Specification : |
Short description
Interfaces
|
1x RS232, 1x Ethernet, 1x POWERLINK (V1/V2), 2x USB, 1x X2X Link
|
System module
|
Controller
|
General information
B&R ID code
|
0xC3AE
|
Cooling
|
Fanless
|
Status indicators
|
CPU function, Ethernet, POWERLINK, CompactFlash, battery
|
Diagnostics
|
|
Battery
|
Yes, using LED status indicator and software
|
CPU function
|
Yes, using LED status indicator
|
CompactFlash
|
Yes, using LED status indicator
|
Ethernet
|
Yes, using LED status indicator
|
POWERLINK
|
Yes, using LED status indicator
|
Temperature
|
Yes, using software register
|
Support
|
|
Controller redundancy
|
No
|
Storage health data support
|
Yes
|
ACOPOS support
|
Yes
|
Visual Components support
|
Yes
|
Power consumption without interface module and USB
|
8.8 W
|
Power consumption for X2X Link power supply
|
1.42 W
|
Power consumption
|
|
Internal I/O
|
0.6 W
|
Additional power dissipation caused by actuators (resistive) [W]
|
-
|
Certifications
|
|
CE
|
Yes
|
UKCA
|
Yes
|
ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X
|
UL
|
cULus E115267 Industrial control equipment
|
HazLoc
|
cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
|
DNV
|
Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
|
LR
|
ENV1
|
KR
|
Yes
|
ABS
|
Yes
|
BV
|
EC33B Temperature: 5 - 55°C Vibration: 4 g EMC: Bridge and open deck
|
EAC
|
Yes
|
KC
|
Yes
|
CPU and X2X Link power supply
Input voltage
|
24 VDC -15% / +20%
|
Input current
|
Max. 1.5 A
|
Fuse
|
Integrated, cannot be replaced
|
Reverse polarity protection
|
Yes
|
X2X Link power supply output
Nominal output power
|
7 W
|
Parallel connection
|
Yes
|
Redundant operation
|
Yes
|
Input I/O power supply
Input voltage
|
24 VDC -15% / +20%
|
Fuse
|
Required line fuse: Max. 10 A, slow-blow
|
Output I/O power supply
Nominal output voltage
|
24 VDC
|
Permissible contact load
|
10 A
|
Power supply - General information
Status indicators
|
Overload, operating status, module status, RS232 data transfer
|
Diagnostics
|
|
RS232 data transfer
|
Yes, using LED status indicator
|
Module run/error
|
Yes, using LED status indicator and software
|
Overload
|
Yes, using LED status indicator and software
|
Electrical isolation
|
|
I/O supply - I/O power supply
|
No
|
CPU/X2X Link supply - CPU/X2X Link power supply
|
Yes
|
Controller
CompactFlash slot
|
1
|
Real-time clock
|
Nonvolatile, resolution 1 s, -10 to 10 ppm accuracy at 25°C
|
FPU
|
Yes
|
Processor
|
|
Type
|
Atom E640T
|
Clock frequency
|
1 GHz
|
L1 cache
|
|
Data code
|
24 kB
|
Program code
|
32 kB
|
L2 cache
|
512 kB
|
Integrated I/O processor
|
Processes I/O data points in the background
|
Modular interface slots
|
1
|
Remanent variables
|
Max. 256 kB
|
Shortest task class cycle time
|
200 µs
|
Typical instruction cycle time
|
0.0044 µs
|
Data buffering
|
|
Battery monitoring
|
Yes
|
Lithium battery
|
Min. 2 years at 23°C ambient temperature
|
Standard memory
|
|
RAM
|
256 MB DDR2 SDRAM
|
User RAM
|
1 MB SRAM
|
Interfaces
Interface IF1
|
|
Signal
|
RS232
|
Variant
|
Connection via 12-pin terminal block X20TB12
|
Max. distance
|
900 m
|
Transfer rate
|
Max. 115.2 kbit/s
|
Interface IF2
|
|
Signal
|
Ethernet
|
Variant
|
1x RJ45 shielded
|
Line length
|
Max. 100 m between 2 stations (segment length)
|
Transfer rate
|
10/100/1000 Mbit/s
|
Transfer
|
|
Physical layer
|
10BASE-T/100BASE-TX/1000BASE-T
|
Half-duplex
|
Yes
|
Full-duplex
|
Yes
|
Autonegotiation
|
Yes
|
Auto-MDI/MDIX
|
Yes
|
Interface IF3
|
|
Fieldbus
|
POWERLINK (V1/V2) managing or controlled node
|
Type
|
Type 4
|
Variant
|
1x RJ45 shielded
|
Line length
|
Max. 100 m between 2 stations (segment length)
|
Transfer rate
|
100 Mbit/s
|
Transfer
|
|
Physical layer
|
100BASE-TX
|
Half-duplex
|
Yes
|
Full-duplex
|
POWERLINK mode: No / Ethernet mode: Yes
|
Autonegotiation
|
Yes
|
Auto-MDI/MDIX
|
Yes
|
Interface IF4
|
|
Type
|
USB 1.1/2.0
|
Variant
|
Type A
|
Max. output current
|
0.5 A
|
Interface IF5
|
|
Type
|
USB 1.1/2.0
|
Variant
|
Type A
|
Max. output current
|
0.5 A
|
Interface IF6
|
|
Fieldbus
|
X2X Link master
|
Electrical properties
Electrical isolation
|
Ethernet (IF2), POWERLINK (IF3) and X2X (IF6) isolated from each other, from other interfaces and from PLC
|
Operating conditions
Mounting orientation
|
|
Horizontal
|
Yes
|
Vertical
|
Yes
|
Installation elevation above sea level
|
|
0 to 2000 m
|
No limitation
|
>2000 m
|
Reduction of ambient temperature by 0.5°C per 100 m
|
Degree of protection per EN 60529
|
IP20
|
Ambient conditions
Temperature
|
|
Operation
|
|
Horizontal mounting orientation
|
-25 to 60°C
|
Vertical mounting orientation
|
-25 to 50°C
|
Derating
|
See section "Derating".
|
Storage
|
-40 to 85°C
|
Transport
|
-40 to 85°C
|
Relative humidity
|
|
Operation
|
5 to 95%, non-condensing
|
Storage
|
5 to 95%, non-condensing
|
Transport
|
5 to 95%, non-condensing
|
Mechanical properties
Note
|
Order application memory (CompactFlash) separately Backup battery included in delivery X20 end cover plate (right) included in delivery 12-pin X20 terminal block included in delivery Interface module slot covers included in delivery
|
Dimensions
|
|
Width
|
150 mm
|
Height
|
99 mm
|
Depth
|
85 mm
|
Weight
|
400 g
|
|