Specification : |
Short description
Interfaces
|
1x RS232, 1x Ethernet, 1x POWERLINK V1/V2, 2x USB, 1x X2X Link
|
System module
|
CPU
|
General information
B&R ID code
|
0x1F19
|
Cooling
|
Fanless with derating (see operating conditions) Replaceable fan for full temperature range Fan monitored
|
Status indicators
|
CPU function, overtemperature, Ethernet, POWERLINK, CompactFlash, battery
|
Diagnostics
|
|
Battery
|
Yes, using LED status indicator and software
|
CPU function
|
Yes, using LED status indicator
|
CompactFlash
|
Yes, using LED status indicator
|
Ethernet
|
Yes, using LED status indicator
|
POWERLINK
|
Yes, using LED status indicator
|
Overtemperature
|
Yes, using LED status indicator
|
Fans
|
Yes, using software
|
Support
|
|
ACOPOS support
|
Yes
|
Visual Components support
|
Yes
|
Power consumption without memory card, interface module and USB
|
13.5 W
|
Internal power consumption of X2X Link and I/O power supply
|
|
Bus
|
1.42 W
|
Internal I/O
|
0.6 W
|
Additional power dissipation caused by actuators (resistive) [W]
|
-
|
Electrical isolation
|
|
IF1 - IF2
|
Yes
|
IF1 - IF3
|
Yes
|
IF1 - IF4
|
No
|
IF1 - IF5
|
No
|
IF1 - IF6
|
Yes
|
IF2 - IF4
|
Yes
|
IF2 - IF5
|
Yes
|
IF3 - IF4
|
Yes
|
IF3 - IF5
|
Yes
|
IF4 - IF5
|
No
|
IF4 - IF6
|
Yes
|
IF5 - IF6
|
Yes
|
PLC - IF1
|
No
|
PLC - IF2
|
Yes
|
PLC - IF3
|
Yes
|
PLC - IF4
|
No
|
PLC - IF5
|
No
|
PLC - IF6
|
Yes
|
Certifications
|
|
CE
|
Yes
|
UKCA
|
Yes
|
ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
|
UL
|
cULus E115267 Industrial control equipment
|
HazLoc
|
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
|
DNV
|
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
|
LR
|
ENV1
|
KR
|
Yes
|
ABS
|
Yes
|
BV
|
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
|
EAC
|
Yes
|
KC
|
Yes
|
CPU and X2X Link power supply
Input voltage
|
24 VDC -15% / +20%
|
Input current
|
Max. 2.2 A
|
Fuse
|
Integrated, cannot be replaced
|
Reverse polarity protection
|
Yes
|
X2X Link power supply output
Nominal output power
|
7 W
|
Parallel connection
|
Yes
|
Redundant operation
|
Yes
|
Input I/O power supply
Input voltage
|
24 VDC -15% / +20%
|
Fuse
|
Required line fuse: Max. 10 A, slow-blow
|
Output I/O power supply
Nominal output voltage
|
24 VDC
|
Permissible contact load
|
10 A
|
Power supply - General information
Status indicators
|
Overload, operating status, module status, RS232 data transfer
|
Diagnostics
|
|
RS232 data transfer
|
Yes, using LED status indicator
|
Module run/error
|
Yes, using LED status indicator and software
|
Overload
|
Yes, using LED status indicator and software
|
Electrical isolation
|
|
I/O supply - I/O power supply
|
No
|
CPU/X2X Link supply - CPU/X2X Link power supply
|
Yes
|
Controller
CompactFlash slot
|
1
|
Real-time clock
|
Nonvolatile, resolution 1 s, -20 to 20 ppm accuracy at 25°C
|
FPU
|
Yes
|
Processor
|
|
Type
|
Celeron 650
|
L2 cache
|
256 kB
|
L1 cache for data and program code
|
2x 16 kB
|
Integrated I/O processor
|
Processes I/O data points in the background
|
Modular interface slots
|
3
|
Remanent variables
|
Max. 256 kB
|
Shortest task class cycle time
|
200 µs
|
Typical instruction cycle time
|
0.0034 µs
|
Data buffering
|
|
Battery monitoring
|
Yes
|
Lithium battery
|
At least 3 years
|
Standard memory
|
|
RAM
|
64 MB SDRAM
|
User RAM
|
1 MB SRAM
|
Interfaces
Interface IF1
|
|
Type
|
RS232
|
Variant
|
Connection via 12-pin terminal block TB12
|
Transfer rate
|
Max. 115.2 kbit/s
|
Interface IF2
|
|
Type
|
Ethernet
|
Variant
|
Shielded RJ45
|
Line length
|
Max. 100 m between 2 stations (segment length)
|
Transfer rate
|
10/100 Mbit/s
|
Interface IF3
|
|
Fieldbus
|
POWERLINK V1/V2
|
Type
|
100BASE-T (ANSI/IEEE 802.3)
|
Variant
|
Shielded RJ45
|
Line length
|
Max. 100 m between 2 stations (segment length)
|
Transfer rate
|
100 Mbit/s
|
Interface IF4
|
|
Type
|
USB 1.1
|
Variant
|
Type A
|
Max. output current
|
0.5 A
|
Interface IF5
|
|
Type
|
USB 1.1
|
Variant
|
Type A
|
Max. output current
|
0.5 A
|
Interface IF6
|
|
Type
|
X2X Link master
|
Quantity
|
1
|
Operating conditions
Mounting orientation
|
|
Horizontal
|
Yes
|
Vertical
|
Yes
|
Installation elevation above sea level
|
|
0 to 2000 m
|
No limitation
|
>2000 m
|
Reduction of ambient temperature by 0.5°C per 100 m
|
Degree of protection per EN 60529
|
IP20
|
Ambient conditions
Temperature
|
|
Operation
|
|
Horizontal mounting orientation
|
0 to 55°C, fanless: 0 to 45°C
|
Vertical mounting orientation
|
0 to 55°C, fanless not permitted
|
Derating
|
-
|
Storage
|
-25 to 70°C
|
Transport
|
-25 to 70°C
|
Relative humidity
|
|
Operation
|
5 to 95%, non-condensing
|
Storage
|
5 to 95%, non-condensing
|
Transport
|
5 to 95%, non-condensing
|
Mechanical properties
Note
|
Order application memory (CompactFlash) separately. Backup battery included in delivery X20 end cover plate (right) included in delivery 12-pin X20 terminal block included in delivery Interface module slot covers included in delivery
|
Dimensions
|
|
Width
|
200 mm
|
Height
|
99 mm
|
Depth
|
85 mm
|
|