Beckhoff KL1889

Bus Terminal, 16-channel digital input, 24 V DC, 3 ms, ground switching

MPN
KL1889
Price and lead time confirmed within 1 business day
Request a Quote

A real person replies, typically within 1 business day — see our privacy policy.

  • 12-month warranty (new) · 3-month (used/refurbished)
  • 30-day returns, no restocking fee on unused parts
  • Ships via

What is the Beckhoff KL1889?

The KL1889 digital input terminal acquires the binary 24 V DC control signals from the process level and transmits them, in an electrically isolated form, to the higher-level automation unit. The Bus Terminal contains sixteen channels whose signal states

Specifications

Specifications

Connection technology1-wire
Specificationground switching
Number of inputs16
Nominal voltage24 V DC (-15%/+20%)
“0” signal voltage18…30 V
“1” signal voltage0…7 V
Input filtertyp. 3.0 ms
Input currenttyp. 3 mA
Current consumption K-bustyp. 20 mA
Current consumption power contactstyp. 4 mA + load
Electrical isolation500 V (K-bus/field potential)
Bit width in the process image16 inputs
Configurationno address or configuration setting
Weightapprox. 55 g
Storage temperature-40…+85°C
Operating temperature-25…+60°C
Relative humidity95%, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable (see documentation)
Approvals/markingsCE, CCC, UL, ATEX, IECEx, DNV
Ex markingATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc
Design formHD (High Density) housing with signal LEDs
Materialpolycarbonate
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Marking–
Wiringsolid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver
Connection cross-sections*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm²
Stripping length8…9 mm
Dimensions (W x H x D)12 mm x 100 mm x 68 mm

KL1889: frequently asked questions

When can KL1889 be shipped?

KL1889 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.

Can I pick up KL1889 in person?

Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.

Is express delivery available?

Yes — mention it when you request a quote for KL1889 and we'll include express shipping options in our reply.

My factory is down and I need this urgently — can you help?

For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for KL1889, subject to availability and destination.

More Beckhoff parts

Beckhoff KL1859 – Bus Terminal, 8-channel digital input + 8-channel digital output, 24 V DC, 3 ms, 0.5 A
Beckhoff
KL1859

Bus Terminal, 8-channel digital input + 8-channel digital output, 24 V DC, 3 ms, 0.5 A

Beckhoff KL1862 – Bus Terminal, 16-channel digital input, 24 V DC, 3 ms, flat-ribbon cable
Beckhoff
KL1862

Bus Terminal, 16-channel digital input, 24 V DC, 3 ms, flat-ribbon cable

Beckhoff KL1862-0010 – Bus Terminal, 16-channel digital input, 24 V DC, 3 ms, ground switching, flat-ribbon cable
Beckhoff
KL1862-0010

Bus Terminal, 16-channel digital input, 24 V DC, 3 ms, ground switching, flat-ribbon cable

Beckhoff KL1872 – Bus Terminal, 16-channel digital input, 24 V DC, 0.2 ms, flat-ribbon cable
Beckhoff
KL1872

Bus Terminal, 16-channel digital input, 24 V DC, 0.2 ms, flat-ribbon cable

Beckhoff KL1904 – Bus Terminal, 4-channel digital input, 24 V DC, TwinSAFE
Beckhoff
KL1904

Bus Terminal, 4-channel digital input, 24 V DC, TwinSAFE

Beckhoff KL2012 – Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A
Beckhoff
KL2012

Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A

Beckhoff KL2022 – Bus Terminal, 2-channel digital output, 24 V DC, 2 A
Beckhoff
KL2022

Bus Terminal, 2-channel digital output, 24 V DC, 2 A

Beckhoff KL2032 – Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A, reverse voltage protection
Beckhoff
KL2032

Bus Terminal, 2-channel digital output, 24 V DC, 0.5 A, reverse voltage protection

Beckhoff KL1889Price and lead time confirmed within 1 business day
Request a Quote