4-channel vibration measurement and analysis module24-bit resolution at 51.562 kHzIEPE supplyInternal calculation of an extensive range of condition parametersData buffer upload This compact module provides a system for measuring and analyzing vibrations for use in applications such as condition monitoring for machinery and equipment. The measurement unit consists of 4 vibration inputs with 24-bit converter resolution and a sampling frequency of 51.562 kHz. Each of the inputs has a separately activated constant current source to supply IEPE sensors. Signal conditioning algorithms integrated in the module include configurable high and low-pass filters, an envelope curve generator and a Fourier transform, among many others. Various characteristic values and configurable frequency bands are available to ensure seamless signal evaluation. The module-internal calculation minimizes the load on the bus and PLC. Whether used for traditional condition monitoring or as a means of process optimization, the maximum evaluable frequency of 10 kHz and maximum frequency resolution of under 63 mHz make it suitable for almost any application. If desired, it can also be used as a standard input module. The ability to upload all values in the time and frequency domain also allow measurements to be evaluated externally or archived.
技术规格
Specifications
| I/O module | X20 4-channel analog input module for vibration measurement and analysis of condition monitoring tasks |
| Insulation voltage between channel and bus | 500 Veff |
| Nominal voltage | 24 VDC ±20% |
| B&R ID code | 0xC8F9 |
| Status indicators | Run, error, vibration inputs 1 to 4 |
| Module run/error | Yes, using LED status indicator and software |
| Bus | 0.01 W |
| Internal I/O | 2.5 W |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Quantity | 4 |
| Input type | IEPE sensor: Acceleration |
| Digital converter resolution | 24-bit |
| Per channel | Yes |
| At minimum supply voltage | Starting at 17 V (or greater) for more than 1 ms |
| At nominal supply voltage | Starting at 21.3 V (or greater) for more than 1 ms |
| At maximum supply voltage | Starting at 25.5 V (or greater) for more than 1 ms |
| Permissible input signal | ±10 VAC |
| Conversion procedure | Sigma-delta |
| Type | Vibration input |
| Sampling frequency | 51.5625 kHz |
| Input high pass cutoff frequency | 34 mHz |
| Input low pass cutoff frequency | 19.75 kHz |
| Downsampling | 200 Hz, 500 Hz, 1 kHz, 2 kHz, 5 kHz, 10 kHz (configurable) |
| Frequency resolution of spectra | 0.0629 Hz, 0.1574 Hz, 0.3147 Hz, 0.6294 Hz, 1.5736 Hz, 3.1471 Hz |
| Sensor power supply | IEPE, 5 mA constant current source (4.9 - 5.5 mA), can be switched off for each channel |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 50°C |
| Vertical mounting orientation | -25 to 45°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM31 separately. |
| Pitch | 25+0.2 mm |