Beckhoff KL9560
Power supply unit terminal 24 V DC/24 V DC, 0.1 A
- MPN
- KL9560
- Category
- KL9xxx | System
Request a Quote
- 12-month warranty (new) · 3-month (used/refurbished)
- 30-day returns, no restocking fee on unused parts
- Ships via
What is the Beckhoff KL9560?
The KL9560 power supply unit terminal generates an electrically isolated output voltage from the 24 V DC input voltage, which can be accessed at the terminal. The following Bus Terminals are also supplied with this voltage via the power contacts. The
Specifications
Specifications
| Input voltage | 24 V DC (-15%/+20%) |
| Output voltage | 24 V DC (-15%/+5%) |
| Output current | ≤ 0.1 A |
| Short-circuit current | approx. 0.15 A |
| Efficiency | approx. 85% |
| Diagnostics in the process image | yes |
| Short-circuit proof | yes, automatic restart |
| Insulation voltage input/output | 500 V AC permanent load |
| Insulation voltage | 1,500 V AC constant load field/K-bus |
| Residual ripple | no data |
| Special features | analog voltage with electrical isolation |
| Weight | approx. 65 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Pluggable wiring | for all KSxxxx Bus Terminals |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
| Design form | compact terminal housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
KL9560: frequently asked questions
When can KL9560 be shipped?
KL9560 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up KL9560 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for KL9560 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KL9560, subject to availability and destination.
More Beckhoff parts