:1:1)
- EU Declaration of Conformity (Pepperl+Fuchs)
- Australia Test Safe (ANZEx 19.3001X)
NJ50-FP-N-P1: frequently asked questions
When can NJ50-FP-N-P1 be shipped?
NJ50-FP-N-P1 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up NJ50-FP-N-P1 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for NJ50-FP-N-P1 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for NJ50-FP-N-P1, subject to availability and destination.
More Pepperl Fuchs parts