reACTION technology module4 high-speed digital inputs4 high-speed digital channels, configurable as inputs or outputs1 ABR incremental encoder input 24 VPulse width modulation24 VDC and GND for encoder supplySupports blackout mode This reACTION technology module has four high-speed digital inputs and four high-speed digital mixed channels. All connections are designed for 1-wire connections. All inputs are designed for sink connections, the outputs for push-pull connections.Ultrafast reACTION Technology makes it possible to control the integrated I/O channels with response times down to 1 μs. All of the commands that can be used for reACTION programs are provided as function blocks in special libraries (e.g. AsIORTI). Programming in compliance with IEC 61131-3 requirements takes place in the Function Block Diagram editor in Automation Studio.The module supports blackout mode. In blackout mode, programmable module functionality persists even if the network fails.
技术规格
Specifications
| I/O module | 4 digital input channels, 4 digital channels configurable as inputs or outputs, reACTION Technology |
| B&R ID code | 0xE559 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator and software (output error status) |
| reACTION-capable I/O channels | Yes |
| Scope | Module |
| Function | Programmable |
| Standalone mode | No |
| Bus | 0.01 W |
| Internal I/O | 1 W |
| Additional power dissipation caused by actuators (resistive) [W] | +0.6 |
| Type of signal lines | Shielded cables must be used for all signal lines, cable length: Max. 20 m |
| Type | 64 Mbit flash memory |
| Data retention | 20 years at 55°C |
| Guaranteed erase/write cycles | 100,000 |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| Output voltage | 24 VDC -15% / +20% |
| Output current | Module-internal, max. 600 mA |
| Short-circuit proof, overload protection | Yes |
| Quantity | 4 mixed channels, configuration as input or output using software |
| Nominal voltage | 24 VDC |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Typ. 1.3 mA |
| Input circuit | Sink |
| Hardware | <3 µs |
| Software | Default 200 ns, configurable between 200 ns and 5 ms in 10 ns intervals |
| Connection type | 1-wire connections |
| Input resistance | 18.16 kΩ |
| Low | <5 VDC |
| High | >15 VDC |
| Insulation voltage between channel and bus | 500 Veff (Rev. <E0); 856 VAC (Rev. ≥E0) |
| Encoder inputs | 24 V, asymmetrical |
| Counter size | 32-bit |
| Input frequency | Max. 333 kHz |
| Evaluation | 4x |
| Variant | Push-Pull |
| Switching voltage | 24 VDC -15% / +20% |
| Nominal output current | 100 mA (Rev. <E0) Configurable: 100/530 mA (Rev. ≥E0) |
| Total nominal current | 400 mA (Rev. <E0); 2.12 A (Rev. ≥E0) |
| Output circuit | Sink or source |
| Output protection | Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current") |
| Diagnostic status | Output monitoring with delay <700 ns |
| Leakage current when the output is switched off | Approx. 25 µA |
| RDS(on) | 140 mΩ |
| Residual voltage | <0.4 V at nominal current |
| Max. continuous current | 100 mA (Rev. <E0); 530 mA (Rev. ≥E0) |
| Peak short-circuit current | <10 A |
| Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 3 ms |
| 0 → 1 | <1 µs |
| 1 → 0 | <1 µs |
| Resistive load | 100 mA: Max. 500 kHz 530 mA: Max. 20 Hz (Rev. ≥E0) |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section "Derating and hardware configuration". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2 mm |