Supply for Compact or Fieldbus CPU, X2X Link network and internal I/O power supplyCost-effective power supply module for small X20 systemsNo electrical isolation of supply and CPU / X2X Link power supplyExpansion or redundancy of CPU / X2X Link power supply not possible by operating multiple power supply modules simultaneouslyRS232 configurable as an online interfaceCAN bus The power supply module is used together with an X20 Compact or Fieldbus CPU. It is equipped with a supply for the Compact or Fieldbus CPU, X2X Link network and internal I/O power supply. This module is intended as a cost-effective power supply module for small X20 systems. The use of potential groups is possible. Expansion or redundancy of the X2X Link network with power supply module X20PS3300 or X20PS3310 is not possible. Expanding the X20 system with a bus transmitter is also not permitted.
技术规格
Specifications
| Power supply module | 24 VDC power supply module for Compact or Fieldbus CPU, X2X Link power supply and I/O |
| Interfaces | 1x RS232, 1x CAN bus |
| B&R ID code | 0xA38A |
| Status indicators | Operating state, module status, RS232, CAN bus |
| Module run/error | Yes, using LED status indicator and software |
| CAN bus data transfer | Yes, using LED status indicator |
| RS232 data transfer | Yes, using LED status indicator |
| Overload | Yes, using LED status indicator and software |
| Power consumption for X2X Link power supply | 1.64 W |
| Internal I/O | 0.6 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| KC | Yes |
| Input voltage | 24 VDC -15% / +20% |
| Input current | Max. 0.7 A |
| Fuse | Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection | No |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Parallel connection | No |
| Redundant operation | No |
| Overload characteristics | Short-circuit proof, temporary overload |
| Nominal output voltage | 24 VDC |
| Behavior on short circuit | Required line fuse |
| Permissible contact load | 10 A |
| Signal | CAN bus |
| Variant | Connection via 12-pin terminal block X20TB12 |
| Transfer rate | Max. 1 Mbit/s |
| Electrical isolation | CPU/X2X Link supply not isolated from CPU/X2X Link power supply, and I/O supply not isolated from I/O power supply |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Derating | See section "Derating". |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x Compact CPU base X20BB22 or X20BB27 separately Order 1x Fieldbus CPU base X20BB32 or X20BB37 separately |
| Pitch | 12.5+0.2 mm |