Specification : |
Short description
I/O module
|
8 safe type A digital inputs, 4 pulse outputs, 24 VDC, SafeLOGIC-X technology
|
General information
B&R ID code
|
0xE757
|
System requirements
|
|
Automation Studio
|
4.0 or later
|
Automation Runtime
|
B4.25 or later
|
SafeDESIGNER
|
4.2.0 or later
|
Safety Release
|
1.10 or later
|
mapp Technology Package
|
mapp Safety 5.7.0 or later
|
Status indicators
|
I/O function per channel, operating state, module status
|
Diagnostics
|
|
Module run/error
|
Yes, using LED status indicator and software
|
Inputs
|
Yes, using LED status indicator and software
|
Max. I/O cycle time
|
1 ms
|
Power consumption
|
|
Bus
|
0.4 W
|
Internal I/O
|
2.5 W
|
Additional power dissipation caused by actuators (resistive) [W]
|
0.8
|
Electrical isolation
|
|
Channel - Bus
|
Yes
|
Channel - Channel
|
No
|
Certifications
|
|
CE
|
Yes
|
UKCA
|
Yes
|
Functional safety
|
cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013
|
Functional safety
|
IEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
|
Functional safety
|
EN 50156-1:2004
|
ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
|
UL
|
cULus E115267 Industrial control equipment
|
DNV
|
In preparation
|
EAC
|
Yes
|
Safety characteristics
EN ISO 13849-1:2015
|
|
Category
|
Cat. 3 when using individual input channels, Cat. 4 when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels
|
PL
|
PL e
|
DC
|
>94%
|
Mission time
|
Max. 20 years
|
IEC 61508:2010, IEC 61511:2004, EN 62061:2013
|
|
SIL CL
|
SIL 3
|
SFF
|
>90%
|
PFH / PFHd
|
|
openSAFETY wired
|
Negligible
|
openSAFETY wireless
|
<1*10-14 * Number of openSAFETY packets per hour
|
Proof test interval (PT)
|
20 years
|
Safe digital inputs
|
|
EN ISO 13849-1:2015
|
|
MTTFD per channel
|
100 years when using individual input channels, 2500 years when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels
|
IEC 61508:2010, IEC 61511:2004, EN 62061:2013
|
|
PFH / PFHd per channel
|
<1*10-10
|
PFD per channel
|
<2*10-5
|
Functionality
Communication with each other
|
Communication only possible with SafeLOGIC controller X20(c)SL81xx Max. 1 active SafeLOGIC-X controller per standard CPU (e.g. X20(c)CPxxxx)
|
Support for Safe Commissioning Options
|
|
BOOL
|
64
|
INT
|
16
|
UINT
|
16
|
DINT
|
16
|
UDINT
|
16
|
SafeMOTION support
|
Yes
|
Max. number of SafeMOTION axes
|
6, depends on the data width of the modules used
|
Timing precision
|
Time * 0.05 + Cycle time of the safety application
|
Shortest task class cycle time
|
2 ms
|
Max. number of SafeNODEs
|
10, depends on the data width of the modules used
|
Data exchange between CPU and SafeLOGIC controller
|
|
Max. total data width for each direction
|
16 bytes
|
Max. number of data points for each direction
|
|
BOOL
|
96
|
INT
|
8
|
UINT
|
8
|
DINT
|
4
|
UDINT
|
4
|
Data exchange between SafeDOMAIN and SafeDOMAIN
|
|
Use as Managing SafeDOMAIN
|
Yes, starting with mapp Safety 5.10.0 and hardware upgrade 2.2.1.0
|
Use as Connected SafeDOMAIN
|
Yes, starting with mapp Safety 5.13.0, hardware upgrade 2.4.0.0 and Automation Runtime A4.90
|
Max. total data width for each direction
|
8 bytes
|
Max. total number of data points for each direction
|
4
|
Max. number of data points for each direction
|
|
BOOL
|
16
|
INT
|
2
|
UINT
|
2
|
DINT
|
2
|
UDINT
|
2
|
Max. number of linked Managing SafeDOMAINs
|
0, starting with mapp Safety 5.13.0, hardware upgrade 2.4.0.0 and Automation Runtime A4.90: 1
|
Limit values for SafeDESIGNER application
Max. resources available for SafeDESIGNER info window entries
|
|
FB instances
|
256
|
Marker memory
|
5120 bytes (0x1400)
|
Stack memory
|
4096 bytes
|
Memory for safe input data
|
128 bytes, 68 bytes of which are usable for modules
|
Memory for safe output data
|
64 bytes
|
Memory for standard input data
|
64 bytes
|
Memory for standard output data
|
64 bytes
|
Marker count
|
256
|
Additional SafeDESIGNER limit values
|
|
Max. number of function block types
|
64
|
Max. number of force variables
|
8
|
Max. number of variable with variable status
|
128
|
I/O power supply
Nominal voltage
|
24 VDC
|
Voltage range
|
24 VDC -15% / +20%
|
Integrated protection
|
Reverse polarity protection
|
Safe digital inputs
Quantity
|
8
|
Variant
|
Type A
|
Nominal voltage
|
24 VDC
|
Input characteristics per EN 61131-2
|
Type 1
|
Input filter
|
|
Hardware
|
≤150 µs
|
Software
|
Configurable between 0 and 500 ms
|
Input circuit
|
Sink
|
Input voltage
|
24 VDC -15% / +20%
|
Input current at 24 VDC
|
Min. 2 mA to max. 3.28 mA
|
Input resistance
|
Min. 7.33 kΩ
|
Error detection time
|
100 ms
|
Insulation voltage between channel and bus
|
500 Veff
|
Switching threshold
|
|
Low
|
<5 VDC
|
High
|
>15 VDC
|
Line length between signal source (pulse output or external signal) and input
|
Max. 60 m with unshielded line Max. 400 m with shielded line
|
Pulse outputs
Quantity
|
4
|
Variant
|
Push-Pull
|
Nominal output current
|
50 mA
|
Output protection
|
Shutdown of individual channels in the event of overload or short circuit
|
Peak short-circuit current
|
0.5 A for 120 µs
|
Short-circuit current
|
15 mAeff
|
Leakage current when the output is switched off
|
0.1 mA
|
RDS(on)
|
80 Ω
|
Switching voltage
|
I/O power supply minus voltage drop due to RDS(on)
|
Total nominal current
|
200 mA
|
Operating conditions
Mounting orientation
|
|
Horizontal
|
Yes
|
Vertical
|
Yes
|
Installation elevation above sea level
|
0 to 2000 m, no limitation
|
Degree of protection per EN 60529
|
IP20
|
Ambient conditions
Temperature
|
|
Operation
|
|
Horizontal mounting orientation
|
0 to 60°C
|
Vertical mounting orientation
|
0 to 50°C
|
Derating
|
See section "Derating".
|
Storage
|
-40 to 85°C
|
Transport
|
-40 to 85°C
|
Relative humidity
|
|
Operation
|
5 to 95%, non-condensing
|
Storage
|
5 to 95%, non-condensing
|
Transport
|
5 to 95%, non-condensing
|
Mechanical properties
Note
|
Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module (single-width) separately.
|
Pitch
|
12.5+0.2 mm
|
|