| Availability | Confirmed on request |
| Category | ABB AX Contactors |
| Lifecycle | Active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Weight | 0.326 kg |
| UPC / EAN | 3471522410887 |
Shipping & availability
When can 1SBL891074R8801 be shipped?
1SBL891074R8801 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 1SBL891074R8801 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 1SBL891074R8801 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 1SBL891074R8801, subject to availability and destination.
AX06 contactor relays are used for switching auxiliary and control circuits.
Specifications
General
| Order code (ABB product ID) | 1SBL891074R8801 |
| Type | AX06-30-01-88 |
| Lifecycle | Active (current ABB product) |
Ordering
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
Dimensions
| Product Net Width | 44 mm |
| Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm |
| Product Net Weight | 0.326 kg |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Auxiliary Circuit 690 V, Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz, Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (I<sub>th</sub>) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 22 A, acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-1 (I<sub>e</sub>) | (220 / 240 V) 55 °C 20 A, (690 V) 40 °C 20 A, (690 V) 70 °C 16 A |
| Rated Operational Current AC-3 (I<sub>e</sub>) | (415 V) 55 °C 7 A, (440 V) 55 °C 7 A, (500 V) 55 °C 7 A, (690 V) 55 °C 5 A, (380 / 400 V) 55 °C 7 A, (220 / 230 / 240 V) 55 °C 7 A |
| Rated Operational Current AC-15 (I<sub>e</sub>) | (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (380 / 400 V) 3 A, (400 / 440 V) 2 A |
| Rated Operational Current DC-13 (I<sub>e</sub>) | (24 V) 6 A / 144 W, (110 V) 0.55 A / 60 W, (125 V) 1.1 A / 138 W, (220 V) 0.55 A / 121 W, (250 V) 0.55 A / 138 W, (400 V) 2.8 A / 134 W, (500 V) 2 A / 144 W |
| Rated Operational Power AC-3 (P<sub>e</sub>) | (415 V) 3 kW, (440 V) 3 kW, (500 V) 3.5 kW, (690 V) 4 kW, (380 / 400 V) 3 kW, (220 / 230 / 240 V) 1.5 kW |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 100 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 50 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 250 A, at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 60 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour, (AC-15) 1200 cycles per hour, (AC-3) 1200 cycles per hour, (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (U<sub>c</sub>) | 50 Hz 230 ... 240 V, 60 Hz 240 ... 260 V |
| Coil Consumption | Average Holding Value 50 / 60 Hz 8 V·A, Average Holding Value 50 Hz 8 V·A, Average Holding Value 60 Hz 8 V·A, Average Holding Value, from Warm State 2 W, Average Pull-in Value 50 Hz 70 V·A, Average Pull-in Value 60 Hz 80 V·A |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.8 W, at Rated Operating Conditions AC-3 per Pole 0.1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 16 ms, Between Coil De-energization and NO Contact Opening 4 ... 11 ms, Between Coil Energization and NC Contact Opening 7 ... 21 ms, Between Coil Energization and NO Contact Closing 10 ... 26 ms |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Tightening Torque | Auxiliary Circuit 1 N·m, Control Circuit 1 N·m, Main Circuit 1 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
Technical UL/CSA
| General Use Rating UL/CSA | (600 V AC) 20 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1/3 hp, (200 ... 208 V AC) Three Phase 1.5 hp, (220 ... 240 V AC) Three Phase 2, (240 V AC) Single Phase 3/4 hp, (440 ... 480 V AC) Three Phase 3 hp, (550 ... 600 V AC) Three Phase 5 hp |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb, Control Circuit 9 in·lb, Main Circuit 9 in·lb |
| Full Load Amps Motor Use | (120 V AC) Single Phase 7.2 A, (200 ... 208 V AC) Three Phase 6.9 A, (220 ... 240 V AC) Three Phase 6.8 A, (240 V AC) Single Phase 6.9 A, (440 ... 480 V AC) Three Phase 4.8 A, (550 ... 600 V AC) Three Phase 6.1 A |
Environmental
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C, Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
Material Compliance
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
External Classifications and Standards
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
Downloads & documentation
Official documents from ABB, downloaded directly from the manufacturer.
Data sheets & manuals
| Data Sheet, Technical Information (1SBC100187L0203) | |
| Instructions and Manuals (9AKK107492A7057) |
CAD & dimension drawings
| CAD Dimensional Drawing (2CDC001079B0201) |
Certificates (8)
More ABB parts
Available on requestAX06-30-01-85 380-400V50Hz 400-415V60Hz Contactor
Available on requestAX06-30-10-85 380-400V50Hz 400-415V60Hz Contactor
Available on requestAX06-30-01-86 400-415V50Hz 415-440V60Hz Contactor
Available on requestAX06-30-10-86 400-415V50Hz 415-440V60Hz Contactor
Available on requestAX06-30-10-88 230-240V50Hz 240-260V60Hz Contactor
Available on requestA2X06-30-01 110V50HZ/60HZ Contactor with 40Pcs
Available on requestA2X06-30-10 110V50HZ/60HZ Contactor with 40Pcs
Available on requestA2X06-30-01 220V50HZ/230V60HZ Contactor with 40Pcs