Specification : |
Short description
I/O module
|
4 safe type A digital outputs, with current monitoring, 24 VDC, 2 A, OSSD <500 µs
|
General information
B&R ID code
|
0x2007
|
System requirements
|
|
Automation Studio
|
3.0.71 or later
|
Automation Runtime
|
2.95 or later
|
SafeDESIGNER
|
2.58 or later
|
Safety Release
|
1.1 or later
|
mapp Technology Package
|
mapp Safety 5.7.0 or later
|
Status indicators
|
I/O function per channel, operating state, module status
|
Diagnostics
|
|
Module run/error
|
Yes, using LED status indicator and software
|
Outputs
|
Yes, using LED status indicator and software
|
Blackout mode
|
|
Scope
|
Module
|
Function
|
Module functionality
|
Standalone mode
|
No
|
Max. I/O cycle time
|
800 µs
|
Power consumption
|
|
Bus
|
0.25 W
|
Internal I/O
|
1.3 W
|
Additional power dissipation caused by actuators (resistive) [W]
|
2.16
|
Electrical isolation
|
|
Channel - Bus
|
Yes
|
Channel - Channel
|
No
|
Certifications
|
|
CE
|
Yes
|
UKCA
|
Yes
|
Functional safety
|
cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
|
Functional safety
|
IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
|
Functional safety
|
EN 50156-1:2004
|
ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
|
UL
|
cULus E115267 Industrial control equipment
|
HazLoc
|
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
|
DNV
|
Temperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
|
LR
|
ENV1
|
KR
|
Yes
|
ABS
|
Yes
|
BV
|
EC21B Temperature: 5 - 45°C Vibration: 0.7 g EMC: Bridge and open deck
|
EAC
|
Yes
|
KC
|
Yes
|
Safety characteristics
EN ISO 13849-1:2015
|
|
Category
|
Cat. 3 if parameter "Disable OSSD = Yes - Warning", Cat. 4 if parameter "Disable OSSD = No"
|
PL
|
PL d if parameter "Disable OSSD = Yes - Warning", PL e if parameter "Disable OSSD = No"
|
DC
|
>60% if parameter "Disable OSSD = Yes - Warning", >94% if parameter "Disable OSSD = No"
|
Mission time
|
Max. 20 years
|
IEC 61508:2010, IEC 61511:2004, EN 62061:2013
|
|
SIL CL
|
SIL 2 if parameter "Disable OSSD = Yes - Warning", SIL 3 if parameter "Disable OSSD = No"
|
SFF
|
>60% if parameter "Disable OSSD = Yes - Warning", >90% if parameter "Disable OSSD = No"
|
PFH / PFHd
|
|
openSAFETY wired
|
Negligible
|
openSAFETY wireless
|
<1*10-14 * Number of openSAFETY packets per hour
|
Proof test interval (PT)
|
20 years
|
Safe digital outputs
|
|
EN ISO 13849-1:2015
|
|
MTTFD per channel
|
100 years if parameter "Disable OSSD = Yes - Warning", 2500 years if parameter "Disable OSSD = No"
|
IEC 61508:2010, IEC 61511:2004, EN 62061:2013
|
|
PFH / PFHd per channel
|
<5*10-8 if parameter "Disable OSSD = Yes - Warning", <1*10-10 if parameter "Disable OSSD = No"
|
PFD per channel
|
<1*10-3 if parameter "Disable OSSD = Yes - Warning", <2*10-5 if parameter "Disable OSSD = No"
|
I/O power supply
Nominal voltage
|
24 VDC
|
Voltage range
|
24 VDC -15% / +20%
|
Integrated protection
|
Reverse polarity protection
|
Safe digital outputs
Quantity
|
4
|
Variant
|
FET, 1x positive switching, 1x negative switching, type A, output level readable, open-circuit detection
|
Nominal voltage
|
24 VDC
|
Nominal output current
|
2 A
|
Total nominal current
|
5 A
|
Output protection
|
See section "Inrush current behavior for output channels".
|
Braking voltage when switching off inductive loads
|
Max. 90 VDC
|
Open-circuit detection
|
Via internal current measurement, output current <10 mA: Signal "CurrentOK" = FALSE, output current 10 to 50 mA: Signal "CurrentOK" = Undefined, output current >50 mA: Signal "CurrentOK" = TRUE
|
Error detection time
|
1 s
|
Insulation voltage between channel and bus
|
500 Veff
|
Peak short-circuit current
|
See section "Inrush current behavior for output channels".
|
Leakage current when the output is switched off
|
<10 µA
|
RDS(on)
|
240 mΩ
|
Switching voltage
|
I/O power supply minus voltage drop due to RDS(on)
|
Max. switching frequency
|
See section "Inrush current behavior for output channels".
|
Test pulse length
|
Max. 500 µs
|
Time between two test pulses
|
Min. 49.5 ms
|
Max. capacitive load
|
100 nF
|
Operating conditions
Mounting orientation
|
|
Horizontal
|
Yes
|
Vertical
|
Yes
|
Installation elevation above sea level
|
0 to 2000 m, no limitation
|
Degree of protection per EN 60529
|
IP20
|
Ambient conditions
Temperature
|
|
Operation
|
|
Horizontal mounting orientation
|
0 to 60°C
|
Vertical mounting orientation
|
0 to 50°C
|
Derating
|
See section "Derating".
|
Storage
|
-40 to 85°C
|
Transport
|
-40 to 85°C
|
Relative humidity
|
|
Operation
|
5 to 95%, non-condensing
|
Storage
|
5 to 95%, non-condensing
|
Transport
|
5 to 95%, non-condensing
|
Mechanical properties
Note
|
Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
|
Pitch
|
25+0.2 mm
|
|