产品概览
| 库存情况 | 需按需确认 |
| 分类 | Digital inputs |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
X20cDI4760 何时可以发货?
X20cDI4760 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X20cDI4760 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X20cDI4760 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X20cDI4760 安排当日快递或专车加急配送。
4 digital inputsInput module for NAMUR encodersOpen line and short circuit detectionEach input can be used as a counter input The module is used to transfer digital signals from NAMUR encoders according to EN 60947-5-6. In addition to NAMUR encoders, normal switches can also be used.
技术规格
Specifications
| I/O module | 4 NAMUR inputs, special function |
| B&R ID code | 0xE221 |
| Status indicators | I/O function per channel, open-circuit and short-circuit detection per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Short circuit | Yes, using LED status indicator and software |
| Open circuit | Yes, using LED status indicator and software |
| Bus | 0.01 W |
| Internal I/O | 1.5 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user's manual)FTZÚ 09 ATEX 0083X |
| UL | cULus E115267Industrial control equipment |
| HazLoc | cCSAus 244665Process control equipmentfor hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C)Humidity: B (up to 100%)Vibration: B (4 g)EMC: B (bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33BTemperature: 5 - 55°CVibration: 4 gEMC: Bridge and open deck |
| Quantity | 4 |
| Signal form | Symmetrical square waves or corresponding minimum pulse duration |
| Evaluation | Each positive edge, cyclic counter |
| Counter size | 8-bit |
| 1 input active | ≤310 µs |
| 2 inputs active | ≤450 µs |
| 3 inputs active | ≤570 µs |
| 4 inputs active | ≤735 µs |
| Open-circuit detection | <350 µA |
| Input circuit | For NAMUR encoder per EN 60947-5-6 |
| Insulation voltage between channel and bus | 500 Veff |
| Short-circuit detection | >7 mA |
| Open-circuit voltage | 8.05 V ±0.33% |
| Switching amplifier internal resistance | 1 kΩ ±1% |
| Max. short-circuit current | 8.2 mA |
| Area | 1.2 mA to 2.1 mA |
| Switching hysteresis | Typ. 300 µA |
| Electrical isolation | Channel isolated from busChannel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | See section "Derating". |
| Starting temperature | Yes, -40°C |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | Up to 100%, condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately. |
| Pitch | 12.5+0.2 mm |
12个月保修适用于所有全新库存
3个月保修适用于二手及翻新零部件
30天退货未使用零部件退货免收上架费
全球发货全球快速可追踪配送