| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Rated Operational Current AC-1 (I<sub>e</sub>) | (1000 V) 40 °C 375 A, (1000 V) 60 °C 325 A, (1000 V) 70 °C 260 A, (690 V) 40 °C 500 A, (690 V) 60 °C 400 A, (690 V) 70 °C 325 A |
| Rated Operational Current AC-3 (I<sub>e</sub>) | (415 V) 55 °C 305 A, (440 V) 55 °C 305 A, (500 V) 55 °C 290 A, (690 V) 55 °C 290 A, (1000 V) 55 °C 100 A, (380 / 400 V) 55 °C 305 A, (220 / 230 / 240 V) 55 °C 305 A |
| Rated Operational Current DC-1 (I<sub>e</sub>) | (100 V) 1 Pole, 40 °C 500 A, (100 V) 1 Pole, 60 °C 400 A, (100 V) 1 Pole, 70 °C 325 A, (110 V) 1-Pole, 40 °C 500 A, (110 V) 1-Pole, 60 °C 400 A, (110 V) 1-Pole, 70 °C 325 A, (110 V) 2 Poles in Series, 40 °C 500 A, (110 V) 2 Poles in Series, 60 °C 400 A, (110 V) 2 Poles in Series, 70 °C 325 A, (110 V) 3 Poles in Series, 40 °C 500 A, (110 V) 3 Poles in Series, 60 °C 400 A, (110 V) 3 Poles in Series, 70 °C 325 A, (175 V) 2 Poles in Series, 40 °C 500 A, (175 V) 2 Poles in Series, 60 °C 400 A, (175 V) 2 Poles in Series, 70 °C 325 A, (200 V) 2 Poles in Series, 40 °C 500 A, (200 V) 2 Poles in Series, 60 °C 400 A, (200 V) 2 Poles in Series, 70 °C 325 A, (220 V) 2 Poles in Series, 40 °C 500 A, (220 V) 2 Poles in Series, 60 °C 400 A, (220 V) 2 Poles in Series, 70 °C 325 A, (220 V) 3 Poles in Series, 40 °C 500 A, (220 V) 3 Poles in Series, 60 °C 400 A, (220 V) 3 Poles in Series, 70 °C 325 A, (260 V) 3 Poles in Series, 40 °C 500 A, (260 V) 3 Poles in Series, 60 °C 400 A, (260 V) 3 Poles in Series, 70 °C 325 A, (300 V) 3 Poles in Series, 40 °C 500 A, (300 V) 3 Poles in Series, 60 °C 400 A, (300 V) 3 Poles in Series, 70 °C 325 A, (340 V) 3 Poles in Series, 40 °C 500 A, (340 V) 3 Poles in Series, 60 °C 400 A, (340 V) 3 Poles in Series, 70 °C 325 A, (72 V) 1-Pole, 40 °C 500 A, (72 V) 1-Pole, 60 °C 400 A, (72 V) 1-Pole, 70 °C 325 A, (72 V) 2 Poles in Series, 40 °C 500 A, (72 V) 2 Poles in Series, 60 °C 400 A, (72 V) 2 Poles in Series, 70 °C 325 A, (72 V) 3 Poles in Series, 40 °C 500 A, (72 V) 3 Poles in Series, 60 °C 400 A, (72 V) 3 Poles in Series, 70 °C 325 A, (90 V) 1 Pole, 40 °C 500 A, (90 V) 1 Pole, 60 °C 400 A, (90 V) 1 Pole, 70 °C 325 A |
| Rated Operational Current DC-3 (I<sub>e</sub>) | (110 V) 2 Poles in Series, 40 °C 400 A, (110 V) 2 Poles in Series, 60 °C 400 A, (110 V) 2 Poles in Series, 70 °C 325 A, (110 V) 3 Poles in Series, 40 °C 400 A, (110 V) 3 Poles in Series, 60 °C 400 A, (110 V) 3 Poles in Series, 70 °C 325 A, (220 V) 3 Poles in Series, 40 °C 400 A, (220 V) 3 Poles in Series, 60 °C 400 A, (220 V) 3 Poles in Series, 70 °C 325 A, (72 V) 2 Poles in Series, 40 °C 400 A, (72 V) 2 Poles in Series, 60 °C 400 A, (72 V) 2 Poles in Series, 70 °C 325 A, (72 V) 3 Poles in Series, 40 °C 400 A, (72 V) 3 Poles in Series, 60 °C 400 A, (72 V) 3 Poles in Series, 70 °C 325 A |
| Rated Operational Current DC-5 (I<sub>e</sub>) | (110 V) 2 Poles in Series, 40 °C 400 A, (110 V) 2 Poles in Series, 60 °C 400 A, (110 V) 2 Poles in Series, 70 °C 325 A, (110 V) 3 Poles in Series, 40 °C 400 A, (110 V) 3 Poles in Series, 60 °C 400 A, (110 V) 3 Poles in Series, 70 °C 325 A, (220 V) 3 Poles in Series, 40 °C 400 A, (220 V) 3 Poles in Series, 60 °C 400 A, (220 V) 3 Poles in Series, 70 °C 325 A, (72 V) 2 Poles in Series, 40 °C 400 A, (72 V) 2 Poles in Series, 60 °C 400 A, (72 V) 2 Poles in Series, 70 °C 325 A, (72 V) 3 Poles in Series, 40 °C 400 A, (72 V) 3 Poles in Series, 60 °C 400 A, (72 V) 3 Poles in Series, 70 °C 325 A |
| Rated Operational Power AC-3 (P<sub>e</sub>) | (415 V) 160 kW, (440 V) 160 kW, (500 V) 200 kW, (690 V) 250 kW, (1000 V) 132 kW, (380 / 400 V) 160 kW, (220 / 230 / 240 V) 90 kW |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 500 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1409 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3050 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2440 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 996 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-3) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (U<sub>c</sub>) | 50 Hz / 60 Hz 250 ... 500 V, DC Operation 250 ... 500 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 28.9 V·A, Holding at Max. Rated Control Circuit Voltage 50 Hz 4.3 W, Holding at Max. Rated Control Circuit Voltage 60 Hz 28.9 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 4.3 W, Holding at Max. Rated Control Circuit Voltage DC 4.3 W, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 735 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 735 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 1638 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 1638 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 32 W, at Rated Operating Conditions AC-3 per Pole 12 W |
| Connecting Capacity Main Circuit | Flexible 2 x 70 ... 185 mm², Rigid Cu-Cable 2 x 70 ... 185 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Flexible 2x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Flexible 2 x 70 ... 185 mm², Rigid Cu-Cable 2 x 70 ... 185 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Tightening Torque | Cable Lug 9 N·m, Main Circuit 22 ... 43 N·m |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |