产品概览
| 库存情况 | 需按需确认 |
| 分类 | Digital output modules |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
X20SO6530 何时可以发货?
X20SO6530 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X20SO6530 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X20SO6530 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X20SO6530 安排当日快递或专车加急配送。
6 safe relay outputsOutput type "Relay"Relay module for 230 VAC / 24 VDCSwitching current 6 ANormally open contactSingle-channel isolated outputs This module is equipped with 6 safe relay outputs.The module can be used for controlling floating actuators in safety-related applications up to PL e or SIL 3.Safety relays are installed in the module. The positively driven feedback contacts are evaluated internally by the module. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
技术规格
Specifications
| I/O module | 6 relays with 1 normally open contact each, 230 VAC / 2 A (6 A), 24 VDC / 6 A |
| B&R ID code | 0xF22A |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator and software |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 1 ms |
| Bus | 0.26 W |
| Internal I/O | 1.65 W |
| Additional power dissipation caused by actuators (resistive) [W] | 4.32 |
| Channel - Bus | Yes |
| Channel - Channel | Yes |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| Functional safety | IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment cULus E537419 Engine generator controller |
| EN 50155 | No |
| EN 61810-3 | Yes |
| Note | Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
| Nominal voltage | 24 VDC |
| Voltage range | 24 VDC -15% / +20% |
| Integrated protective function | Reverse polarity protection |
| Quantity | 6 |
| Variant | Relay / Normally open contact, internal high-side and low-side control |
| Nominal output current | 5 mA to 6 A (hardware revision <B5: 2 A) |
| Diagnostic status | Contact position determined by positively driven contacts |
| Max. switching frequency | See section "Inrush current behavior for output channels". |
| 0 → 1 | <50 ms |
| 1 → 0 | <50 ms Hardware upgrade 2.2.0.0 or later: <20 ms |
| Insulation voltage between channel and bus | Safe disconnection of 300 VAC per EN 50178 |
| Insulation voltage between channel and channel | Tested at 1350 VAC |
| Contact resistance (without terminal block) | 20 mΩ |
| Contact service life | See "Contact service life". |
| Short-circuit/Overload protection | External 6 A gL/gG fuse (melting fuse), LS automat C characteristic 1.6 A |
| Switching voltage range | 5 to 24 VDC, 5 to 230 VAC |
| Coil voltage | 24 VDC -15% / +20% |
| Short-circuit proof | Yes, 1000 A (with specified short-circuit/overload protection) |
| Max. inrush current | AC: 50 A for 100 ms, DC: 10 A for 200 ms |
| Overvoltage category per EN 60664-1 | II |
| UL 508 | B300 / R300 |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 50°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Pitch | 25+0.2 mm |