2 safe analog input pairs for current measurement 0.5 to 25 mA24-bit digital converter resolutionChannels individually galvanically isolatedSensor power supplies galvanically isolatedInput filter configurable The module is equipped with 2 safe analog input pairs for current measurement. Each input pair has its own sensor power supply. The channels with their respective sensor supplies are electrically isolated from each other. It can be used to capture current signals in the range from 0.5 to 25 mA.The safe analog input module is suitable for safely acquiring current signals for safety-related applications up to PL e or SIL 3.This module is designed for X20 16-pin terminal blocks.
技术规格
Specifications
| I/O module | 2x 2 safe type A analog inputs, 0.5 to 25 mA, channels individually galvanically isolated |
| B&R ID code | 0xDD9F |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 2 ms |
| Bus | 0.25 W |
| Internal I/O | 1.7 W |
| Additional power dissipation caused by actuators (resistive) [W] | 0.36 |
| Channel - Bus | 500 VDC |
| Channel - Channel | Yes |
| Channel pair - Channel pair | 500 VDC |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| Functional safety | EN 50156-1:2004 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck |
| Note | Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
| Nominal voltage | 29 VDC ±5% |
| Voltage range | 24 VDC -15% / +20% |
| Quantity | 2 safe input channel pairs |
| Variant | Type A |
| Input type | Differential input |
| Digital converter resolution | 24-bit |
| Conversion time | See chapter "I/O update time". |
| Output format | SAFEINT |
| Load | Up to hardware revision D3: 230 to 420 Ω, hardware revision E0 or later: 185 to 245 Ω |
| Input protection | Protection against external supply voltages and overcurrent |
| Open-circuit detection | Yes, using software |
| Voltage | Max. 30.5 V |
| Conversion procedure | Sigma-delta |
| 0.5 to <4 mA | <0.735 µA/°C |
| 4 to 25 mA | <0.735 µA/°C |
| DC | >70 dB |
| 50 Hz | >70 dB |
| Common-mode range | Between the inputs ±50 V |
| Nonlinearity | <0.003% |
| Measurement range | 0.5 to 25 mA |
| Hardware | First-order low-pass filter / cutoff frequency 500 Hz |
| Software | Sinc3 filter |
| Resolution | 1 µA/LSB |
| Overload detection | Yes, using software |
| Channel - Ground | 500 VDC |
| Cat. 3 | 0.184 mA |
| Cat. 4 | 0.49 mA |
| Filter time | Configurable between 1 and 66.7 ms |
| Nominal output current | Max. 60 mA |
| Short-circuit proof | Yes, continuous |
| Sensor power supply - Channel | No |
| Sensor power supply - Sensor power supply | Yes |
| RDS(on) | 50 Ω |
| Behavior on short circuit | Voltage cutoff |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 40°C |
| Derating | See section "Derating". |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Pitch | 25+0.2 mm |