EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, high-precision, TwinSAFE SC
EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC
The EL3362-0100 analog input terminal enables the direct connection of resistance bridges (strain gauges) or load cells using the 4-wire or 6-wire terminating system. It processes the ratio of the bridge voltage UBridge to the supply voltage USense and
| Number of inputs | 4, for 2 resistor bridge in full bridge technology |
| Function | resistance bridge, strain gauge (SG), voltage measurement |
| Wiring | solid conductors (s): direct plug-in technique; fine-stranded conductors (st) and ferrule (f): spring actuation by screwdriver |
| Ground reference (input) | differential |
| Max. sampling rate | 10 kSps |
| Sampling type | simultaneous |
| Internal resistance | > 1 MΩ |
| Supported nominal sensitivity | 0.5…320 mV/V |
| Sensor supply | 10 V DC from power contacts |
| Measuring range, nominal | USense: ±12 V | UBrdge: ±4 V |
| Measuring range, technical | USense: ±12.84 V | UBridge: ±4.28 V |
| Resolution | 24 bit |
| Measurement error/uncertainty | ±0.05% |
| Electrical isolation | Channel/channel | no |
| Power supply | via the E-bus |
| Distributed clocks | – |
| Electrical isolation | Channel/bus | 707 V DC (type test) |
| Current consumption E-bus | typ. 90 mA |
| Current consumption power contacts | typ. 30 mA, depends on UExc |
| Special features | integrated sensor supply |
| Weight | approx. 50 g |
| Operating temperature | 0…55°C |
| Storage temperature | -25…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE |
| Design form | HD (High Density) housing with signal LEDs |
| Material | polycarbonate |
| Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
| Side by side mounting by means of | double slot and key connection |
| Marking | labeling of the BZxxxx series |
| Connection cross-section | s*: 0.08…1.5 mm², st*: 0.25…1.5 mm², f*: 0.14…0.75 mm² |
| Connection cross-section AWG | s*: AWG28…16, st*: AWG22…16, f*: AWG26…19 |
| Stripping length | 8…9 mm |
| Current load power contacts | Imax: 10 A |
| Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
No matching specifications
EL3362-0100 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Yes — mention it when you request a quote for EL3362-0100 and we'll include express shipping options in our reply.
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for EL3362-0100, subject to availability and destination.

EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, high-precision, TwinSAFE SC

EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 1 x digital input, 1 x digital output

EtherCAT Terminal, 1-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 10 V DC

EtherCAT Terminal, 2-channel analog input, measuring bridge, full bridge, 24 bit, sensor supply 5/10 V DC, with 2 x digital combi


EtherCAT Terminal, 3-channel analog input, power measurement, 500 V AC, 5 A, 16 bit

EtherCAT Terminal, 3-channel analog input, power measurement, 500 V AC, 1 A, 16 bit, without EMC discharge

EtherCAT Terminal, 3-channel analog input, power measurement, 500 V AC, 0.1 A, 16 bit