What is the Pepperl Fuchs K34-STR-24..30V-3X500VAC-10A?
8 A output load
3 x 380 ... 500 V AC supply voltage
Sustained short-circuit proof, overload-proof and open-circuit proof
23 ... 30 VDC output voltage, can be regulated
LED operating display
LED output overload indicator
SELV
Suitable for AS-Interface power supply in gateway-integrated data decoupling
Switched mode power supply, 23 ... 30 V DC, 8 A
Specifications
General specifications
| Order code (Pepperl+Fuchs part number) | 211139 |
| UL File Number | E223176 |
| Lifecycle | Active (current Pepperl+Fuchs product) |
Indicators/operating means
| LED Overload | Red LEDlights up for overload, flashes for hiccup mode |
| LED PWR | LED green |
| Potentiometer | Output voltage settings: 23 ... 30 VDC |
Electrical specifications
| Capacity factor | 0.55 capacitive |
| Rated operating voltage | 3 x 340 ... 550 V AC Ue |
| Rated operating current | 3 x 700 mA At 400 VAC Ie |
| Supply frequency | 47 ... 63 Hz |
| Efficiency | 89 % |
| Nominal voltage | 3 x 380 ... 500 V AC |
Output
| Current limit | 12.5 A |
| Voltage | 30 V ± 1 % Adjustment range 23 to 30 V DC |
| Current | 0 ... 8 A |
Directive conformity
| Electromagnetic compatibility: Directive 2014/30/EU | EN 55011, EN 61000-6-1, EN 61000-6-2 |
| Low voltage: Directive 2014/35/EU | EN 55011, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 class A, EN 61000-3-3, EN 61010-1 |
Conformity
| Degree of protection | IEC 60529:2001 |
Standard conformity
| Standards | Harmonic waves: EN 61000-3-2 Class AInterference suppression: EN 55011 Class BElectrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge)Electromagnetic fields: IEC 61000-4-3 (10 V/m)Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled)Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical)Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz) |
Ambient conditions
| Ambient temperature | -10 ... 60 °C (14 ... 140 °F) with free convection non-condensing |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications
| Degree of protection | IP20 |
| Protection class | I, Protective conductor connection necessary |
| Connection | Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
| Mass | approx. 1400 g |
| Dimensions: Height | 153 mm |
| Dimensions: Width | 81 mm |
| Dimensions: Length | 160 mm |
| Mounting | DIN mounting rail |
No matching specifications
Downloads & documentation
Official documents from Pepperl Fuchs, downloaded directly from the manufacturer.
Data sheets & manuals
CAD & dimension drawings
K34-STR-24..30V-3X500VAC-10A: frequently asked questions
When can K34-STR-24..30V-3X500VAC-10A be shipped?
K34-STR-24..30V-3X500VAC-10A is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up K34-STR-24..30V-3X500VAC-10A in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for K34-STR-24..30V-3X500VAC-10A and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for K34-STR-24..30V-3X500VAC-10A, subject to availability and destination.
More Pepperl Fuchs parts