产品概览
| 库存情况 | 需按需确认 |
| 分类 | Digital output modules |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
| 重量 | 180 kg |
发货与库存
X67DO1332 何时可以发货?
X67DO1332 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X67DO1332 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X67DO1332 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X67DO1332 安排当日快递或专车加急配送。
8 A summation current per moduleAll outputs with single-channel diagnostics for short circuit or overloadExtremely short cycle timesOutputs with short circuit protectionIntegrated protection for switching inductances The module is a digital output module for 24 VDC. It is equipped with 8 outputs for a source output circuit.
技术规格
Specifications
| I/O module | 8 digital outputs 24 VDC |
| B&R ID code | 0x1467 |
| Status indicators | I/O function per channel, supply voltage, bus function |
| Outputs | 8x M8, 3-pin |
| I/O power supply | M8, 4-pin |
| X2X Link | M12, B-coded |
| Internal I/O | 2 W |
| X2X Link power supply | 0.75 W |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA IIA T5 Gc IP67, Ta = 0 - Max. 60°C TÜV 05 ATEX 7201X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC | Yes |
| Nominal voltage | 24 VDC |
| Voltage range | 18 to 30 VDC |
| Integrated protective function | Reverse polarity protection |
| Actuator power supply | 0.5 A summation current |
| Quantity | 8 |
| Variant | Current-sourcing FET |
| Switching voltage | I/O power supply minus residual voltage |
| Nominal output current | 2 A |
| Total nominal current | 8 A |
| Output circuit | Source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply |
| Diagnostic status | Output monitoring with 10 ms delay |
| Leakage current when the output is switched off | 5 µA |
| Switching on after overload shutdown | Approx. 10 ms (depends on the module temperature) |
| Group 1 | Channels 1 to 4 |
| Group 2 | Channels 5 to 8 |
| Residual voltage | <0.5 V at 2 A nominal current |
| Peak short-circuit current | <21 A |
| 0 → 1 | <250 µs |
| 1 → 0 | <270 µs |
| Resistive load | Max. 100 Hz |
| Braking voltage when switching off inductive loads | 50 VDC |
| Output | Max. 2 A |
| Group | Max. 4 A (simultaneity factor = 50%) |
| Module | Max. 8 A |
| Voltage | I/O power supply minus voltage drop for short-circuit protection |
| Voltage drop for short-circuit protection at 500 mA | Max. 2 VDC |
| Summation current | Max. 0.5 A |
| Short-circuit proof | Yes |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Any | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP67 |
| Operation | -25 to 60°C |
| Derating | See section "Derating". |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Width | 53 mm |
| Height | 85 mm |
| Depth | 42 mm |
| Weight | 180 g |
| M8 | Max. 0.4 Nm |
| M12 | Max. 0.6 Nm |
12个月保修适用于所有全新库存
3个月保修适用于二手及翻新零部件
30天退货未使用零部件退货免收上架费
全球发货全球快速可追踪配送