产品概览
| 库存情况 | 需按需确认 |
| 分类 | Power supply modules |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
X20SP1130 何时可以发货?
X20SP1130 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X20SP1130 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X20SP1130 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X20SP1130 安排当日快递或专车加急配送。
24 VDC power supply module for internal I/O power supplySafe cutoff of potential groups with standard outputsSafely switched potential can also be tapped externally1 safe digital output with 10 ASource circuitOutput type BIntegrated output protection This module is equipped with 1 safe digital output. The nominal output current is 10 A. The power supply module is used for the internal I/O power supply.A safe digital output channel is integrated in the module for cutting off the I/O power supply of connected X20 modules in safety-related applications up to PL e or SIL 3.The output is designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles.The "High-side-High-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case.In addition, the instructions for switching off X20 potential groups must be observed.The safe digital output channel provides protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
技术规格
Specifications
| I/O module | 1 safe type B1 digital output, 24 VDC, 10 A, without OSSD, note list of permitted modules in the potential group |
| B&R ID code | 0x1DBF |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator and software |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 800 µs |
| Bus | 0.2 W |
| Internal I/O | 1.5 W |
| Additional power dissipation caused by actuators (resistive) [W] | 3 |
| Channel - Bus | Yes |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| Functional safety | EN 50156-1:2004 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC | Yes |
| Note | Order 1x safety-keyed terminal block separately.Order 1x safety-keyed bus module separately. |
| Input voltage | 24 VDC -15% / +20% |
| Fuse | Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection | No |
| Quantity | 1 |
| Variant | FET, 2x positive switching, type B1, output level readable |
| Nominal voltage | 24 VDC |
| Nominal output current | 10 A |
| Output protection | See section "Inrush current behavior for output channels". |
| Braking voltage when switching off inductive loads | 1 VDC |
| Diagnostic status | Output monitoring, current measurement (shutdown in the event of overcurrent) |
| Error detection time | 2 s |
| Insulation voltage between channel and bus | 500 Veff |
| Peak short-circuit current | See section "Inrush current behavior for output channels". |
| Leakage current when the output is switched off | 1 mA |
| RDS(on) | 30 mΩ |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency | 5 times per minute with max. 2 HzHardware upgrade 2.2.0.0 and later: 120 times per minute with max. 2 HzSee section "Inrush current behavior for output channels" and table "Switching inductive loads". |
| Test pulse length | Without test pulse |
| Max. capacitive load | 1 mF |
| Minimum load | 15 mA |
| IOUT | <1 mA |
| IGND | <50 mA |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 35°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Pitch | 25+0.2 mm |