产品概览
| 库存情况 | 需按需确认 |
| 分类 | Temperature measurement |
| 生命周期状态 | active |
| 保修 | 12个月(全新)· 3个月(二手/翻新) |
发货与库存
X20ATC402 何时可以发货?
X20ATC402 属于按需采购产品——请申请报价,我们会为这一具体单品确认准确的库存情况及发货时间。
可以亲自到店提取 X20ATC402 吗?
可以在我们位于荷兰格罗宁根的仓库安排自提——请在下单前联系我们,确认库存情况并预约提货时间。
是否提供快递服务?
可以——在为 X20ATC402 申请报价时告诉我们,我们会在回复中附上快递发货选项。
我们的工厂停产了,急需这个零部件——你们能帮忙吗?
如遇紧急故障,请直接致电 +31 (0)50-7110348 或发邮件至 sales@partnerplc.com 联系我们——我们可根据库存情况及目的地,为 X20ATC402 安排当日快递或专车加急配送。
6 channels for thermocouplesFor sensor types J, K, N, S, B, R, E, C, T, raw value measurementIntegrated terminal temperature compensation2x PT1000 sensor integrated in the terminal (X20TB1E)2x external PT1000 sensor can be connected (X20TB1F)Configurable filter timeConfigurable resolutionNetTime timestamp: Moment of measurement The module is equipped with 6 inputs for J, K, N, S, B, R, E, C and T thermocouple sensors.This module can also be equipped with the X20TB1E thermocouple terminal block with integrated PT1000 temperature sensors. This makes it possible to achieve optimal terminal temperature compensation.
技术规格
Specifications
| I/O module | 6 inputs for thermocouples |
| B&R ID code | 0xBB99 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Bus | 0.01 W |
| Internal I/O | 0.85 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck |
| KC | Yes |
| Input | Thermocouple |
| Digital converter resolution | 16-bit |
| Filter time | Configurable between 1 and 200 ms |
| N channels | (n + 2) * 4 * x ms |
| 1 channel | x ms |
| Output format | INT |
| Type J: Fe-CuNi | ±0.0033 %/°C |
| Type K: NiCr-Ni | ±0.0042 %/°C |
| Type N: NiCrSi-NiSi | ±0.0048 %/°C |
| Type S: PtRh10-Pt | ±0.0123 %/°C |
| Type B: PtRh30-PtRh6 | ±0.0166 %/°C |
| Type R: PtRh13-Pt | ±0.0109 %/°C |
| Type E: NiCr-CuNi | ±0.003 %/°C |
| Type C: WRe5-WRe26 | ±0.0062 %/°C |
| Type T: Cu-CuNi | ±0.011%/°C |
| Terminal temperature | ±0.004% |
| Voltage | ±0.003 %/°C |
| Sensor standard | EN 60584 |
| Sensor temperature | 1 LSB = 0.1°C or 0.01°C |
| Range undershoot | 0x8001 or 0x80000001 |
| Range overshoot | 0x7FFF or 0x7FFFFFFF |
| Open circuit | 0x7FFF or 0x7FFFFFFF |
| Open inputs | 0x7FFF or 0x7FFFFFFF |
| General fault | 0x8000 or 0x80000000 |
| Conversion procedure | Sigma-delta |
| Linearization method | Internal |
| Permissible input signal | Max. ±15 V |
| Input filter | First-order low-pass filter / cutoff frequency 500 Hz |
| Gain | ±0.04% |
| Channel | ±0.004% |
| Operating modes | Internal/remote or external |
| Basic accuracy at 25°C not taking Pt1000 sensor into account | ±0.06% |
| With natural convection | ±1.5°C after 20 min |
| With artificial convection | ±3°C after 20 min |
| DC | >100 dB |
| 50 Hz | >100 dB |
| 60 Hz | >100 dB |
| Common-mode range | ±14 V |
| Crosstalk between channels | <-70 dB |
| Between channel and bus | 500 Veff |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB1E for internal/remote terminal temperature compensation separately. Order 1x terminal block X20TB1F for external terminal temperature compensation separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2 mm |