产品概览
| 库存情况 | 需按需确认 |
| 分类 | Two switching outputs |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
PP7554 何时可以发货?
PP7554 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 PP7554 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 PP7554 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 PP7554 安排当日快递或专车加急配送。
Robust design for use in harsh industrial environments Two switching outputs, one of which can be configured as diagnostic output High shock and vibration resistance Lifespan of more than 100 million pressure cycles User-friendly communication and parameterisation via IO-Link
技术规格
Product characteristics
| Number of inputs and outputs | Number of digital outputs: 2 |
| Measuring range | -1...10 bar; -14.5...145 psi; -100...1000 kPa; -0.1...1 MPa |
| -1...10 bar | -14.5...145 psi |
| Process connection | threaded connection G 1/4 external thread internal thread:M5 |
Application
| Application | for industrial applications |
| Media | liquids and gases |
| Medium temperature[°C] [°C] | -25...90 |
| Min. burst pressure | 150 bar; 2175 psi; 15 MPa |
| 150 bar | 2175 psi |
| Pressure rating | 75 bar; 1087 psi; 7.5 MPa |
| 75 bar | 1087 psi |
| Type of pressure | relative pressure; vacuum |
Electrical data
| Operating voltage[V] [V] | 9.6...36 DC; (communication mode: 18...32) |
| Current consumption[mA] [mA] | < 45 |
| Min. insulation resistance[MΩ] [MΩ] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time[s] [s] | 0.3 |
Inputs / outputs
| Number of inputs and outputs | Number of digital outputs: 2 |
Outputs
| Total number of outputs | 2 |
| Output signal | switching signal; IO-Link; (configurable) |
| Electrical design | PNP |
| Number of digital outputs | 2 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC[V] [V] | 2 |
| Permanent current rating of switching output DC[mA] [mA] | 250 |
| Switching frequency DC[Hz] [Hz] | 170 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
Measuring/setting range
| Measuring range | -1...10 bar; -14.5...145 psi; -100...1000 kPa; -0.1...1 MPa |
| -1...10 bar | -14.5...145 psi |
| Set point SP | -0.9...10 bar; -13...145 psi; -0.09...1 MPa |
| -0.9...10 bar | -13...145 psi |
| Reset point rP | -0.95...9.95 bar; -14...144 psi; -0.095...0.995 MPa |
| -0.95...9.95 bar | -14...144 psi |
| In steps of | 0.05 bar; 1 psi; 0.005 MPa |
| 0.05 bar | 1 psi |
| Factory setting | SP1 = 2.50 bar; rP1 = 2.30 bar; SP2 = 7.50 bar; rP2 = 7.30 bar; OUT1 = Hno; OUT2 = Hno |
Accuracy / deviations
| Switch point accuracy[% of the span] [% of the span] | < ± 0,5 |
| Repeatability[% of the span] [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation[% of the span] [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Zero-point stabilisation[% of the span] [% of the span] | IO-Link; 1,0; (see operating instructions zero-point behaviour) |
| switching output | 1,0 |
| IO-Link | 1,0; (see operating instructions zero-point behaviour) |
| Hysteresis deviation[% of the span] [% of the span] | < ± 0,1 |
| Long-term stability[% of the span] [% of the span] | < ± 0,1; (per year) |
| Temperature coefficient zero point[% of the span / 10 K] [% of the span / 10 K] | < ± 0,2; (0...80 °C) |
| Temperature coefficient span[% of the span / 10 K] [% of the span / 10 K] | < ± 0,2; (0...80 °C) |
Response times
| Response time[ms] [ms] | < 3 |
| Damping process value dAP in steps[s] [s] | 0,003 - 0,006 - 0,010 - 0,017 - 0,060 - 0,125 - 0,250 - 0,500 |
Interfaces
| Communication interface | IO-Link |
| Transmission type | COM2 (38,4 kBaud) |
| IO-Link revision | 1.0 |
| SIO mode | yes |
| Required master port type | A |
| Process data analogue | 1 |
| Process data binary | 2 |
| Min. process cycle time[ms] [ms] | 2.3 |
| Supported DeviceIDs | default; 6 |
| default | 6 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...85 |
| Storage temperature[°C] [°C] | -40...100 |
| Protection | IP 68; (7 days / 1 m water depth / 0.1 bar) |
Tests / approvals
| EMC | immunity; EN 61000-6-2; EN 61000-4-2 ESD; 4 kV contact discharge / 15 kV air discharge; EN 61000-4-3 HF radiated; 20 V/m; EN 61000-4-4 Burst; 4 kV coupling clamp; EN 61000-4-5 Surge; 0,5 kV supply / 1 kV signal for DC units; EN 61000-4-6 HF conducted; 10 V; immunity; according to the automotive directive 1995/54/EC / 04/104EG / 05/83/EG; absorber chamber test to ISO 11452-2:; 80 V/m |
| immunity | according to the automotive directive 1995/54/EC / 04/104EG / 05/83/EG |
| EN 61000-4-2 ESD | 4 kV contact discharge / 15 kV air discharge |
| EN 61000-4-3 HF radiated | 20 V/m |
| EN 61000-4-4 Burst | 4 kV coupling clamp |
| EN 61000-4-5 Surge | 0,5 kV supply / 1 kV signal for DC units |
| EN 61000-4-6 HF conducted | 10 V |
| absorber chamber test to ISO 11452-2: | 80 V/m |
| Shock resistance | DIN IEC 60068-2-27 / DIN IEC 60068-2-29; 1000 g; DIN EN 61373; category 3 |
| DIN IEC 60068-2-27 / DIN IEC 60068-2-29 | 1000 g |
| DIN EN 61373 | category 2 |
| Vibration resistance | DIN IEC 68-2-6; 20 g (10...2000 Hz); DIN EN 60068-2-64; 14 g; DIN EN 61373; category 2 |
| DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
| DIN EN 60068-2-64 | 14 g |
| MTTF[years] [years] | 310 |
| Pressure Equipment Directive | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Railway applications | DIN EN 50155; Klasse T3, C1, S1 |
| DIN EN 50155 | Klasse T3, C1, S1 |
Mechanical data
| Weight[g] [g] | 226 |
| Housing | cylindrical |
| Dimensions[mm] [mm] | Ø 30 / L = 79.5 |
| Materials | stainless steel (304/1.4301); FKM; EPDM/X; PA |
| Materials (wetted parts) | stainless steel (303/1.4305); ceramics; FKM |
| Min. pressure cycles | 100 million |
| Process connection | threaded connection G 1/4 external thread internal thread:M5 |
| Restrictor element integrated | no (can be retrofitted) |
Displays / operating elements
| Display | operation; 2 x LED, green; switching status; 2 x LED, yellow |
| operation | 2 x LED, green |
| switching status | 2 x LED, yellow |
| Teach function | yes |
Remarks
| Remarks | with reference to UL: "limited voltage" with overcurrent protection in accordance with UL508 |
| Pack quantity | 1 pcs. |
Electrical connection
| Connector | 1 x M12; coding: A |
12个月保修适用于所有全新库存
3个月保修适用于二手及翻新零部件
30天退货未使用零部件退货免收上架费
全球发货全球快速可追踪配送