Keyence GC-1000

Main controller Standard type. . Series: Safety Controller. Series code: GC series

MPN
GC-1000
Price and lead time confirmed within 1 business day
Request a Quote
  1. 1We check stock, condition and lead time
  2. 2You get a written quote by email
  3. 3Approve it and we ship — in-stock parts within 1 business day

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • 100% positive eBay feedback
  • Ships via

Have spare Keyence parts? We buy surplus →

What is the Keyence GC-1000?

Main controller Standard type. GC-1000. Series: Safety Controller. Series code: GC series

Specifications

Specifications

Model NameMain controller Standard type
Model CodeGC-1000
Series TitleSafety Controller
Series CodeGC series
Data Sheet URLhttps://www.keyence.com/download/download/confirmation/?dlSeriesId=WS_SR57359&dlModelId=PM_2691000&dlSiteId=1&dlLanguageId=en-US&dlLangType=en-US
CAD URLhttps://www.keyence.com/products/safety/safety-controller/gc/downloads/?mode=cd&modelId=PM_2691000
Manuals URLhttps://www.keyence.com/products/safety/safety-controller/gc/downloads/?mode=ma&modelId=PM_2691000
ModelGC-1000
Input/output points - Safety inputs16
Input/output points - Safety outputs6
Input/output points - Safety relay output-
Input/output points - AUX outputs4
Maximum number of connectable expansion units10*1
Maximum number of connectable remote I/O modules4
GC-Link ports2 ports
Safety input specifications - Input deviceContact output device or PNP output device
Safety input specifications - Input typeType3
Safety input specifications - ON level (voltage/current)Min. 11 V/2 mA
Safety input specifications - OFF level (voltage/current)Max. 5 V/1.5 mA
Safety input specifications - Short-circuit currentSi 0 to 3: Approx. 5 mASi 4 to 15: Approx. 3 mA
Safety input specifications - Protection circuitSurge protection circuit, wrong wiring protection circuit
Safety input specifications - Maximum cable lengthMax. 100 m 328.1'
Safety output specifications - Output typePNP transistor output (DC-13, Type 0.5, Protected outputs)*2
Safety output specifications - Maximum load current500 mA
Safety output specifications - Residual voltage (during ON)Max. 2.0 V
Safety output specifications - Leakage current (during OFF)Max. 0.5mA
Safety output specifications - Maximum capacitive load0.5 µF
Safety output specifications - Load wiring resistanceMax. 2.5Ω
Safety output specifications - Protection circuitOvercurrent protection circuit, reverse connection protection circuit
Safety output specifications - Maximum cable lengthMax. 30 m 98.4'
Safety relay output specifications - Output type-
Test output specifications - Output typePNP transistor output*3
Test output specifications - Maximum load current100 mA
Test output specifications - Protection circuitOvercurrent protection circuit, reverse connection protection circuit
Test output specifications - Maximum cable lengthMax. 100 m 328.1'*4
AUX output specifications - Output typeTransistor output (PNP/NPN selectable by wiring)PNP output (DC-13, Type 0.1, Protected outputs)*2*3
AUX output specifications - Maximum load currentPNP: 100 mA, NPN: 20 mA
AUX output specifications - Residual voltage (during ON)Max. 2.0 V
AUX output specifications - Leakage current (during OFF)Max. 0.5 mA
AUX output specifications - Protection circuitOvercurrent protection circuit, reverse connection protection circuit
AUX output specifications - Maximum cable lengthMax. 30 m 98.4'
Communication interface - USBUSB2.0
Communication interface - Ethernet100BASE-TXSTP (shielded twisted pair) cable of Category 5 or higher
Network functionalityEtherNet/IP™ *5, PROFINET, Modbus/TCP, MC protocol, UDP
Others - LCD display1.77-inch color LCD
Others - Display buttons4 points (3 operation keys + 1 BACK key)
Applicable standards - EMCEMS: IEC 61131-2/-6, EN61131-2/-6EMI: IEC 61131-2, FCC Part15B Class A,ICES-003, Class A
Applicable standards - SafetyIEC 61508, EN 61508 SIL3IEC62061 SIL CL3ISO/EN13849-1:2015 Cat. 4, PL e, UL1998
Dimensions60×95×90 mm 2.36"× 3.74"×3.54" (W×D×H)
Power supply - Power voltage24 VDC (-30 to +20%) Class 2
Power supply - Power consumptionMax. 200 mA
Environmental resistance - Ambient temperature−10 to +55 °C 14 to 131 °F (No freezing)
Environmental resistance - Relative humidity5 to 85% (No condensation)
Environmental resistance - Storage temperature−25 to +70 °C -13 to 158 °F (No freezing)
Environmental resistance - Operating altitudeMax. 2000 m 6561.7'
Environmental resistance - Overvoltage categoryII
Environmental resistance - Pollution degree2
Environmental resistance - Vibration resistanceFrequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14"Frequency: 9 to 150 Hz, Acceleration: 10 m/s210 times each in X, Y, Z directions
Environmental resistance - Shock resistanceAcceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions
MaterialPolycarbonate
WeightApprox. 260 g

GC-1000: frequently asked questions

When can GC-1000 be shipped?

GC-1000 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up GC-1000 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for GC-1000 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for GC-1000, subject to availability and destination.

More Keyence parts

Keyence FW-V20 – Amplifier Unit. . Series: High Power Digital Ultrasonic Sensors. Series code: FW series
Keyence
FW-V20

Amplifier Unit. . Series: High Power Digital Ultrasonic…

Keyence FW-V20P – Amplifier Unit PNP. . Series: High Power Digital Ultrasonic Sensors. Series code: FW series
Keyence
FW-V20P

Amplifier Unit PNP. . Series: High Power Digital Ultrasonic…

Keyence FW-V25 – Amplifier Unit. . Series: High Power Digital Ultrasonic Sensors. Series code: FW series
Keyence
FW-V25

Amplifier Unit. . Series: High Power Digital Ultrasonic…

Keyence FW-V25P – Amplifier Unit PNP. . Series: High Power Digital Ultrasonic Sensors. Series code: FW series
Keyence
FW-V25P

Amplifier Unit PNP. . Series: High Power Digital Ultrasonic…

Keyence GC-1000R – Main controller Relay output type. . Series: Safety Controller. Series code: GC series
Keyence
GC-1000R

Main controller Relay output type.

Keyence GC-A16 – Auxiliary output unit. . Series: Safety Controller. Series code: GC series
Keyence
GC-A16

Auxiliary output unit. . Series: Safety Controller. Series…

Keyence GC-B30 – Bus extension unit. . Series: Safety Controller. Series code: GC series
Keyence
GC-B30

Bus extension unit. . Series: Safety Controller. Series…

Keyence GC-R45 – Remote I/O modules Standard (5-pin). . Series: Safety Controller. Series code: GC series
Keyence
GC-R45

Remote I/O modules Standard (5-pin).

Keyence GC-1000Price and lead time confirmed within 1 business day