| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Rated Operational Current AC-1 (I<sub>e</sub>) | (690 V) 40 °C 200 A, (690 V) 60 °C 175 A, (690 V) 70 °C 160 A |
| Rated Operational Current AC-3 (I<sub>e</sub>) | (415 V) 55 °C 140 A, (440 V) 55 °C 140 A, (380 / 400 V) 55 °C 140 A, (220 / 230 / 240 V) 55 °C 140 A |
| Rated Operational Current DC-1 (I<sub>e</sub>) | (110 V) 2 Poles in Series, 40 °C 200 A, (110 V) 2 Poles in Series, 60 °C 175 A, (110 V) 2 Poles in Series, 70 °C 160 A, (110 V) 3 Poles in Series, 40 °C 200 A, (110 V) 3 Poles in Series, 60 °C 175 A, (110 V) 3 Poles in Series, 70 °C 160 A, (175 V) 2 Poles in Series, 40 °C 200 A, (175 V) 2 Poles in Series, 60 °C 175 A, (175 V) 2 Poles in Series, 70 °C 160 A, (220 V) 3 Poles in Series, 40 °C 200 A, (220 V) 3 Poles in Series, 60 °C 175 A, (220 V) 3 Poles in Series, 70 °C 160 A, (260 V) 3 Poles in Series, 40 °C 200 A, (260 V) 3 Poles in Series, 60 °C 175 A, (260 V) 3 Poles in Series, 70 °C 160 A, (350 V) 4 Poles in Series, 40 °C 200 A, (350 V) 4 Poles in Series, 60 °C 175 A, (350 V) 4 Poles in Series, 70 °C 160 A, (72 V) 1-Pole, 40 °C 200 A, (72 V) 1-Pole, 60 °C 175 A, (72 V) 1-Pole, 70 °C 160 A, (72 V) 2 Poles in Series, 40 °C 200 A, (72 V) 2 Poles in Series, 60 °C 175 A, (72 V) 2 Poles in Series, 70 °C 160 A, (72 V) 3 Poles in Series, 40 °C 200 A, (72 V) 3 Poles in Series, 60 °C 175 A, (72 V) 3 Poles in Series, 70 °C 160 A, (90 V) 1 Pole, 40 °C 200 A, (90 V) 1 Pole, 60 °C 175 A, (90 V) 1 Pole, 70 °C 160 A |
| Rated Operational Current DC-3 (I<sub>e</sub>) | (110 V) 2 Poles in Series, 40 °C 160 A, (110 V) 2 Poles in Series, 60 °C 160 A, (110 V) 2 Poles in Series, 70 °C 160 A, (110 V) 3 Poles in Series, 40 °C 160 A, (110 V) 3 Poles in Series, 60 °C 160 A, (110 V) 3 Poles in Series, 70 °C 160 A, (220 V) 3 Poles in Series, 40 °C 160 A, (220 V) 3 Poles in Series, 60 °C 160 A, (220 V) 3 Poles in Series, 70 °C 160 A, (72 V) 2 Poles in Series, 40 °C 160 A, (72 V) 2 Poles in Series, 60 °C 160 A, (72 V) 2 Poles in Series, 70 °C 160 A, (72 V) 3 Poles in Series, 40 °C 160 A, (72 V) 3 Poles in Series, 60 °C 160 A, (72 V) 3 Poles in Series, 70 °C 160 A |
| Rated Operational Current DC-5 (I<sub>e</sub>) | (110 V) 2 Poles in Series, 40 °C 160 A, (110 V) 2 Poles in Series, 60 °C 160 A, (110 V) 2 Poles in Series, 70 °C 160 A, (110 V) 3 Poles in Series, 40 °C 160 A, (110 V) 3 Poles in Series, 60 °C 160 A, (110 V) 3 Poles in Series, 70 °C 160 A, (220 V) 3 Poles in Series, 40 °C 160 A, (220 V) 3 Poles in Series, 60 °C 160 A, (220 V) 3 Poles in Series, 70 °C 160 A, (72 V) 2 Poles in Series, 40 °C 160 A, (72 V) 2 Poles in Series, 60 °C 160 A, (72 V) 2 Poles in Series, 70 °C 160 A, (72 V) 3 Poles in Series, 40 °C 160 A, (72 V) 3 Poles in Series, 60 °C 160 A, (72 V) 3 Poles in Series, 70 °C 160 A |
| Rated Operational Power AC-3 (P<sub>e</sub>) | (415 V) 75 kW, (440 V) 90 kW, (500 V) 90 kW, (690 V) 75 kW, (380 / 400 V) 75 kW, (220 / 230 / 240 V) 37 kW |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 674 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1460 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1168 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 477 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-3) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (U<sub>c</sub>) | 50 Hz / 60 Hz 48 ... 130 V, DC Operation 48 ... 130 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 15.9 V·A, Holding at Max. Rated Control Circuit Voltage 50 Hz 2.5 W, Holding at Max. Rated Control Circuit Voltage 60 Hz 15.9 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 2.5 W, Holding at Max. Rated Control Circuit Voltage DC 2.5 W, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 347 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 347 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 473 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 473 W |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 6 W, at Rated Operating Conditions AC-3 per Pole 3 W |
| Connecting Capacity Main Circuit | Flexible 2 x 10 ... 70 mm², Rigid Cu-Cable 2 x 10 ... 95 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm², Flexible 2x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Flexible 2 x 10 ... 70 mm², Rigid Cu-Cable 2 x 10 ... 95 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Tightening Torque | Cable Lug 9 N·m |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |