产品概览
| 库存情况 | 需按需确认 |
| 分类 | Digital mixed modules |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
X20SC2212 何时可以发货?
X20SC2212 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X20SC2212 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X20SC2212 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X20SC2212 安排当日快递或专车加急配送。
6 safe digital inputs, sink circuit6 pulse outputsSoftware input filter configurable for each channel2 safe digital outputs, output type B with 0.5 A, source circuitIntegrated output protection The module is equipped with 6 safe digital inputs and 2 safe digital outputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read in digital signals and to control actuators in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "high-side high-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
技术规格
Specifications
| I/O module | 6 safe type A digital inputs, 6 pulse outputs, 24 VDC, 2 safe type B1 digital outputs, 24 VDC, 0.5 A, OSSD <500 µs |
| B&R ID code | 0xBDA5 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 1 ms |
| Bus | 0.25 W |
| Internal I/O | 1.4 W |
| Safe digital outputs | 0.075 |
| Pulse outputs | 0.264 |
| Channel - Bus | Yes |
| Channel - Channel | No |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| Functional safety | EN 50156-1:2004 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck |
| KC | Yes |
| Note | Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
| Nominal voltage | 24 VDC |
| Voltage range | 24 VDC -15% / +20% |
| Integrated protective function | Reverse polarity protection |
| Quantity | 6 |
| Variant | Push-Pull |
| Input characteristics per EN 61131-2 | Type 1 |
| Hardware | ≤150 μs |
| Software | Configurable between 0 and 500 ms |
| Input circuit | Sink |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Min. 2 mA to max. 3.28 mA |
| Input resistance | Min. 7.33 kΩ |
| Error detection time | 1 s |
| Insulation voltage between channel and bus | 500 Veff |
| Low | <5 VDC |
| High | >15 VDC |
| Line length between signal source (pulse output or external signal) and input | Max. 60 m with unshielded line Max. 400 m with shielded line |
| Nominal output current | 20 mA |
| Total nominal current | 120 mA |
| Output protection | Shutdown of individual channels in the event of overload or short circuit |
| Braking voltage when switching off inductive loads | Max. 45 VDC |
| Peak short-circuit current | 25 A for 15 µs |
| Leakage current when the output is switched off | 0.1 mA |
| RDS(on) | 110 Ω |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency | See section "Inrush current behavior for output channels". |
| Test pulse length | Max. 500 µs |
| Max. capacitive load | 100 nF |
| IOUT | <1 mA |
| IGND | <180 mA |
| Short-circuit current | 100 mAeff |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 50°C |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Pitch | 25+0.2 mm |