ABB 1SBH901074R8040 – NX40E-80 220-230V50Hz/230-240V60Hz Contactor relay
Request a Quote
Quick facts
| Availability | Confirmed on request |
| Category | ABB NX Contactor Relays |
| Lifecycle | Active |
| Warranty | 12-month (new) · 3-month (used/refurbished) |
| Weight | 0.315 kg |
| Country of origin | India |
| UPC / EAN | 3471522390806 |
Shipping & availability
When can 1SBH901074R8040 be shipped?
1SBH901074R8040 is sourced on request — request a quote and we'll confirm the exact availability and shipping timeline for this specific unit.
Can I pick up 1SBH901074R8040 in person?
Local pickup from our Groningen, Netherlands warehouse may be possible — contact us before ordering to check availability and arrange a collection time.
Is express delivery available?
Yes — mention it when you request a quote for 1SBH901074R8040 and we'll include express shipping options in our reply.
My factory is down and I need this urgently — can you help?
For a critical breakdown, contact us directly at +31 (0)50-7110348 or sales@partnerplc.com — we can look into same-day courier or dedicated taxi/hotshot delivery for 1SBH901074R8040, subject to availability and destination.
NX...contactor relays are used for switching auxiliary circuits and control circuits. These contactor relays are of the block type design with: – 4 poles. Contactor relays have mechanically linked auxiliary contact elements – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.
Specifications
General
| Order code (ABB product ID) | 1SBH901074R8040 |
| Type | NX40E-80 |
| Lifecycle | Active (current ABB product) |
| Country of origin | India |
Ordering
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
Dimensions
| Product Net Width | 44 mm |
| Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm |
| Product Net Weight | 0.315 kg |
Technical
| Number of Auxiliary Contacts NO | 4 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Auxiliary Circuit 690 V, Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz, Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (I<sub>th</sub>) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (I<sub>e</sub>) | (500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (380 / 400 V) 3 A, (400 / 440 V) 2 A |
| Rated Operational Current DC-13 (I<sub>e</sub>) | (24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.30 A / 66 W, (250 V) 0.30 A / 75 W |
| Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>) | for 0.1 s 140 A, for 1 s 100 A |
| Rated Insulation Voltage (U<sub>i</sub>) | acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour, (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (U<sub>c</sub>) | 50 Hz 220 ... 230 V, 60 Hz 230 ... 240 V |
| Coil Consumption | 2 W |
| Power Loss | at 6 A per Pole 0.1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 16 ms, Between Coil De-energization and NO Contact Opening 4 ... 11 ms, Between Coil Energization and NC Contact Opening 7 ... 21 ms, Between Coil Energization and NO Contact Closing 10 ... 26 ms |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Tightening Torque | Auxiliary Circuit 1 N·m, Control Circuit 1 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
Technical UL/CSA
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb, Control Circuit 9 in·lb |
Environmental
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C, Close to Contactor without Thermal O/L Relay -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C, Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
Material Compliance
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 4119d4e7-ea06-4a8b-925c-6ec9ed3c00b2 Bulgaria |
| Simplified SCIP | 00616fed-9ea5-4b62-a890-6199a254f2f1 Sweden, 02a311fd-3227-4aae-8638-62c82edcb09d Germany, 10fdee06-0b9f-4421-a9dc-1843bbce216d Sweden, 22480de5-c312-43e6-a922-bfbe3f563417 Netherlands, 33a68082-9b1f-46dc-9826-809609b98cbe Italy, 425e30cd-8997-44d7-835d-4667fcbbe753 Hungary, 442fff88-0fed-4629-b311-c3eacc1a17fd Germany, 46191db3-e047-49e5-99b2-ed58d21cac34 Germany, 53463052-416f-40df-8dce-8633d5a2068f Germany, 5527f775-24c4-44d2-8871-e3026e8ac14f Croatia, 56d82315-e263-4def-b1c5-dc75a8d57f88 Poland, 5f5da01c-8cdb-4836-a647-64c639197c45 Belgium, 628858bd-089d-49d7-93ca-4af1945d56e7 France, 6d57a814-ba67-446f-a993-fc29c31cfb47 Finland, 6f5963e2-7d28-4aa6-b283-d4986cbb79d0 Hungary, 862b37f0-354e-4420-b80e-8b6f7dc20780 Germany, 8ec37bd1-2ede-49b6-9738-befcff41ee71 Belgium, 97a5e425-4d8e-4918-98d7-b047b28f9b21 Denmark, a0aff0ab-b469-46d3-b22d-7bc444a1385c Czechia, a290f7d1-e23e-468a-9804-dd483fe9d168 Spain, b4002da7-1b15-41f9-8a61-42ff924eb0ac France, cc346738-0011-4ae7-954a-30022681888c Greece, cd9b4a53-d1e5-4eed-aa0e-f5e57254cd85 Portugal, d0417464-4867-4e8c-91bd-f7f4db2a1f4c Poland, d2784906-ca13-4785-a867-ec2043c13024 Poland, e243f09a-b451-435f-98c6-e5cd338a1c40 Estonia, ef62bdf8-6b04-4d5e-a2d6-296b4af01c47 Norway |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
External Classifications and Standards
| Object Classification Code | K |
| ETIM 7 | EC000196 - Contactor relay |
| ETIM 8 | EC000196 - Contactor relay |
| ETIM 9 | EC000196 - Contactor relay |
| eClass | V11.0 : 27371001 |
| UNSPSC | 39121500 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
| E-Number (Finland) | 3707386 |
Downloads & documentation
Official documents from ABB, downloaded directly from the manufacturer.
Data sheets & manuals
| Data Sheet, Technical Information (1SBC100187L0203) |
CAD & dimension drawings
| CAD Dimensional Drawing (2CDC001079B0201) |
Certificates (9)
More ABB parts
Available on requestNX31E-75 200V50HZ/200-220V60HZ Contactor relay
Available on requestNX40E-75 200V50HZ/200-220V60HZ Contactor relay
Available on requestNX22E-80 220-230V50Hz/230-240V60Hz Contactor relay
Available on requestNX31E-80 220-230V50Hz/230-240V60Hz Contactor relay
Available on requestNX22E-81 24V 50/60Hz Contactor relay
Available on requestNX31E-81 24V 50/60Hz Contactor relay
Available on requestNX40E-81 24V 50/60Hz Contactor relay
Available on requestNX22E-83 48V 50/60Hz Contactor relay